Allen-Bradley 1766-L32BXBA PLC
Does the 1766-L32BXBA include analog I/O, or only discrete points?
It carries the analog complement: 6 analog I/O points (4 analog inputs and 2 analog outputs) in addition to 32 discrete I/O points (20 digital inputs, 12 discrete outputs). The General Specifications number of I/O is 24 inputs (20 digital and 4 analog) and 14 outputs (12 digital and 2 analog).
What input power does this controller require?
The power supply voltage for this catalog number is 24V DC Class 2 SELV, and the power supply inrush current is 24V DC: 15 A for 20 ms.
How many 1762 expansion I/O modules can be connected?
A maximum of seven 1762 expansion I/O modules, in any combination, can be connected to the controller. The expansion bus supports up to seven 1762 modules, up to a maximum of 5V, 1500 mA (1300 mA for Series C only), and 24V, 1500 mA (1300 mA for Series C only).
What are the digital input voltage ranges for the high-speed and standard inputs?
Inputs 0...11 (the 12 high-speed DC inputs) have an on-state voltage range of 4.5…24V DC (4.5…26.4V DC (+10%) at 60 °C/140 °F; 4.5…30V DC (+25%) at 30 °C/86 °F). Inputs 12 and higher (the 8 standard DC inputs) have an on-state voltage range of 10…24V DC (10…26.4V DC (+10%) at 60 °C/140 °F; 10…30V DC (+25%) at 30 °C/86 °F).
What are the relay contact ratings of the built-in relay outputs?
At 240V AC: make 7.5 A, break 0.75 A, continuous 2.5 A, 1800VA make / 180VA break; at 120V AC: make 15.0 A, break 1.5 A, continuous 2.5 A, 1800VA make / 180VA break; at 250V DC: break 0.11 A, continuous 1.0 A, 28VA; at 125V DC: break 0.22 A, continuous 1.0 A, 28VA. Pilot duty rating C300, R300.
What is the operating temperature range?
Operating temperature is -20 °C < Ta < +65 °C (-4 °F < Ta < +149 °F), tested per IEC 60068-2-1, IEC 60068-2-2, and IEC 60068-2-14; nonoperating temperature is -40…+85 °C (-40…+185 °F).
- Register posture - remaining-gaps585 entry for goods 1757: title "Allen-Bradley 1766-L32BXBA PLC", model_candidate "1766-L32BXBA", category manufacturer_provenance_gap, original_job_status evidence_review_pending; the posture is an acquisition/provenance failure only, NOT a supplier-identity hold - full binding proceeds with the posture disclosed, and the register's reseller document was not used as evidence for any fact
- Register entry for goods 1757: title "Allen-Bradley 1766-L32BXBA PLC", model_candidate "1766-L32BXBA", category manufacturer_provenance_gap, original_job_status evidence_review_pending. The posture is an acquisition/provenance failure only ("Received reseller document is not manufacturer technical/weight evidence; shipping values not adopted"), not a supplier-identity hold, so full binding proceeds with the posture disclosed and the reseller document itself not used as evidence.
- Catalog number attestation - the 1766-IN001F-EN-P cover catalog-number list names 1766-L32BXBA among the six controllers covered; the exact catalog string is attested inside the manufacturer document itself, not taken from the catalog-linked lead filename
- The installation instructions list 1766-L32BXBA among the catalog numbers covered by the document; the exact catalog string 1766-L32BXBA is attested inside the manufacturer document itself, not taken from the catalog-linked lead filename.
- Hardware features and ports - the controller contains a power supply, input and output circuits, a processor, an isolated combination RS-232/RS-485 communication port, an Ethernet port, and a non-isolated RS-232 communication port
- The MicroLogix 1400 programmable controller contains a power supply, input and output circuits, a processor, an isolated combination RS-232/RS-485 communication port, an Ethernet port, and a non-isolated RS-232 communication port.
- I/O points overview - each controller supports 32 discrete I/O points (20 digital inputs, 12 discrete outputs); the 6 analog I/O points (4 analog inputs and 2 analog outputs) are provided only by 1766-L32BWAA, 1766-L32AWAA, and 1766-L32BXBA, so 1766-L32BXBA carries the analog complement
- Each controller supports 32 discrete I/O points (20 digital inputs, 12 discrete outputs); the 6 analog I/O points (4 analog inputs and 2 analog outputs) are provided only by 1766-L32BWAA, 1766-L32AWAA, and 1766-L32BXBA, so 1766-L32BXBA carries the analog complement.
