6EP1332-1SH71 Procurement Questions
Does 6EP1332-1SH71 accept any voltage from 85 to 264 V AC?
No. The data sheet specifies two discrete input bands, 85 ... 132 V AC and 176 ... 264 V AC, and marks wide-range input as No; supply voltage is 120 V/230 V with automatic range selection.
What output voltage and current does 6EP1332-1SH71 provide, and can the voltage be adjusted?
The output is a controlled, isolated DC voltage rated 24 V DC at a rated output current of 2.5 A (rated range 0 ... 2.5 A), with supplied active power typical 60 W. Output voltage adjustable is marked No.
How does 6EP1332-1SH71 behave on a short circuit or short-term overload?
The output is short-circuit proof with a constant current characteristic typical 2.65 A, and the enduring short-circuit current RMS value is typical 2.7 A. Short-term overload current is typical 6 A both on short-circuiting during start-up and at short-circuit during operation, with a duration of overloading capability of 100 ms in each case.
What are the input current, inrush current and fuse protection of 6EP1332-1SH71?
Rated input current is 1.2 A at 120 V and 0.67 A at 230 V. Inrush current limitation at 25 °C is 13 A maximum with a duration of 3 ms maximum and an I2t value of 0.5 A²·s maximum. The internal fuse is printed T 3,15 A/250 V (not accessible), and the recommended feeder miniature circuit breaker is 16 A characteristic B or 10 A characteristic C.
What ambient temperature range and protection class apply to 6EP1332-1SH71?
Ambient temperature during operation is 0 ... 60 °C with natural convection; during transport and during storage it is -40 ... +85 °C. The protection class is IP20, and the environmental category according to IEC 60721 is climate class 3K3, 5 ... 95 % relative humidity, no condensation.
How is 6EP1332-1SH71 mounted and wired?
It snaps onto DIN rail EN 60715 35x7.5/15, with wall mounting also possible; S7 rail mounting is marked No. Wiring is by screw terminals: L, N, PE at the input with 1 screw terminal each for 0.5 ... 2.5 mm², and L+, M at the output with 2 screw terminals each for 0.5 ... 2.5 mm²; there are no terminals for auxiliary contacts.
- Existing partial state - record absent from the remaining-gaps register (no register posture, full binding); one published English GEO row carrying only six facts; this wave captures the missing standard; all six published values agree with the data sheet on every overlapping point
- The record is absent from the remaining-gaps register - no register posture, full binding. Its current published state is partial (below-standard): the verified production receipt records one published English GEO row for it (published, revision 1) whose fact list covers only the product type (SIMATIC PM1207 stabilized power supply), the input supply (single-phase 120/230 VAC with automatic range selection), the permitted AC input bands (85–132 VAC or 176–264 VAC, not continuous wide-range input), the output (24 VDC, 2.5 A, 60 W), output-voltage adjustment (not adjustable) and the short-circuit characteristic (constant-current protection). The rest of the data-sheet specification - rated input current, inrush limiting, mains buffering, output tolerance and ripple, closed-loop control, overload behaviour, efficiency and power loss, safety and EMC data, approvals, ambient conditions, connection method, enclosure dimensions and net weight - is absent from the published row; this wave captures exactly that missing standard from the manufacturer's per-model data sheet. The published row's six values agree with the data sheet on every overlapping point, so the new evidence extends rather than contradicts the published row.
- Shipping status in the audit inventory - UNDETERMINED_UNTIL_FULL_SPEC_CAPTURE; the data sheet prints no shipping weight, so shipping weight remains GAP_NOT_APPROVED and package dimensions remain GAP
- In the shipping-weight audit's published-English inventory this record's shipping status stands recorded as UNDETERMINED_UNTIL_FULL_SPEC_CAPTURE. The Siemens data sheet prints no shipping weight, so shipping weight remains GAP_NOT_APPROVED after this wave; package dimensions are likewise not printed and remain GAP.
- Model attestation - Siemens data sheet headed "SIMATIC PM 1207/1AC/24VDC/2.5A" for Article No. 6EP1332-1SH71, attested by the printed header inside the document itself, not by any file name
- Siemens AG data sheet for the SIMATIC S7-1200 power module PM1207, Article No. 6EP1332-1SH71, headed "SIMATIC PM 1207/1AC/24VDC/2.5A" and described as a stabilized power supply with input 120/230 V AC and output DC 24 V/2.5 A. The article number is attested by the printed header inside the document itself, not by any file name.
- Input supply - 1-phase AC network; supply voltage 120 V/230 V with automatic range selection; band 1: 85 ... 132 V AC; band 2: 176 ... 264 V AC; wide-range input: No; line frequency 50/60 Hz, range 47 ... 63 Hz
- Input: 1-phase AC network; supply voltage 120 V/230 V with automatic range selection; input voltage band 1: 85 ... 132 V AC; input voltage band 2: 176 ... 264 V AC; wide-range input: No; line frequency 50/60 Hz, range 47 ... 63 Hz.
