Omron CJ1W-AD042 CJ-Series 4-Channel Analog Input Unit.
| Specification | Details |
|---|---|
| Manufacturer | Omron |
| Order number | CJ1W-AD042 |
| Analog inputs | 4 |
| Input ranges | 1–5 V; 0–10 V; −5–5 V; −10–10 V; 4–20 mA |
| Resolution by input range | 10,000: 1–5 V or 4–20 mA; 20,000: 0–10 V or −5–5 V; 40,000: −10–10 V |
| A/D conversion period | 20 μs/1 point; 25 μs/2 points; 30 μs/3 points; 35 μs/4 points |
| 5 VDC consumption | 520 mA max. |
| Signal isolation | Digital isolation between I/O and controller signals; no isolation between input signals |
| Terminals | 18-point detachable terminal block, M3 screws |
| Dimensions (W × H × D) | 31 × 90 × 65 mm |
| Manufacturer maximum product weight | 150 g max. Omron reference, PDF page 4 |
The CJ1W-AD042 provides 4 analog inputs.
The maximum rated input is +/-15 V for voltage input and +/-30 mA for current input.
Voltage input has an input impedance of 1 Mohm min.; current input has 250 ohm (rated value).
At 25 °C, accuracy is +/-0.2% of F.S. for voltage input and +/-0.4% of F.S. for current input. Over 0 to 55 °C, it is +/-0.4% of F.S. for voltage input and +/-0.6% of F.S. for current input.
Direct conversion is supported by CJ2H-CPU[][](-EIP) CPU Units with unit version 1.1 or later, and by CJ2M-CPU[][]. A/D conversion is performed and the converted value is refreshed when the ANALOG INPUT DIRECT CONVERSION instruction (AIDC) is executed.
Technical facts follow the cited manufacturer reference and exact model column or explicit model-number legend. Numeric weight remains only in the specifications table with its documented product/max/unpacked basis; no shipping mass is inferred.