- Embedded discrete I/O (Chapter 1 Controller Input and Output Description table) - the 1766-L32BXBA row: input power 24V DC, user power None, embedded discrete I/O of 12 fast 24V DC inputs and 8 normal 24V DC inputs, outputs of 6 relay outputs, 3 fast DC outputs, and 3 normal DC outputs; the shared comm-ports cell reads 1 RS-232/RS-485 (isolated combo port), 1 Ethernet, and 1 RS-232 (non-isolated)
- In the table, the 1766-L32BXBA row reads: input power 24V DC, user power None, embedded discrete I/O of 12 fast 24V DC inputs and 8 normal 24V DC inputs, and outputs of 6 relay outputs, 3 fast DC outputs, and 3 normal DC outputs. The shared comm-ports cell for the table reads 1 RS-232/RS-485 (isolated combo port), 1 Ethernet, and 1 RS-232 (non-isolated).
- Memory module and built-in real-time clock - the controller has a built-in real-time clock; a memory module, 1766-MM1, can be ordered as an accessory for optional backup of the user program and data and for transporting programs between controllers, but it does not increase the available memory of the controller; the program and data in the controller are non-volatile. NOTE: no user-memory SIZE is printed in the filed documents' specification tables - no memory size is bound (see gaps_and_unresolved)
- The controller has a built-in real-time clock. A memory module, 1766-MM1, can be ordered as an accessory; it provides optional backup of the user program and data and a means to transport programs between controllers, but it does not increase the available memory of the controller. The program and data in the controller are non-volatile.
- Expansion I/O modules - a maximum of seven 1762 expansion I/O modules, in any combination, can be connected to a MicroLogix 1400 controller
- A maximum of seven 1762 expansion I/O modules, in any combination, can be connected to a MicroLogix 1400 controller.
- Dimensions - 90 x 180 x 87 mm, HxWxD 3.5 x 7.08 x 3.43 in., as printed in the General Specifications table across the family columns including 1766-L32BXB/A; these are the controller BODY dimensions - package dimensions are not printed and remain GAP
- Controller dimensions are 90 x 180 x 87 mm, HxWxD 3.5 x 7.08 x 3.43 in., as printed in the General Specifications table (single value printed across the 1766-L32AWA/A, 1766-L32BWA/A, and 1766-L32BXB/A columns). These are the controller body dimensions; package dimensions are not printed.
- Shipping weight (manufacturer's own printed kind) - the General Specifications table prints "Shipping weight 900 g (31.74 oz.)"; the figure is bound exactly as printed under the manufacturer's own shipping-weight kind, with that basis - it is NOT inferred, NOT an experience estimate, and NOT a device weight; the card's shipping_weight_status nevertheless remains GAP_NOT_APPROVED per factory convention, so the figure counts only if adjudication approves it (DIVERGENCE 1: UM001M renders the same mass as "0.9 kg (2.0 lbs)" - carried as corroboration in the final fact, not bound here)
- The General Specifications table prints "Shipping weight 900 g (31.74 oz.)" (single value across the three controller columns, including 1766-L32BXB/A). The figure is bound exactly as printed under the manufacturer's own shipping-weight kind; it is not an inference or an experience estimate.
- Number of I/O (General Specifications) - 24 inputs (20 digital and 4 analog) and 14 outputs (12 digital and 2 analog), the analog-inclusive count that applies to the analog models, including 1766-L32BXBA
- The General Specifications table prints the number of I/O as 24 inputs (20 digital and 4 analog) and 14 outputs (12 digital and 2 analog) — the analog-inclusive count that applies to the analog models, including 1766-L32BXBA.
- Power supply voltage - for the 1766-L32BXB/A column, 24V DC Class 2 SELV (the 1766-L32AWA/A and 1766-L32BWA/A columns print 100…240V AC @ 47…63 Hz and are not bound)
- For the 1766-L32BXB/A column, the power supply voltage is 24V DC Class 2 SELV (the 1766-L32AWA/A and 1766-L32BWA/A columns print 100…240V AC @ 47…63 Hz and are not bound).
- Power supply inrush current - for the 1766-L32BXB/A column, 24V DC: 15 A for 20 ms
- For the 1766-L32BXB/A column, the power supply inrush current is 24V DC: 15 A for 20 ms.
- Power consumption - for the 1766-L32BXB/A column, 50 W, and 7.5 W with no 1762 expansion I/O
- For the 1766-L32BXB/A column, power consumption is 50 W, and 7.5 W with no 1762 expansion I/O.
