  • SICK UE48-2OS2D2 safety relay, manufacturer part number 6024915.
  • Operates from 24 VAC/DC at A1/A2, with a permissible supply range of 20.4–26.4 VAC/DC.
  • Provides 2 normally open safety-relevant enabling current paths and 1 normally closed signaling path that is not safety-relevant.
  • Uses positively driven contacts, with a response time of ≤ 25 ms for K1/K2.
  • Compact housing measuring 22.5 x 114 x 96.5 mm (W x H x D).

Specification

Technical Specifications

SpecificationDetails
ManufacturerSICK
Model / order referenceUE48-2OS2D2
Device type and manufacturer part numberSafety relay; SICK part number 6024915
Supply voltage at A1/A224 VAC/DC; permissible 20.4–26.4 VAC/DC
Control voltage at S11/S21/S3322 VDC; minimum 17.4 VDC
Enabling current paths2 normally open paths, safety-relevant
Signaling current path1 normally closed path, not safety-relevant
Contact typePositively driven contacts
Response time≤ 25 ms for K1/K2
Dimensions (W x H x D)22.5 x 114 x 96.5 mm
Manufacturer device weight0.21 kg

SICK UE48-2OS2D2 Safety relay

What supply voltage does the UE48-2OS2D2 require at A1/A2, and what is the control voltage at S11/S21/S33?

The UE48-2OS2D2 is supplied at 24 VAC/DC at terminals A1/A2, with a permissible supply range of 20.4–26.4 VAC/DC. This is separate from the control voltage at S11/S21/S33, which is 22 VDC nominal with a minimum of 17.4 VDC.

How many safety enabling paths and signaling paths does the UE48-2OS2D2 provide?

The UE48-2OS2D2 has 2 normally open enabling current paths that are safety-relevant, plus 1 normally closed signaling current path that is not safety-relevant. The contacts are positively driven.

What response time is specified for the UE48-2OS2D2?

The specified response time for K1/K2 on the UE48-2OS2D2 is ≤ 25 ms.

What are the housing dimensions of the UE48-2OS2D2?

The UE48-2OS2D2 housing measures 22.5 x 114 x 96.5 mm (width x height x depth).

Device type and manufacturer part number
Safety relay; SICK part number 6024915
Supply voltage at A1/A2
24 VAC/DC; permissible 20.4–26.4 VAC/DC
Control voltage at S11/S21/S33
22 VDC; minimum 17.4 VDC
Enabling current paths
2 normally open paths, safety-relevant
Signaling current path
1 normally closed path, not safety-relevant
Contact type
Positively driven contacts
Response time
≤ 25 ms for K1/K2
Dimensions (W x H x D)
22.5 x 114 x 96.5 mm

Technical specifications and answers reviewed against the exact-model SICK manufacturer data sheet. Range, supply, output and test-condition qualifications are retained.

Unmatched Customer Service

After Hours Shipping

Real Time Order Tracking

Flexible Delivery Options

Intact Technical Supports

What Does Our Clients Say

Mitsubishi MR-J4

Laura Navas

Great product!

2019/12/01

Keyence sensor

EQDR SALES

Original and fast!

2020/02/22

Need Professional Tech Support or a Quote?

  • Our senior engineers provide 1-on-1 selection & configuration advice
  • 100% genuine products guaranteed with rapid global delivery
UP
WhatsApp