SM560-S Procurement Questions
Does the SM560-S act as a PROFIsafe F-Host, an F-Device, or both?
It is an F-Host only: PROFIsafe V2 F-Host via PROFINET. F-Device functionality is not part of this base type.
How much user program memory does the SM560-S provide?
1 MB of user program memory. Its user data memory is printed as 1 MB (thereof 120 kB saved) in the data sheet, and the main catalog prints the integrated data memory as 1 MB thereof 120 KB saved.
Which safety ratings does the SM560-S carry?
SIL3 (IEC 61508:2010, IEC 62061, IEC 61511) and performance level PL e (ISO 13849-1).
How many safety extension modules and centralized I/O can be used with this safety CPU?
Up to 10 safety extension modules on the I/O bus. Centralized digital I/O is up to 160 digital inputs (SIL2) / 80 (SIL3) and 80 digital outputs (SIL3); centralized analog inputs are up to 40 (SIL2) / 20 (SIL3).
What are the supply voltage and operating temperature conditions?
Process and supply voltage (without ripple) is 24 (-15 %, +20 %) V DC, and the operating temperature is 0 ... +60 °C.
Is additional software needed to program the SM560-S?
Yes: the AC500-S Safety PLC programming license needs to be purchased as an additional feature of Automation Builder.
- Ordering data (data sheet)
- 1SAP 280 000 R0001 — Safety module - CPU, safety related module up to SIL 3 (part number spacing as printed in the data sheet ordering data)
- Safety protocol (main catalog)
- PROFIsafe V2 F-Host via PROFINET
- User program memory
- 1 MB
- User data memory (data sheet joint row)
- 1 MB (thereof 120 kB saved)
- Integrated data memory (main catalog printing)
- 1 MB thereof 120 KB saved (integrated data memory as printed in the main catalog technical data, first column; the data sheet prints the joint row as '1 MB' thereof 120 kB saved)
- Performance level (PL)
- PL e (ISO 13849-1)
- Safety integrity level (SIL)
- SIL3 (IEC 61508:2010, IEC 62061, IEC 61511)
- Cycle time - binary
- 0.05 µs/instruction
- Cycle time - word
- 0.06 µs/instruction
- Cycle time - floating-point
- 0.50 µs/instruction
- Max. safety extension modules on I/O bus
- 10
- Max. centralized digital inputs/outputs
- 160 digital inputs (SIL2) / 80 (SIL3); 80 digital outputs (SIL3)
- Max. centralized analog inputs
- 40 analog inputs (SIL2) / 20 (SIL3)
- Max. decentralized inputs/outputs
- On PROFINET: up to 128 stations with up to 10 safety extension modules
- Ethernet interface
- Via AC500 CPU or PROFINET coupler
- Programming interface
- Via AC500 CPU
- Process and supply voltage
- 24 (-15 %, +20 %) V DC (process and supply voltage without ripple, as printed in the data sheet)
- Operating temperature
- 0 ... +60 °C
- Device dimensions WxHxD
- 28 x 135 x 75 mm (device dimensions WxHxD as printed in the data sheet; not package dimensions)
- Device weight (data sheet printing)
- ~ 100 g (device weight as printed in the data sheet; not a shipping weight)
- Weight per piece (main catalog ordering printing)
- 0.100 kg (weight per piece as printed in the main catalog ordering data; not a shipping weight)
- Degree of protection
- IP 20
- MTBF
- 168 years
- Certifications
- CE, cUL (further certifications at www.abb.com/plc)
- Mounting
- horizontal (or vertical with derating — maximal operating temperature reduced to +40 °C)
- Programming license (Automation Builder)
- AC500-S Safety PLC programming license needs to be purchased as an additional feature of Automation Builder
Technical facts follow the exact manufacturer model table or named reference. Conflicting or unestablished numeric claims are withheld. Weight appears only in the specifications table with source basis; no shipping-weight estimate is inferred.