- Mains buffering and overvoltage - buffering time 20 ms minimum at Vin = 93/187 V; overvoltage overload capability 2.3 x Vin rated for 1.3 ms
- Mains buffering time at rated output current in the event of power failure: 20 ms minimum, at Vin = 93/187 V; overvoltage overload capability 2.3 x Vin rated for 1.3 ms.
- Rated input current, inrush limiting and fuse - 1.2 A at 120 V, 0.67 A at 230 V; inrush maximum 13 A, duration maximum 3 ms, I2t maximum 0.5 A2s; internal fuse T 3,15 A/250 V as printed (comma decimal form, flagged, not normalised); recommended feeder miniature circuit breaker 16 A characteristic B or 10 A characteristic C
- Rated input current: 1.2 A at 120 V, 0.67 A at 230 V. Inrush current limitation at 25 °C: 13 A maximum, duration 3 ms maximum, I2t value 0.5 A²·s maximum. Internal fuse protection: T 3,15 A/250 V (not accessible), as printed with the comma decimal form; recommended feeder miniature circuit breaker: 16 A characteristic B or 10 A characteristic C.
- Output voltage - controlled, isolated DC voltage; rated output voltage 24 V DC; output voltage adjustable: No
- Output: controlled, isolated DC voltage; rated output voltage 24 V DC (output 1 rated value 24 V); output voltage adjustable: No.
- Output current and power - rated output current 2.5 A, rated range 0 ... 2.5 A; supplied active power typical 60 W
- Rated output current 2.5 A, rated range 0 ... 2.5 A; supplied active power typical 60 W.
- Signalling and switch-on behaviour - green LED for 24 V OK; no overshoot of Vout (soft start); response delay maximum 6 s (2 s at 230 V, 6 s at 120 V); voltage increase time typical 10 ms
- Display: green LED for 24 V OK. Behaviour of the output voltage when switching on: no overshoot of Vout (soft start). Response delay maximum 6 s (2 s at 230 V, 6 s at 120 V); voltage increase time of the output voltage typical 10 ms.
- Output tolerance and ripple - relative overall tolerance 3 %; relative control precision 0.1 % (input fluctuation) / 0.2 % (load fluctuation); residual ripple maximum 150 mV; voltage peak maximum 240 mV
- Relative overall tolerance of the output voltage 3 %; relative control precision 0.1 % on slow fluctuation of input voltage and 0.2 % on slow fluctuation of ohm loading; residual ripple maximum 150 mV; voltage peak maximum 240 mV.
- Closed-loop control - relative control precision 0.3 % at rapid input-voltage fluctuation of +/- 15 % (typical); 3 % at resistive load step 50/100/50 % (typical); setting time typical 5 ms for both load-step directions
- Closed-loop control: relative control precision of the output voltage 0.3 % with rapid fluctuation of the input voltage by +/- 15 % (typical); 3 % for a resistive load step of 50/100/50 % (typical); setting time typical 5 ms for load steps 50 to 100 % and 100 to 50 %.
- Short-term overload and parallel operation - short-term overload current typical 6 A for 100 ms on start-up short-circuit and on operating short-circuit; bridging of equipment Yes; up to 2 parallel-switched units for increasing the power
- Short-term overload current typical 6 A both on short-circuiting during start-up and at short-circuit during operation, with a duration of overloading capability of 100 ms in each case. Bridging of equipment: Yes; up to 2 parallel-switched units for increasing the power.
- Protection and monitoring - overvoltage protection design < 33 V; output short-circuit proof Yes, constant current characteristic typical 2.65 A; enduring short-circuit current RMS typical 2.7 A
- Overvoltage protection design: < 33 V. Output is short-circuit proof: Yes; short-circuit protection design: constant current characteristic, typical 2.65 A; enduring short-circuit current RMS value typical 2.7 A.
- Efficiency and power loss - efficiency 83 %; power loss typical 12 W at rated output voltage and rated output current
- Efficiency 83 %; power loss at rated output voltage and rated output current typical 12 W.
- Safety and isolation - galvanic isolation between input and output Yes; output voltage SELV, ES1 (IEC 62368-1), DVC As (IEC 61204-7); protection class I; leakage current maximum 3.5 mA; protection class IP20
- Galvanic isolation between input and output: Yes; the output voltage is SELV, ES1 (IEC 62368-1), DVC As (IEC 61204-7); operating resource protection class Class I; leakage current maximum 3.5 mA; protection class IP20.
- EMC - emitted interference EN 55022 Class B; mains harmonics limitation not applicable; interference immunity EN 61000-6-2
- EMC: emitted interference to EN 55022 Class B; mains harmonics limitation not applicable; interference immunity to EN 61000-6-2.