- Sensor power and circuit types - for the 1766-L32BXB/A column: 24V DC sensor power is none; input circuit type is digital 24V DC sink/source (standard and high-speed) and analog 0…10V DC; output circuit type is Relay/FET
- For the 1766-L32BXB/A column: 24V DC sensor power is none; the input circuit type is digital 24V DC sink/source (standard and high-speed) and analog 0…10V DC; the output circuit type is Relay/FET.
- Relay life, enclosure type and terminal torque - Relay life – Mechanical 20,000,000 cycles (electrical life refers to the Relay Life Chart); enclosure type rating None (open-style); terminal screw torque 0.791 N•m (7.0 lb•in) rated
- Relay life – Mechanical is 20,000,000 cycles (electrical life refers to the Relay Life Chart); the enclosure type rating is None (open-style); terminal screw torque is 0.791 N•m (7.0 lb•in) rated.
- Digital inputs 0...11 (the 12 high-speed DC inputs) - on-state voltage range 4.5…24V DC (4.5…26.4V DC (+10%) at 60 °C/140 °F; 4.5…30V DC (+25%) at 30 °C/86 °F); off-state voltage range 0…1.5V DC; operating frequency 0 Hz...100 kHz; on-state current min 7.0 mA @ 4.5V DC, nom 9.5 mA @ 24V DC, max 10.0 mA @ 30V DC; off-state leakage current 0.1 mA max; nominal impedance 2.0 kΩ (user-manual figures bound - DIVERGENCE 2: IN001F prints different figures for these attributes, not bound)
- For inputs 0...11 (the 12 high-speed DC inputs): on-state voltage range 4.5…24V DC (4.5…26.4V DC (+10%) at 60 °C/140 °F; 4.5…30V DC (+25%) at 30 °C/86 °F); off-state voltage range 0…1.5V DC; operating frequency 0 Hz...100 kHz; on-state current min 7.0 mA @ 4.5V DC, nom 9.5 mA @ 24V DC, max 10.0 mA @ 30V DC; off-state leakage current 0.1 mA max; nominal impedance 2.0 kΩ.
- Digital inputs 12 and higher (the 8 standard DC inputs) - on-state voltage range 10…24V DC (10…26.4V DC (+10%) at 60 °C/140 °F; 10…30V DC (+25%) at 30 °C/86 °F); off-state voltage range 0…5V DC; operating frequency 0 Hz...1 kHz (scan time dependent); on-state current min 3.0 mA @ 10V DC, nom 5.0 mA @ 24V DC, max 5.5 mA @ 30V DC; off-state leakage current 1.5 mA max; nominal impedance 5.5 kΩ (user-manual figures bound - DIVERGENCE 2 applies)
- For inputs 12 and higher (the 8 standard DC inputs): on-state voltage range 10…24V DC (10…26.4V DC (+10%) at 60 °C/140 °F; 10…30V DC (+25%) at 30 °C/86 °F); off-state voltage range 0…5V DC; operating frequency 0 Hz...1 kHz (scan time dependent); on-state current min 3.0 mA @ 10V DC, nom 5.0 mA @ 24V DC, max 5.5 mA @ 30V DC; off-state leakage current 1.5 mA max; nominal impedance 5.5 kΩ.
- Analog inputs - voltage input range 0…10.0V DC – 1 LSB; type of data 12-bit unsigned integer; input coding 0…4095; voltage input impedance >199 kΩ; input resolution 12 bit; non-linearity ±0.5% of full scale (user-manual figure bound - IN001F prints ±1.0%, not bound); overall accuracy ±1.0% of full scale over -20…+65 °C (-4…+149 °F); update time 100/20/16.67/4 ms (selectable); voltage input overvoltage protection 10.5V DC; field wiring to logic isolation non-isolated with internal logic
- Analog inputs: voltage input range 0…10.0V DC – 1 LSB; type of data 12-bit unsigned integer; input coding 0…4095; voltage input impedance >199 kΩ; input resolution 12 bit; non-linearity ±0.5% of full scale; overall accuracy ±1.0% of full scale over -20…+65 °C (-4…+149 °F); update time 100/20/16.67/4 ms (selectable); voltage input overvoltage protection 10.5V DC; field wiring to logic isolation non-isolated with internal logic.
