1769-BOOLEAN Procurement Questions
What input voltage range does the 1769-BOOLEAN accept?
The inputs are 24V AC sinking, with an operating voltage range of 10…30V DC @ 30 °C (86 °F) and 10…26V DC @ 60 °C (140 °F).
How much current can each output point carry?
Current per point, max is 0.5 A @ 60 °C (140 °F) and 1.0 A @ 30 °C (86 °F).
What digital filter settings are available for the inputs?
Both the off-to-on and on-to-off digital filters offer 0 s, 100 μs, 200 μs, 500 μs, 1 ms, 2 ms, 4 ms, and 8 ms.
What wire size and wire type does the module accept?
Wire size is (22…14 AWG) solid and (22…16 AWG) stranded, with wire type Cu-90 °C (194 °F).
How is the module isolated?
Input isolation is verified by one of the following dielectric tests: 1200V AC for 1 s or 1697V DC for 1 s, input point to bus, with 75V DC working voltage (IEC Class 2 reinforced insulation); output isolation is verified by one of the following dielectric tests: 1200V AC for 1 s or 1697V DC for 1 s, output point to bus, with 75V DC working voltage (IEC Class 2 reinforced insulation).
What are the terminal and retaining screw torque values?
Terminal screw torque is 0.68 N·m (6 lb·in) and retaining screw torque is 0.46 N·m (4.1 lb·in).
- Current draw @ 5.1V
- 220 mA
- Current draw @ 24V
- 0 mA
- Heat dissipation, max
- 3.55 W
- Closed loop time
- Output on-state current > 5 mA: 100 μs max Output on-state current < 5 mA: 150 μs max
- Isolation voltage
- Verified by one of the following dielectric tests: 1200V AC for 1 s or 1697V DC for 1 s 75V DC working voltage (IEC Class 2 reinforced insulation)
- Weight, approx (product weight as published)
- 282 g (0.625 lb)
- Dimensions (HxWxD), approx
- 118 x 35 x 87 mm (4.65 x 1.38 x 3.43 in.) Height with mounting tabs 138 mm (5.43 in.)
- Slot width
- 1
- Module location
- DIN rail or panel mount
- Power supply
- 1769-PA2, 1769-PB2, 1769-PA4, 1769-PB4
- Power supply distance rating
- 8 modules
- Terminal screw torque
- 0.68 N·m (6 lb·in)
- Retaining screw torque
- 0.46 N·m (4.1 lb·in)
- Wire size
- (22…14 AWG) solid (22…16 AWG) stranded
- Wire type
- Cu-90 °C (194 °F)
- Vendor ID code
- 1
- Product type code
- 109
- Product code
- 37
- Enclosure type rating
- None (open-style)
- Inputs
- 8 real 8 virtual
- Voltage category
- 24V AC sinking
- Operating voltage range
- 10…30V DC @ 30 °C (86 °F) 10…26V DC @ 60 °C (140 °F)
- Digital filter, off to on
- 0 s, 100 μs, 200 μs, 500 μs, 1 ms, 2 ms, 4 ms, 8 ms
- Digital filter, on to off
- 0 s, 100 μs, 200 μs, 500 μs, 1 ms, 2 ms, 4 ms, 8 ms
- Input delay, off to on
- 10 μs
- Input delay, on to off
- 10 μs
- Current draw @ 5.1V
- 115 mA
- Off-state voltage, max
- 5V DC
- Off-state current, max
- 1.5 mA
- On-state voltage, min
- 10V DC
- On-state current, min
- 2 mA (1)
- Inrush current, max
- 250 mA
- Input impedance, max
- 2.0 kΩ @ 24V DC 2.3 kΩ @ 30V DC
- IEC input compatibility
- Type 1+
- Isolation voltage
- Verified by one of the following dielectric tests: 1200V AC for 1 s or 1697V DC for 1 s, input point to bus 75V DC working voltage (IEC Class 2 reinforced insulation)
- input, the inrush current is reduced to 35 mA. In this configuration the minimum on-state voltage incr
- eases to 92V AC. Before adding the resistor in a hazardous environment, be sure to consider the
- operating temperature of the resistor and the temperature limits of the environment. The operating tem
- perature of the resistor must remain below the temperature limit of the environment.
- Outputs
- 4
- Voltage category
- 24V DC, sourcing
- Operating voltage range
- 20.4…26.4V DC
- Output delay, on
- 10 μs, output on-state current > 5 mA (footnote (1) of Table 92: Triac outputs turn on and off at AC line zero cross.)
- Output delay, off
- 10 μs, output on-state current > 5 mA (footnote (1) of Table 92: Triac outputs turn on and off at AC line zero cross.)
- Off-state leakage current, max
- 1.0 mA @ 26.4V DC (footnote (2) of Table 92: To limit the effects of leakage current through solid state outputs, a loading resistor can be connected in parallel with your load. For 120V AC operation, use a 15 kΩ, 2 W resistor. For 240V AC operation use a 5 kΩ, 5 W resistor.)
- On-state current, max
- 1.0 mA
- On-state voltage drop, max
- 1.0V DC @ 1 A
- Current per point, max
- 0.5 A @ 60 °C (140 °F) 1.0 A @ 30 °C (86 °F)
- Surge current
- 2 A for 10 ms, repeatable every 2 s (footnote (3) of Table 92: Connecting surge suppressors across your external load will extend the life of the triac outputs.)
- Isolation voltage
- Verified by one of the following dielectric tests: 1200V AC for 1 s or 1697V DC for 1 s, output point to bus 75V DC working voltage (IEC Class 2 reinforced insulation)