- Approvals (general) - CE marking Yes; UL approval Yes: cULus-Listed (UL 508, CSA C22.2 No. 107.1) File E197259 and cURus-Recognized (UL 60950-1, CSA C22.2 No. 60950-1) File E151273; UKCA marking Yes; EAC approval Yes; NEC Class 2 Yes, according to UL1310, File E151273
- Approvals: CE marking Yes; UL approval Yes - cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259, and cURus-Recognized (UL 60950-1, CSA C22.2 No. 60950-1), File E151273; UKCA marking Yes; EAC approval Yes; NEC Class 2 Yes, according to UL1310, File E151273.
- Approvals (hazardous environments and marine) and MTBF - CB certificate Yes; MTBF at 40 °C: 1 492 537 h; IECEx Yes (Ex nA nC IIC T4 Gc); ATEX Yes ((EX) II 3G Ex ec nC IIC T4 Gc); UL hazloc Yes; UKEX Yes; CCC for hazardous zone Yes; FM registration Yes (Class I, Div. 2, Group ABCD, T4); shipbuilding approval Yes with ABS, BV, DNV, LRS and NK all Yes
- CB certificate Yes. MTBF at 40 °C: 1 492 537 h. Hazardous-environment approvals: IECEx Yes (IECEx Ex nA nC IIC T4 Gc); ATEX Yes (ATEX (EX) II 3G Ex ec nC IIC T4 Gc); UL hazloc approval Yes; UKEX Yes; CCC for hazardous zone according to GB standard Yes; FM registration Yes (Class I, Div. 2, Group ABCD, T4). Shipbuilding approval Yes, with marine classification approvals from ABS, BV, DNV, LRS and NK all marked Yes.
- Ambient conditions - operation 0 ... 60 °C with natural convection; transport -40 ... +85 °C; storage -40 ... +85 °C; environmental category IEC 60721 climate class 3K3, 5 ... 95 % relative humidity, no condensation
- Ambient temperature during operation 0 ... 60 °C with natural convection; during transport -40 ... +85 °C; during storage -40 ... +85 °C. Environmental category according to IEC 60721: climate class 3K3, 5 ... 95 % relative humidity, no condensation.
- Connection method - screw terminals: at the input L, N, PE with 1 screw terminal each for 0.5 ... 2.5 mm2 conductors; at the output L+, M with 2 screw terminals each for 0.5 ... 2.5 mm2; no terminals for auxiliary contacts
- Connection method: screw terminals - at the input L, N, PE with 1 screw terminal each for 0.5 ... 2.5 mm² conductors; at the output L+, M with 2 screw terminals each for 0.5 ... 2.5 mm²; no terminals for auxiliary contacts.
- Mechanical data and net weight - enclosure width x height x depth 70 x 100 x 75 mm (device dimensions); installation width x mounting height 70 mm x 140 mm; required spacing 20 mm top, 20 mm bottom, 0 mm left, 0 mm right; fastening snaps onto DIN rail EN 60715 35x7.5/15, wall mounting also possible; net weight 0.3 kg, bound strictly as the printed net weight, NOT a shipping weight
- Mechanical data: enclosure width x height x depth 70 x 100 x 75 mm; installation width x mounting height 70 mm x 140 mm; required spacing 20 mm top, 20 mm bottom, 0 mm left, 0 mm right. Fastening: snaps onto DIN rail EN 60715 35x7.5/15, wall mounting also possible (DIN-rail mounting Yes, S7 rail mounting No, wall mounting Yes); housing can be lined up: Yes. Net weight 0.3 kg.
- Brochure corroboration - Siemens' own SITOP brochure SIMATIC-design table heads its first column "24 V/2.5 A, PM1207" with Article No. 6EP1332-1SH71, and the figures it prints for that column agree with the per-model data sheet
- Corroboration from Siemens' own SITOP brochure: its SIMATIC-design technical-data table heads the first column "24 V/2.5 A, PM1207" with Article No. 6EP1332-1SH71, and the figures it prints for that column (rated input voltage and range, mains buffering, rated input current, inrush current, rated output voltage/current, tolerance, efficiency, short-circuit protection, degree of protection, ambient temperature, dimensions and weight) agree with the per-model data sheet bound above.
- Package dimensions and shipping weight - GAP: the data sheet prints a net weight and the enclosure dimensions only, no package or carton dimensions and no shipping weight; neither is inferred from the printed net weight
- The Siemens data sheet for this article prints a net weight and the enclosure dimensions only; it prints no package or carton dimensions and no shipping weight. Package dimensions therefore remain GAP and shipping weight remains GAP_NOT_APPROVED; neither is inferred from the printed net weight.
Technical facts follow the exact manufacturer model table or named reference. Conflicting or unestablished numeric claims are withheld. Weight appears only in the specifications table with source basis; no shipping-weight estimate is inferred.