6ES7211-0BA22-0XB0 Procurement Questions
Can this CPU 221 be expanded with additional I/O modules?
No. The maximum number of expansion modules is None and the maximum number of intelligent modules allowed is None for this CPU.
What supply voltage does this CPU 221 require?
The nominal power supply is 120 to 240 VAC, and the AC input voltage range is 85 to 264 VAC (47 to 63 Hz).
What load can the relay outputs switch?
The relay outputs are dry contacts rated 24 VDC or 250 VAC, with a voltage range of 5 to 30 VDC or 5 to 250 VAC, a maximum rated current of 2.0 A per point and 10 A per common, and a maximum lamp load of 30 W DC; 200 W AC.
How is the program and data retained, and what backup options exist?
User data of 2048 bytes is stored permanently in EEPROM, and the super capacitor provides backup of 50 hours typical (8 hours min. at 40°C); an optional battery cartridge provides 200 days typical backup.
Does this CPU include a real-time clock?
No built-in clock is listed for this CPU; the Time-of-Day clock is provided by an optional cartridge.
What communication port and baud rates does it offer?
It has 1 RS-485 port, with PPI, DP/T baud rates of 9.6, 19.2, 187.5 kbaud.
- Order number - Table A-2 CPU Order Numbers prints 6ES7 211--0BA22--0XB0 for CPU 221; the exact order number is attested inside the genuine -22-generation manual itself, not taken from a filename
- 6ES7 211--0BA22--0XB0
- CPU model - CPU 221 (Table A-2, CPU 221 row)
- CPU 221
- Power supply (nominal) - 120 to 240 VAC (Table A-2, CPU 221 row)
- 120 to 240 VAC
- Onboard inputs - 6 x 24 VDC (Table A-2, CPU 221 row)
- 6 x 24 VDC
- Onboard outputs - 4 x Relay (Table A-2, CPU 221 row)
- 4 x Relay
- Removable connector - No (Table A-2, CPU 221 row)
- No
- Module description - CPU 221 AC/DC/Relay 6 Inputs/ 4 Relays (Table A-3 CPU General Specifications)
- CPU 221 AC/DC/Relay 6 Inputs/ 4 Relays
- Dimensions (W x H x D) - 90 x 80 x 62 mm (Table A-3; device/body dimensions, NOT package dimensions)
- 90 x 80 x 62
- Weight - 310 g (Table A-3, printed under the column heading 'Weight'; bound as printed device weight under its own kind - NOT a shipping weight)
- 310 g
- Power dissipation - 6 W (Table A-3)
- 6W
- VDC available, +5 VDC - 0 mA (Table A-3)
- 0 mA
- VDC available, +24 VDC - 180 mA (Table A-3)
- 180 mA
- User program size (EEPROM) - 4096 bytes (Table A-4; MERGED CELL spanning the CPU 221 + CPU 222 columns - attribution verified by pdftotext -bbox word geometry, flagged in evidence_flags)
- 4096 bytes
- User data size (EEPROM) - 2048 bytes, stored permanently (Table A-4; MERGED CELL spanning the CPU 221 + CPU 222 columns - attribution geometry-verified as for the program-size fact)
- 2048 bytes (stored permanently)
- Backup, super capacitor - 50 hours typical (8 hours min. at 40°C) (Table A-4; MERGED CELL spanning the CPU 221 + CPU 222 columns - attribution geometry-verified)
- 50 hours typical (8 hours min. at 40°C)
- Backup, optional battery cartridge - 200 days typical (Table A-4, CPU 221 column)
- 200 days typical
- Built-in digital I/O - 6 inputs/4 outputs (Table A-4, CPU 221 column)
- 6 inputs/4 outputs
- Digital I/O image size - 256 (128 In/128 Out) (Table A-4)
- 256 (128 In/128 Out)
- Analog I/O image size - None (Table A-4, CPU 221 column)
- None
- Maximum expansion modules - None (Table A-4, CPU 221 column)
