The 1771-OAD is a high-performance digital output module from the Allen-Bradley PLC-5 family, engineered for precise control in demanding industrial environments. This module provides 16 isolated 120V AC outputs, ideal for switching loads such as contactors, motor starters, and indicator lights. With its robust construction and optical isolation, the 1771-OAD ensures reliable operation even in electrically noisy settings, making it a trusted choice for manufacturing, process control, and material handling systems. Each output channel features a dedicated LED for quick diagnostics, and the module supports standard PLC-5 backplane communication for seamless integration. Whether upgrading an existing system or building a new automation network, the 1771-OAD delivers consistent performance and long service life.
| Parameter | Specification |
|---|---|
| Part Number | 1771-OAD |
| Product Type | PLC-5 Digital Output Module |
| Number of Outputs | 16 |
| Output Voltage | 120V AC (47-63 Hz) |
| Output Current per Point | 2.0 A max (resistive load) |
| Total Output Current per Module | 8.0 A max |
| Output Type | Triac (AC switching) |
| Isolation | Optically isolated, 1500V AC between outputs and backplane |
| Response Time (ON) | 1.0 ms typical |
| Response Time (OFF) | 1.0 ms typical |
| Backplane Current (5V DC) | 0.35 A |
| Backplane Current (24V DC) | 0.0 A |
| Operating Temperature | 0°C to 60°C (32°F to 140°F) |
| Storage Temperature | -40°C to 85°C (-40°F to 185°F) |
| Humidity | 5% to 95% non-condensing |
| Vibration Resistance | 5 g Standard Models 10-500 Hz |
| Shock Resistance | 30 g (11 ms duration) |
| LED Indicators | One per output (ON when output is active) |
| Module Location | Any slot in 1771 I/O chassis |
| Weight | Approx. 0.45 kg (1.0 lb) |
| Certifications | UL, CSA, CE |
| Compatible Processors | PLC-5/10, 5/20, 5/30, 5/40, 5/80 |
The module is compatible with all chassis except 1771-A1, 1771-A2 and 1771-A4 chassis. The specifications list module location as 1771-A1B through -A4B or later I/O chassis, 1771-AM1, -AM2 chassis.
The output voltage range is 10 to 138V ac @ 47 - 63Hz.
The output current rating is 2A per output - not to exceed 8A per module.
The minimum load current is 5mA per output.
The standard field wiring arm is 1771-WH; the 1771-WHF (fused) is optional.
It uses a 10A, 250V rectifier fuse (1/4 x 1-1/4 inch), Littelfuse PN 322010.
Specifications follow the cited manufacturer documents and the approved model-specific conditions. Equipment mass is not a shipping-weight estimate.