SM560-S-FD-4 Procurement Questions
How many PROFIsafe networks can the SM560-S-FD-4 handle?
The SM560-S-FD-4 provides F-Device functionality for up to 4 PROFIsafe networks, with PROFIsafe V2 F-Host and F-Device via PROFINET.
What safety integrity and performance levels are stated for this safety CPU?
The filed catalog data states SIL3 (IEC 61508:2010, IEC 62061, IEC 61511) and PL e (ISO 13849-1).
How much user program and data memory does the SM560-S-FD-4 have?
User program memory is 1.3 MB. User data memory is printed as 1 MB (thereof 120 kB saved) in the data sheet and as 1.0 MB thereof 120 kB saved in the main catalog.
What supply voltage and operating temperature range apply?
Process and supply voltage (without ripple) is 24 (-15 %, +20 %) V DC, and the operating temperature range is 0 ... +60 °C.
Can the module be mounted vertically?
Mounting is horizontal, or vertical with derating (maximal operating temperature reduced to +40 °C).
Is a separate software license required to program this safety CPU?
Yes: the AC500-S Safety PLC programming license needs to be purchased as an additional feature of Automation Builder.
- Ordering data (data sheet)
- 1SAP 286 100 R0001 — Safety module - CPU, safety related module up to SIL 3 with F-Device functionality for up to 4 PROFIsafe networks (part number spacing as printed in the data sheet ordering data)
- Safety protocol (main catalog)
- PROFIsafe V2 F-Host and F-Device (for 4 PROFIsafe networks) via PROFINET
- User program memory
- 1.3 MB
- User data memory (data sheet joint row)
- 1 MB (thereof 120 kB saved)
- Integrated data memory (main catalog printing)
- 1.0 MB thereof 120 kB saved (integrated data memory as printed in the main catalog technical data, second column; the data sheet prints the joint row as '1 MB' thereof 120 kB saved)
- Performance level (PL)
- PL e (ISO 13849-1)
- Safety integrity level (SIL)
- SIL3 (IEC 61508:2010, IEC 62061, IEC 61511)
- Cycle time - binary
- 0.05 µs/instruction
- Cycle time - word
- 0.06 µs/instruction
- Cycle time - floating-point
- 0.50 µs/instruction
- Max. safety extension modules on I/O bus
- 10
- Max. centralized digital inputs/outputs
- 160 digital inputs (SIL2) / 80 (SIL3); 80 digital outputs (SIL3)
- Max. centralized analog inputs
- 40 analog inputs (SIL2) / 20 (SIL3)
- Max. decentralized inputs/outputs
- On PROFINET: up to 128 stations with up to 10 safety extension modules
- Ethernet interface
- Via AC500 CPU or PROFINET coupler
- Programming interface
- Via AC500 CPU
- Process and supply voltage
- 24 (-15 %, +20 %) V DC (process and supply voltage without ripple, as printed in the data sheet)
- Operating temperature
- 0 ... +60 °C
- Device dimensions WxHxD
- 28 x 135 x 75 mm (device dimensions WxHxD as printed in the data sheet; not package dimensions)
- Device weight (data sheet printing)
- ~ 100 g (device weight as printed in the data sheet; not a shipping weight)
- Weight per piece (main catalog ordering printing)
- 0.100 kg (weight per piece as printed in the main catalog ordering data; not a shipping weight)
- Degree of protection
- IP 20
- MTBF
- 168 years
- Certifications
- CE, cUL (further certifications at www.abb.com/plc)
- Mounting
- horizontal (or vertical with derating — maximal operating temperature reduced to +40 °C)
- Programming license (Automation Builder)
- AC500-S Safety PLC programming license needs to be purchased as an additional feature of Automation Builder
Technical facts follow the exact manufacturer model table or named reference. Conflicting or unestablished numeric claims are withheld. Weight appears only in the specifications table with source basis; no shipping-weight estimate is inferred.