- None
- Maximum intelligent modules - None (Table A-4, CPU 221 column)
- None
- Pulse catch inputs - 6 (Table A-4, CPU 221 column)
- 6
- High-speed counters, total - 4 counters total (Table A-4, CPU 221 column)
- 4 counters total
- High-speed counters, single phase - 4 at 30 kHz (Table A-4, CPU 221 column)
- 4 at 30 kHz
- High-speed counters, two phase - 2 at 20 kHz (Table A-4, CPU 221 column)
- 2 at 20 kHz
- Boolean execution speed - 0.37 µs per instruction (Table A-4, CPU 221 column)
- 0.37 µs per instruction
- Analog adjustment - 1 with 8 bit resolution (Table A-4; the cell spans the CPU 221+222 boundary - attribution verified by word geometry)
- 1 with 8 bit resolution
- Time-of-Day clock - Optional cartridge (Table A-4; cell span verified at p.364 word geometry - the next cell, 'Built-in', starts at the CPU 224 column)
- Optional cartridge
- Communication ports - 1 RS-485 port (Table A-4; cell spanning CPU 221-224, geometry-verified)
- 1 RS--485 port
- PPI/DP/T baud rates - 9.6, 19.2, 187.5 kbaud (Table A-4)
- 9.6, 19.2, 187.5 kbaud
- Input voltage, AC supply - 85 to 264 VAC (47 to 63 Hz) (Table A-5, AC column)
- 85 to 264 VAC (47 to 63 Hz)
- Input current, CPU 221 with AC supply - 30/15 mA at 120/240 VAC (CPU only); 120/60 mA at 120/240 VAC (max. load) (Table A-5, AC column)
- 30/15 mA at 120/240 VAC (CPU only); 120/60 mA at 120/240 VAC (max. load)
- Inrush current, AC supply - 20 A at 264 VAC (Table A-5, AC column)
- 20 A at 264 VAC
- Isolation (field side to logic), AC supply - 1500 VAC (Table A-5; the text layer interleaves the Isolation and Hold-up rows - the AC-column attribution was verified by word x-coordinates, and the fact carries the full 6-line block as its quote)
- 1500 VAC
- Hold-up time, AC supply - 20/80 ms at 120/240 VAC (Table A-5; same interleaved-row geometry verification as the isolation fact)
- 20/80 ms at 120/240 VAC
- Fuse (non-replaceable), AC supply - 2 A, 250 V Slow Blow (Table A-5, AC column)
- 2 A, 250 V Slow Blow
- Sensor power output voltage, AC-supply CPU - 20.4 to 28.8 VDC (Table A-5)
- 20.4 to 28.8 VDC
- Input type - Sink/Source (IEC Type 1 Sink) (Table A-6; the manual's family-general 24 VDC input specifications, presented for all CPUs)
- Sink/Source (IEC Type 1 Sink)
- Input rated voltage - 24 VDC at 4 mA typical (Table A-6)
- 24 VDC at 4 mA typical
- Input logic 1 (minimum) - 15 VDC at 2.5 mA (Table A-6)
- 15 VDC at 2.5 mA
- Input logic 0 (maximum) - 5 VDC at 1 mA (Table A-6)
- 5 VDC at 1 mA
- Relay output type - Dry contact (Table A-7, relay-output column)
- Dry contact
- Relay output rated voltage - 24 VDC or 250 VAC (Table A-7)
- 24 VDC or 250 VAC
- Relay output voltage range - 5 to 30 VDC or 5 to 250 VAC (Table A-7)
- 5 to 30 VDC or 5 to 250 VAC
- Relay rated current per point (maximum) - 2.0 A (Table A-7)
- 2.0 A
- Relay rated current per common (maximum) - 10 A (Table A-7)
- 10 A
- Relay lamp load (maximum) - 30 W DC; 200 W AC (Table A-7)
- 30 W DC; 200 W AC
- Siemens official model reference — Listed model features cross-checked on 22 October 2026. Project compatibility, wiring and operating limits require the applicable Siemens documentation.
Listed features checked against official Siemens model descriptions. This is not a replacement-compatibility or installation approval.