- Analog outputs - 2 single-ended (the table row is headed "Number of inputs" as printed); voltage output range 0…10V DC – 1 LSB; type of data 12-bit unsigned integer; output coding 0…4095; output resolution 12 bit; step response 2.5 ms @ 95%; load range voltage output >1 KΩ; analog output setting time, max 3 ms; overall accuracy ±1.0% of full scale over -20…+60 °C (-4…+140 °F); electrical isolation non-isolated with internal logic; cable length 30 m (98 ft) shielded cable
- Analog outputs: 2 single-ended (the table row is headed "Number of inputs" as printed); voltage output range 0…10V DC – 1 LSB; type of data 12-bit unsigned integer; output coding 0…4095; output resolution 12 bit; step response 2.5 ms @ 95%; load range voltage output >1 KΩ; analog output setting time, max 3 ms; overall accuracy ±1.0% of full scale over -20…+60 °C (-4…+140 °F); electrical isolation non-isolated with internal logic; cable length 30 m (98 ft) shielded cable.
- Relay and FET output currents - for the 1766-L32BXB/A column: maximum controlled load 1080VA; maximum continuous current 2.5 A per channel; current per channel and group common 2.5 A per channel with 8 A max on the channel 8...11 common; current per controller 28 A or a total of per-point loads, whichever is less, at 150V max, and 20 A or a total of per-point loads, whichever is less, at 240V max
- For the 1766-L32BXB/A column: maximum controlled load 1080VA; maximum continuous current 2.5 A per channel; current per channel and group common 2.5 A per channel with 8 A max on the channel 8...11 common; current per controller 28 A or a total of per-point loads, whichever is less, at 150V max, and 20 A or a total of per-point loads, whichever is less, at 240V max.
- Relay outputs and contact ratings - turn on time/turn off time, max 10 ms (scan time dependent); load current, min 10 mA (user-manual figure bound - DIVERGENCE 2: IN001F prints "max" 10 mA, not bound). Contact ratings: at 240V AC, make 7.5 A, break 0.75 A, continuous 2.5 A, 1800VA make / 180VA break; at 120V AC, make 15.0 A, break 1.5 A, continuous 2.5 A, 1800VA make / 180VA break; at 250V DC, break 0.11 A, continuous 1.0 A, 28VA; at 125V DC, break 0.22 A, continuous 1.0 A, 28VA. Pilot duty rating C300, R300
- Relay outputs: turn on time/turn off time, max 10 ms (scan time dependent); load current, min 10 mA. Relay contact ratings: at 240V AC, make 7.5 A, break 0.75 A, continuous 2.5 A, 1800VA make / 180VA break; at 120V AC, make 15.0 A, break 1.5 A, continuous 2.5 A, 1800VA make / 180VA break; at 250V DC, break 0.11 A, continuous 1.0 A, 28VA; at 125V DC, break 0.22 A, continuous 1.0 A, 28VA. Pilot duty rating C300, R300.
- FET outputs (Appendix A Table 14, dedicated to 1766-L32BXB and 1766-L32BXBA) - power supply voltage 24V DC (-15%, 10%) Class 2; on-state voltage drop 1V DC at max load current, 2.5V DC at max surge current; current rating per point max load per Figure 67 in general operation and 100 mA in high-speed operation (outputs 2, 3, and 4 only); min load 50 mA (user-manual figure bound - IN001F prints 1.0 mA general / 20 mA high-speed, not bound); max leakage 1.0 mA; surge current per point peak 4.0 A, max duration 10 ms, max rate of repetition once every second at 30 °C (86 °F) and once every 2 seconds at 60 °C (140 °F); turn-on time, max 11 µs (28 ns high-speed); turn-off time, max 89 µs (3.5 µs high-speed); outputs 2, 3, and 4 also provide pulse train output (PTO) or pulse-width modulation (PWM) function
- Table 14 is dedicated to 1766-L32BXB and 1766-L32BXBA. Power supply voltage 24V DC (-15%, 10%) Class 2. On-state voltage drop: 1V DC at max load current, 2.5V DC at max surge current. Current rating per point: max load per Figure 67 in general operation and 100 mA in high-speed operation (outputs 2, 3, and 4 only); min load 50 mA; max leakage 1.0 mA. Surge current per point: peak 4.0 A, max duration 10 ms, max rate of repetition once every second at 30 °C (86 °F) and once every 2 seconds at 60 °C (140 °F). Turn-on time, max 11 µs (28 ns high-speed); turn-off time, max 89 µs (3.5 µs high-speed). Outputs 2, 3, and 4 also provide pulse train output (PTO) or pulse-width modulation (PWM) function.
