Omron CJ1W-ID261 CJ-Series 64-Point DC Input Unit

Series#: Omron

Product Details

  • Omron CJ1W-ID261 CJ-Series 64-Point DC Input Unit
  • Digital inputs: 64
  • Rated input voltage: 24 VDC
  • Rated input voltage range: 20.4–26.4 VDC
  • Input current: 4.1 mA typical at 24 VDC

Specification

Omron CJ1W-ID261 CJ-Series 64-Point DC Input Unit.

Technical Specifications

SpecificationDetails
ManufacturerOmron
Order numberCJ1W-ID261
Digital inputs64
Rated input voltage24 VDC
Rated input voltage range20.4–26.4 VDC
Input current4.1 mA typical at 24 VDC
ConnectionFujitsu connector
Common/circuit arrangement16 points/common, 4 circuits
Simultaneous-ON conditionsObserve the manufacturer voltage/ambient-temperature simultaneous-ON derating chart
Manufacturer maximum product weight110 g max. Omron reference, PDF page 12

CJ1W-ID261 Procurement Questions

What input voltage does the CJ1W-ID261 accept?

The rated input voltage is 24 V DC, and the rated input voltage range is 20.4 to 26.4 V DC.

How many input points and commons does this unit have?

It has 64 circuits, configured as 16 points/common across 4 circuits.

What are the ON and OFF detection thresholds?

The ON voltage/ON current is 19.0 V DC min./3 mA min., and the OFF voltage/OFF current is 5 V DC max./1 mA max.

What is the input current and input impedance?

Input impedance is 5.6 kΩ, and input current is 4.1 mA typical (at 24 V DC).

Can the input response time be changed?

ON response time is 8.0 ms max. and OFF response time is 8.0 ms max.; each can be set to between 0 and 32 in the PLC Setup.

What are the insulation and dielectric strength ratings?

Insulation resistance is 20 MΩ between external terminals and the GR terminal (100 V DC), and dielectric strength is 1,000 V AC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.

Unit classification
DC Input Unit (Fujitsu Connectors, 64 Points)
Rated input voltage
24 V DC
Rated input voltage range
20.4 to 26.4 V DC
Input impedance
5.6 kΩ
Input current
4.1 mA typical (at 24 V DC)
ON voltage / ON current
19.0 V DC min./3 mA min.
OFF voltage / OFF current
5 V DC max./1 mA max.
ON response time
8.0 ms max. (Can be set to between 0 and 32 in the PLC Setup.)
OFF response time
8.0 ms max. (Can be set to between 0 and 32 in the PLC Setup.)
Number of circuits
64 (16 points/common, 4 circuits)
Simultaneously ON points
50% (16 points/common) (at 24 V DC)
Insulation resistance
20 MΩ between external terminals and the GR terminal (100 V DC)
Dielectric strength
1,000 V AC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.
Internal current consumption
5 V DC: 90 mA max.
Device weight
110 g max.

Technical facts follow the cited manufacturer reference and exact model column or explicit model-number legend. Numeric weight remains only in the specifications table with its documented product/max/unpacked basis; no shipping mass is inferred.

Unmatched Customer Service

After Hours Shipping

Real Time Order Tracking

Flexible Delivery Options

Intact Technical Supports

What Does Our Clients Say

Mitsubishi MR-J4

Laura Navas

Great product!

2019/12/01

Keyence sensor

EQDR SALES

Original and fast!

2020/02/22

Need Professional Tech Support or a Quote?

  • Our senior engineers provide 1-on-1 selection & configuration advice
  • 100% genuine products guaranteed with rapid global delivery
UP
WhatsApp