FX5-4AD-TC-ADP Procurement Questions
Which thermocouple types can the FX5-4AD-TC-ADP accept?
It accepts K, J, T, B, R, and S thermocouple types.
What temperature measuring range does it support for type K thermocouples?
For type K, the temperature measuring range is -200 to +1200 °C.
What accuracy applies to type K at an ambient temperature of 25±5 °C?
At an ambient temperature of 25±5 °C, type K accuracy is ±3.7 °C over -100 to +1200 °C, ±4.9 °C over -150 to -100 °C, and ±7.2 °C over -200 to -150 °C.
Which CPU modules is this adapter applicable to?
It is applicable to FX5U CPU module Ver. 1.040 or later and FX5UC CPU module Ver. 1.040 or later.
How are the input channels isolated from each other and from the CPU module?
A photocoupler is used between the input terminal and the CPU module, and there is non-isolation between input channels.
- Product type
- Thermocouple temperature sensor input expansion adapter; measures 4 channels of temperature
- Number of analog input points
- 4 points (4 channels)
- Usable thermocouple types
- K, J, T, B, R, S
- Temperature measuring range, type K
- -200 to +1200 °C
- Temperature measuring range, type J
- -40 to +750 °C
- Temperature measuring range, type T
- -200 to +350 °C
- Temperature measuring range, type B
- 600 to 1700 °C
- Temperature measuring range, type R
- 0 to 1600 °C
- Temperature measuring range, type S
- 0 to 1600 °C
- Digital output value
- 16-bit signed binary
- Digital output value ranges by thermocouple type
- K: -2000 to +12000; J: -400 to +7500; T: -2000 to +3500; B: 6000 to 17000; R: 0 to 16000; S: 0 to 16000
- Accuracy, type K, ambient temperature 25±5 °C
- ±3.7 °C (-100 to +1200 °C); ±4.9 °C (-150 to -100 °C); ±7.2 °C (-200 to -150 °C) at ambient temperature 25±5 °C
- Accuracy, type K, ambient temperature -20 to 55 °C
- ±6.5 °C (-100 to +1200 °C); ±7.5 °C (-150 to -100 °C); ±8.5 °C (-200 to -150 °C) at ambient temperature -20 to 55 °C
- Accuracy, type J, ambient temperature 25±5 °C
- ±2.8 °C at ambient temperature 25±5 °C
- Accuracy, type J, ambient temperature -20 to 55 °C
- ±4.5 °C at ambient temperature -20 to 55 °C
- Accuracy, type T, ambient temperature 25±5 °C
- ±3.1 °C (0 to 350 °C); ±4.1 °C (-100 to 0 °C); ±5.0 °C (-150 to -100 °C); ±6.7 °C (-200 to -150 °C) at ambient temperature 25±5 °C
- Accuracy, type T, ambient temperature -20 to 55 °C
- ±4.1 °C (0 to 350 °C); ±5.1 °C (-100 to 0 °C); ±6.0 °C (-150 to -100 °C); ±7.7 °C (-200 to -150 °C) at ambient temperature -20 to 55 °C
- Accuracy, type B, ambient temperature 25±5 °C
- ±3.5 °C at ambient temperature 25±5 °C
- Accuracy, type B, ambient temperature -20 to 55 °C
- ±6.5 °C at ambient temperature -20 to 55 °C
- Accuracy, type R, ambient temperature 25±5 °C
- ±3.7 °C at ambient temperature 25±5 °C
- Accuracy, type R, ambient temperature -20 to 55 °C
- ±6.5 °C at ambient temperature -20 to 55 °C
- Accuracy, type S, ambient temperature 25±5 °C
- ±3.7 °C at ambient temperature 25±5 °C
- Accuracy, type S, ambient temperature -20 to 55 °C
- ±6.5 °C at ambient temperature -20 to 55 °C
- Resolution
- 0.1 °C (K, J, T); 0.1 to 0.3 °C (B, R, S)
- Conversion speed
- Approx. 85 ms/channel
- Isolation method
- Photocoupler between input terminal and CPU module; non-isolation between input channels
- Number of occupied I/O points
- 0 point
- Internal power supply, A/D conversion circuit
- 24 V DC 20 mA (internal supply from CPU module)
- Internal power supply, interface
- 5 V DC 10 mA (internal supply from CPU module)
- Dielectric withstand voltage
- 500 V AC for one minute (between all external terminals and ground terminal of CPU module)
- Insulation resistance
- 10 MΩ or higher (by 500 V DC insulation resistance tester)
- Applicable CPU module
- FX5U CPU module Ver. 1.040 or later; FX5UC CPU module Ver. 1.040 or later
- Mass (unit weight, as printed)
- Approx. 0.1 kg
- Terminal block type
- European type terminal block
Technical specifications follow the cited manufacturer references.