Siemens 6ES7317-2AJ10-0AB0 SIMATIC CPU 317-2DP

Series#: Siemens

Product Details

  • Siemens 6ES7317-2AJ10-0AB0 SIMATIC CPU 317-2DP
  • Rated DC supply: 24 V
  • DC supply lower limit: 20.4 V
  • DC supply upper limit: 28.8 V
  • Integrated work memory: 512 kbyte

Specification

Siemens 6ES7317-2AJ10-0AB0 SIMATIC CPU 317-2DP.

Technical Specifications

SpecificationDetails
ManufacturerSiemens
Order number6ES7317-2AJ10-0AB0
Rated DC supply24 V
DC supply lower limit20.4 V
DC supply upper limit28.8 V
Integrated work memory512 kbyte
Industrial Ethernet interfaces0
PROFINET interfaces0
Width80 mm
Height125 mm
Depth130 mm
Manufacturer approximate weight460 g Siemens data sheet, PDF page 7

6ES7317-2AJ10-0AB0 Procurement Questions

Which programming package is associated with this CPU?

The associated programming package is STEP 7 as of V5.4 + SP2 or STEP 7 as of V5.2 + SP1 with HSP 141.

How much main memory does the CPU provide, and can it be expanded?

Main memory is integrated 512 KB and is not expandable; the maximum size of non-volatile memory for retentive data blocks is 256 KB.

How is the load memory implemented and how long is data retained on it?

Load memory is a pluggable Micro Memory Card (MMC) with max. 8 MB; data retention on the Micro Memory Card after the last programming action is min. 10 years.

How many S7 counters and S7 timers are available?

There are 512 S7 counters with a counting range of 0 to 999, and 512 S7 timers with configurable retentivity (default: no retentivity) and a time setting range of 10 ms to 9990 s.

Are IEC counters and IEC timers available, and how many can be used?

IEC counter and IEC timer are available as type SFB; the number is unlimited, limited only by main memory.

What are the current consumption and power loss of the CPU?

Current consumption is typically 100 mA open-circuit and 850 mA rated; power loss is typically 4 W.

Model / order number
CPU 317-2 DP — order number (MLFB) 6ES7317-2AJ10-0AB0; hardware version 01
Programming package
Associated programming package: STEP 7 as of V5.4 + SP2 or STEP 7 as of V5.2 + SP1 with HSP 141
Main memory
Integrated 512 KB, not expandable; maximum size of non-volatile memory for retentive data blocks: 256 KB
Load memory
Pluggable Micro Memory Card (MMC), max. 8 MB; data retention on the Micro Memory Card (after the last programming action), min. 10 years
Backup
Ensured by Micro Memory Card (maintenance-free)
Execution times
Bit operation min. 0.05 μs; word operations min. 0.2 μs; fixed-point arithmetic min. 0.2 μs; floating-point arithmetic min. 1.0 μs
S7 counters
512; counting range 0 to 999
S7 timers
512; retentivity configurable, default: no retentivity; time setting range 10 ms to 9990 s
IEC counters / timers
IEC counter and IEC timer available (type SFB); number unlimited (limited only by main memory)
Bit memory
Max. 4096 bytes
Weight (manufacturer-stated product weight)
460 g
Current consumption
current consumption (open-circuit), typically 100 mA; current consumption (rated value) 850 mA
Power loss
Power loss, typically 4 W

Technical statements follow the cited model-specific Siemens data-sheet copy. Weight references remain only in the specifications table and retain the stated packaging basis.

Unmatched Customer Service

After Hours Shipping

Real Time Order Tracking

Flexible Delivery Options

Intact Technical Supports

What Does Our Clients Say

Mitsubishi MR-J4

Laura Navas

Great product!

2019/12/01

Keyence sensor

EQDR SALES

Original and fast!

2020/02/22

Need Professional Tech Support or a Quote?

  • Our senior engineers provide 1-on-1 selection & configuration advice
  • 100% genuine products guaranteed with rapid global delivery
UP
WhatsApp