The Siemens SIMATIC S5 CP 521 SI Communications Processor, model 6ES5521-8MA22, is a specialized interface module engineered for serial communication in industrial automation environments. This processor facilitates efficient data exchange between Siemens S5 PLCs and external devices such as programming terminals, printers, or supervisory systems. Operating over standard RS-232C or RS-422 interfaces, it supports both point-to-point and multi-point configurations, making it ideal for distributed control systems. The CP 521 SI includes comprehensive diagnostic functions to monitor link integrity and transmission errors, ensuring high reliability in factory floor or process control settings. Its compact design allows direct mounting in the S5 rack, and it is fully compatible with the SIMATIC S5 software ecosystem for configuration and operation.
| Parameter | Specification |
|---|---|
| Product Type | Communications Processor |
| Model Number | 6ES5521-8MA22 |
| System Compatibility | Siemens SIMATIC S5 |
| Interface Type | RS-232C / RS-422 (selectable) |
| Communication Protocol | Point-to-point, Multi-point (SI protocol) |
| Data Rate | Up to 19.2 kbps |
| Transmission Distance | Up to 1200 m (RS-422) / 15 m (RS-232C) |
| Diagnostic Functions | Built-in error detection, line monitoring |
| Power Supply | 5 V DC from S5 backplane bus |
| Current Consumption | Typical 0.8 A |
| Operating Temperature | 0 °C to +60 °C |
| Storage Temperature | -20 °C to +80 °C |
| Protection Class | IP20 |
| Dimensions (W x H x D) | 40 mm x 125 mm x 120 mm |
| Weight | Approx. 0.3 kg |
The Siemens data sheet lists it as a serial interface for S5-90U/-95U/-100U and ET 200U.
No. This is the CP 521 SI communications processor with order number 6ES5 521-8MA22. The CP 521 BASIC communications module has a different order number, 6ES5 521-8MB12, and is not this product.
The serial interface is V.24/TTY passive (active). Transmission is asynchronous with a 10-bit or 11-bit character frame, at a transmission rate of 110 to 9600 baud.
For V.24 the permissible cable length is 15 m (49.2 ft.); for TTY it is max. 1000 m (3281 ft.).
The implemented drivers are the ASCII driver (transparent), the ASCII driver in interpreting mode I and interpreting mode II, the 3964(R) driver, the SINEC L1 driver as master (point-to-point) and as slave, and the terminal driver.
Yes. A separate manual is available and can be ordered under order number 6ES5 998-1UD21.
Specifications follow the cited manufacturer documents and the approved model-specific conditions. Equipment mass is not a shipping-weight estimate.