Allen-Bradley 1769-BOOLEAN Boolean control module

Series#: AllenBradley

Product Details

  • Allen-Bradley 1769-BOOLEAN Boolean control module
  • Device type: Boolean control module; Physical inputs: 8, 24 V DC sinking
  • Physical outputs: 4, 24 V DC sourcing

Specification

Allen-Bradley 1769-BOOLEAN — Boolean control module.

Technical Specifications

SpecificationDetails
ManufacturerAllen-Bradley
Catalog number1769-BOOLEAN
Device typeBoolean control module
Physical inputs8, 24 V DC sinking
Physical outputs4, 24 V DC sourcing
Manufacturer approximate product weight0.282 kg — packaging inclusion not specified
1769-TD006H-EN-P (November 2023), p. 55

Ordering & Compatibility

Do not count virtual Boolean points as configurable physical input/output terminals.

Match the complete catalog number, hardware series, installed configuration and required accessories before ordering. Unit condition, package contents, delivery and warranty must be confirmed in the quotation.

1769-BOOLEAN Procurement Questions

What input voltage range does the 1769-BOOLEAN accept?

The inputs are 24V AC sinking, with an operating voltage range of 10…30V DC @ 30 °C (86 °F) and 10…26V DC @ 60 °C (140 °F).

How much current can each output point carry?

Current per point, max is 0.5 A @ 60 °C (140 °F) and 1.0 A @ 30 °C (86 °F).

What digital filter settings are available for the inputs?

Both the off-to-on and on-to-off digital filters offer 0 s, 100 μs, 200 μs, 500 μs, 1 ms, 2 ms, 4 ms, and 8 ms.

What wire size and wire type does the module accept?

Wire size is (22…14 AWG) solid and (22…16 AWG) stranded, with wire type Cu-90 °C (194 °F).

How is the module isolated?

Input isolation is verified by one of the following dielectric tests: 1200V AC for 1 s or 1697V DC for 1 s, input point to bus, with 75V DC working voltage (IEC Class 2 reinforced insulation); output isolation is verified by one of the following dielectric tests: 1200V AC for 1 s or 1697V DC for 1 s, output point to bus, with 75V DC working voltage (IEC Class 2 reinforced insulation).

What are the terminal and retaining screw torque values?

Terminal screw torque is 0.68 N·m (6 lb·in) and retaining screw torque is 0.46 N·m (4.1 lb·in).

Current draw @ 5.1V
220 mA
Current draw @ 24V
0 mA
Heat dissipation, max
3.55 W
Closed loop time
Output on-state current > 5 mA: 100 μs max Output on-state current < 5 mA: 150 μs max
Isolation voltage
Verified by one of the following dielectric tests: 1200V AC for 1 s or 1697V DC for 1 s 75V DC working voltage (IEC Class 2 reinforced insulation)
Weight, approx (product weight as published)
282 g (0.625 lb)
Dimensions (HxWxD), approx
118 x 35 x 87 mm (4.65 x 1.38 x 3.43 in.) Height with mounting tabs 138 mm (5.43 in.)
Slot width
1
Module location
DIN rail or panel mount
Power supply
1769-PA2, 1769-PB2, 1769-PA4, 1769-PB4
Power supply distance rating
8 modules
Terminal screw torque
0.68 N·m (6 lb·in)
Retaining screw torque
0.46 N·m (4.1 lb·in)
Wire size
(22…14 AWG) solid (22…16 AWG) stranded
Wire type
Cu-90 °C (194 °F)
Vendor ID code
1
Product type code
109
Product code
37
Enclosure type rating
None (open-style)
Inputs
8 real 8 virtual
Voltage category
24V AC sinking
Operating voltage range
10…30V DC @ 30 °C (86 °F) 10…26V DC @ 60 °C (140 °F)
Digital filter, off to on
0 s, 100 μs, 200 μs, 500 μs, 1 ms, 2 ms, 4 ms, 8 ms
Digital filter, on to off
0 s, 100 μs, 200 μs, 500 μs, 1 ms, 2 ms, 4 ms, 8 ms
Input delay, off to on
10 μs
Input delay, on to off
10 μs
Current draw @ 5.1V
115 mA
Off-state voltage, max
5V DC
Off-state current, max
1.5 mA
On-state voltage, min
10V DC
On-state current, min
2 mA (1)
Inrush current, max
250 mA
Input impedance, max
2.0 kΩ @ 24V DC 2.3 kΩ @ 30V DC
IEC input compatibility
Type 1+
Isolation voltage
Verified by one of the following dielectric tests: 1200V AC for 1 s or 1697V DC for 1 s, input point to bus 75V DC working voltage (IEC Class 2 reinforced insulation)
input, the inrush current is reduced to 35 mA. In this configuration the minimum on-state voltage incr
eases to 92V AC. Before adding the resistor in a hazardous environment, be sure to consider the
operating temperature of the resistor and the temperature limits of the environment. The operating tem
perature of the resistor must remain below the temperature limit of the environment.
Outputs
4
Voltage category
24V DC, sourcing
Operating voltage range
20.4…26.4V DC
Output delay, on
10 μs, output on-state current > 5 mA (footnote (1) of Table 92: Triac outputs turn on and off at AC line zero cross.)
Output delay, off
10 μs, output on-state current > 5 mA (footnote (1) of Table 92: Triac outputs turn on and off at AC line zero cross.)
Off-state leakage current, max
1.0 mA @ 26.4V DC (footnote (2) of Table 92: To limit the effects of leakage current through solid state outputs, a loading resistor can be connected in parallel with your load. For 120V AC operation, use a 15 kΩ, 2 W resistor. For 240V AC operation use a 5 kΩ, 5 W resistor.)
On-state current, max
1.0 mA
On-state voltage drop, max
1.0V DC @ 1 A
Current per point, max
0.5 A @ 60 °C (140 °F) 1.0 A @ 30 °C (86 °F)
Surge current
2 A for 10 ms, repeatable every 2 s (footnote (3) of Table 92: Connecting surge suppressors across your external load will extend the life of the triac outputs.)
Isolation voltage
Verified by one of the following dielectric tests: 1200V AC for 1 s or 1697V DC for 1 s, output point to bus 75V DC working voltage (IEC Class 2 reinforced insulation)

Technical specifications are based on the linked manufacturer references.

Unmatched Customer Service

After Hours Shipping

Real Time Order Tracking

Flexible Delivery Options

Intact Technical Supports

What Does Our Clients Say

Mitsubishi MR-J4

Laura Navas

Great product!

2019/12/01

Keyence sensor

EQDR SALES

Original and fast!

2020/02/22

Need Professional Tech Support or a Quote?

  • Our senior engineers provide 1-on-1 selection & configuration advice
  • 100% genuine products guaranteed with rapid global delivery
UP
WhatsApp