Omron CJ1W-TC001 CJ-Series 4-Loop Thermocouple Temperature Control Unit

Series#: Omron

Product Details

  • Omron CJ1W-TC001 CJ-Series 4-Loop Thermocouple Temperature Control Unit
  • Control loops: 4
  • Sensor input: Thermocouple: R, S, K, J, T, B, L
  • Control output: Open-collector NPN pulse outputs
  • Internal consumption: 250 mA max. at 5 VDC

Specification

Omron CJ1W-TC001 CJ-Series 4-Loop Thermocouple Temperature Control Unit.

Technical Specifications

SpecificationDetails
ManufacturerOmron
Order numberCJ1W-TC001
Control loops4
Sensor inputThermocouple: R, S, K, J, T, B, L
Control outputOpen-collector NPN pulse outputs
Internal consumption250 mA max. at 5 VDC
NJ-series compatibilityNot supported for CJ1W-TC001
Unit-number allocation2 unit numbers
Dimensions (W × H × D)31 × 90 × 65 mm
Manufacturer maximum product weight150 g max. Omron reference, PDF page 4

CJ1W-TC001 Procurement Questions

How many control loops does the CJ1W-TC001 provide?

The CJ1W-TC001 provides 4 control loops.

Which thermocouple types can the CJ1W-TC001 accept?

The temperature sensor input is thermocouple: R, S, K, J, T, L, B.

What temperature control methods does the CJ1W-TC001 support?

The Unit supports ON/OFF control or PID control with two degrees of freedom.

What is the sampling period with 4 loops in use?

The sampling period is 500 ms (4 loops).

What are the control output and external supply requirements?

Control output and heater burnout alarm output are NPN or PNP outputs, both with short-circuit protection; the external power supply voltage is 24 VDC +10%, -15%, with a max. switching capacity of 100 mA (per output).

What data exchange words does the CJ1W-TC001 use?

It uses 20 words in the Special I/O Unit Area and 200 words in the DM Area.

Unit classification
CJ-series Special I/O Unit
Number of control loops
4 control loops
Temperature sensor
Thermocouple: R, S, K, J, T, L, B
Internal current consumption
250 mA max., 5 VDC
Dimensions
31 x 90 x 65 mm (W x H x D)
Device weight
150 g max.
Temperature control method
ON/OFF control or PID control with two degrees of freedom
Sampling period
500 ms (4 loops)
Control output
NPN or PNP outputs, both with short-circuit protection; external power supply voltage 24 VDC +10%, -15%; max. switching capacity 100 mA (per output)
Max. heater current
Single-phase AC, 50 A
External terminal connections
Removable terminal block with 18 points (M3 screws)
Data exchange words
20 words (Special I/O Unit Area); 200 words (DM Area)

Technical facts follow the cited manufacturer reference and exact model column or explicit model-number legend. Numeric weight remains only in the specifications table with its documented product/max/unpacked basis; no shipping mass is inferred.

Unmatched Customer Service

After Hours Shipping

Real Time Order Tracking

Flexible Delivery Options

Intact Technical Supports

What Does Our Clients Say

Mitsubishi MR-J4

Laura Navas

Great product!

2019/12/01

Keyence sensor

EQDR SALES

Original and fast!

2020/02/22

Need Professional Tech Support or a Quote?

  • Our senior engineers provide 1-on-1 selection & configuration advice
  • 100% genuine products guaranteed with rapid global delivery
UP
WhatsApp