1794-TBNF Procurement Questions
What termination style does the 1794-TBNF use?
It is a screw clamp, fused NEMA-style terminal base.
How many fused terminals does it provide and what fuse size do they take?
It provides eight 5 x 20 mm fused screw terminals with a cover for I/O wiring.
Which module is it shipped with fuses for, and can it be used with other modules?
It is shipped with fuses for the 1794-OA8 module; it can be used to fuse the 1794-OM8 and 1794-OW8 modules with a replacement fuse.
What fuse rating is fitted as shipped?
It is shipped with a 1.6 A, 250V AC slow blow fuse suitable for the 1794-OA8 AC output module.
What wire size does this terminal base accept?
0.34…3.3 mm2 (22…12 AWG) solid or stranded copper wire rated at 75 °C (167 °F) or greater, with 1.2 mm (3/64 in.) insulation max.
What is the operating temperature range?
-20…+55 °C (-4…+131 °F).
- Wire size (common terminal base characteristic)
- 0.34…3.3 mm2 (22…12 AWG) solid or stranded copper wire rated at 75 °C (167 °F) or greater; 1.2 mm (3/64 in.) insulation max
- Dimensions (HxWxD) (common terminal base characteristic)
- 94 x 94 x 69 mm (3.7 x 3.7 x 2.7 in)
- Termination type
- Screw clamp, fused NEMA-style
- Purpose
- Provides eight 5 x 20 mm fused screw terminals with a cover for I/O wiring – shipped with fuses for the 1794-OA8 module; can be used to fuse the 1794-OM8 and 1794-OW8 modules with a replacement fuse
- Fitted fuses (table footnote (4))
- Contains eight 5 x 20 mm fuses (one for each even-numbered terminal – 0…14 on row B); shipped with 1.6 A, 250V AC slow blow fuse suitable for the 1794-OA8 AC output module (Littlefuse PN23901.6, A-B PN94171304, SAN-O PNSD6-1.6A)
- Temperature, operating
- -20…+55 °C (-4…+131 °F)
Technical specifications are based on the linked manufacturer reference.