- Working voltage for 1766-L32BXB/A (bound from UM001P) - input group to backplane and input group to input group isolation, and FET output group to backplane isolation, are 75V DC working voltage (IEC Class 2 reinforced insulation); relay output group to backplane isolation is 265V AC working voltage (IEC Class 2 reinforced insulation). (DIVERGENCE 3: the IN001F excerpt's heading for this section misprints "1766-L16BXB, 1766-L16BXBA" - no such catalog numbers exist; the IN001F heading was not used)
- Working voltage for 1766-L32BXB/A: input group to backplane and input group to input group isolation, and FET output group to backplane isolation, are 75V DC working voltage (IEC Class 2 reinforced insulation); relay output group to backplane isolation is 265V AC working voltage (IEC Class 2 reinforced insulation).
- Expansion bus power (IN001F) - the expansion bus supports up to seven 1762 modules, up to a maximum of 5V, 1500 mA (1300 mA for Series C only), and 24V, 1500 mA (1300 mA for Series C only)
- The expansion bus supports up to seven 1762 modules, up to a maximum of 5V, 1500 mA (1300 mA for Series C only), and 24V, 1500 mA (1300 mA for Series C only).
- Environmental specifications - temperature (IN001F, 1766-L32BXB / 1766-L32BXBA column): operating -20 °C < Ta < +65 °C (-4 °F < Ta < +149 °F), tested per IEC 60068-2-1, IEC 60068-2-2, and IEC 60068-2-14; nonoperating -40…+85 °C (-40…+185 °F)
- Environmental specifications: temperature, operating -20 °C < Ta < +65 °C (-4 °F < Ta < +149 °F), tested per IEC 60068-2-1, IEC 60068-2-2, and IEC 60068-2-14; temperature, nonoperating -40…+85 °C (-40…+185 °F).
- Environmental specifications - humidity, vibration, shock and EMC (IN001F): relative humidity 5…95% non-condensing; vibration 5 g @ 10…500 Hz; shock, operating: panel mount 30 g; shock, nonoperating: panel mount 30 g, DIN mount 40 g; emissions IEC 61000-6-4; ESD immunity 6 kV contact discharges, 8 kV air discharges; radiated RF immunity 10V/m with 1 kHz sine-wave 80% AM from 80…6000 MHz; EFT/B immunity ±2 kV @ 5 kHz on power ports and on signal ports, ±1 kV @ 5 kHz on communications ports; conducted RF immunity 10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
- Relative humidity 5…95% non-condensing. Vibration 5 g @ 10…500 Hz. Shock, operating: panel mount 30 g. Shock, nonoperating: panel mount 30 g, DIN mount 40 g. Emissions IEC 61000-6-4. ESD immunity 6 kV contact discharges, 8 kV air discharges. Radiated RF immunity 10V/m with 1 kHz sine-wave 80% AM from 80…6000 MHz. EFT/B immunity ±2 kV @ 5 kHz on power ports and on signal ports, ±1 kV @ 5 kHz on communications ports. Conducted RF immunity 10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz.
- Corroboration and DIVERGENCE 1 - the earlier user-manual revision UM001M (July 2018) prints the same General Specifications row set for the family columns (including 1766-L32BXB/A): dimensions 90 x 180 x 87 mm, HxWxD 3.5 x 7.08 x 3.43 in., and shipping weight 0.9 kg (2.0 lbs) - the same metric mass as the current revision UM001P's 900 g, with the imperial figure rendered differently; UM001P is bound and this UM001M rendering is carried as a corroboration fact only
- The earlier user-manual revision prints the same General Specifications row set for the family columns (including 1766-L32BXB/A): dimensions 90 x 180 x 87 mm, HxWxD 3.5 x 7.08 x 3.43 in., and shipping weight 0.9 kg (2.0 lbs) — the same mass as the current revision, with the imperial figure rendered differently (see flags).
- MicroLogix 1400 Programmable Controllers Installation Instructions, Publication 1766-IN001F-EN-P — March 2024, Rockwell Automation (partial excerpt as served by the mirror: printed pp. 1, 5, 15, 16, 17, 18) — Publication 1766-IN001F-EN-P — March 2024 (partial excerpt as served, 6 pp)
- MicroLogix 1400 Programmable Controllers User Manual, Publication 1766-UM001P-EN-P — March 2024, Rockwell Automation — Publication 1766-UM001P-EN-P — March 2024 (complete, 294 pp)
- MicroLogix 1400 Programmable Controllers User Manual, Publication 1766-UM001M-EN-P — July 2018, Rockwell Automation — Publication 1766-UM001M-EN-P — July 2018 (complete, 422 pp)
Specifications follow the cited manufacturer documents and the approved model-specific conditions. Equipment mass is not a shipping-weight estimate.