Siemens 6ES7318-3FL00-0AB0 S7-300 CPU 319F-3 PN/DP

Series#: Siemens

Product Details

  • Siemens 6ES7318-3FL00-0AB0 S7-300 CPU 319F-3 PN/DP
  • Work memory: 1400 KB
  • First interface: MPI/DP, 12 Mbit/s
  • Second interface: PROFIBUS DP master/slave
  • Third interface: Ethernet PROFINET

Specification

Siemens 6ES7318-3FL00-0AB0 S7-300 CPU 319F-3 PN/DP.

Technical Specifications

SpecificationDetails
ManufacturerSiemens
Model / order reference6ES7318-3FL00-0AB0
Work memory1400 KB
First interfaceMPI/DP, 12 Mbit/s
Second interfacePROFIBUS DP master/slave
Third interfaceEthernet PROFINET
Memory card requirementMicro Memory Card required
Manufacturer approximate product weight1250 g Siemens reference, PDF page 14. Product/reference configuration only; no shipping mass inferred.

6ES7318-3FL00-0AB0 Procurement Questions

Which STEP 7 version do I need to engineer safety applications for this CPU?

STEP 7 as of version 5.4 + SP1 + HSP 121 is stated; for firmware as of V2.6.0, STEP 7 as of version 5.4 + SP2 + HSP 143 applies, and for firmware as of V2.7.0, STEP 7 as of version 5.4 + SP4.

Is an additional software package needed for safety engineering?

The optional package S7 Distributed Safety as of V5.4 + SP1 is listed for this CPU.

What failure probabilities are printed for the CPU 319F-3 PN/DP?

For the CPU 319F-3 PN/DP row: low demand mode less than 2E-04, high demand/continuous mode less than 3E-09 per hour, proof-test interval 20 years. The F-compatible row states low demand mode less than 1E-04, high demand/continuous mode less than 3E-09 per hour, proof-test interval 10 years.

Are safety-program data blocks copied to load memory by the RAMtoROM function?

No. Data blocks of the safety program are not copied from the work memory to the load memory by the RAMtoROM function.

Can F-DBs be created or deleted with SFC 22, SFC 23 or SFC 82?

No. F-DBs can neither be created nor deleted; this restriction is stated for SFC 22 "CREAT_DB", SFC 23 "DEL_DB" and SFC 82 "CREA_DBL".

Can the safety protector 6ES7195-7KF00-0XA0 be inserted in the same rack as this F-CPU?

Safety protector 6ES7195-7KF00-0XA0 in product versions 01 and 02 must not be inserted in the same rack as the F-CPU; the restriction does not apply to product version 03 and higher.

Validity / order number - the Product Information's own validity statement names CPU 319F-3 PN/DP, order number 6ES7318-3FL00-0AB0, as of hardware release 01 and firmware V2.5.2 (PI A5E01061862-04)
CPU 319F-3 PN/DP, order number 6ES7318-3FL00-0AB0, as of hardware release 01 and as of firmware version V2.5.2
Application areas (PI A5E01061862-04)
Mainly designed for personal and machine safety and burner controls; standard applications can also be programmed
Engineering - STEP 7 versions for safety applications (PI A5E01061862-04)
STEP 7 as of version 5.4 + SP1 + HSP 121 (for firmware as of V2.6.0: STEP 7 as of version 5.4 + SP2 + HSP 143; for firmware as of V2.7.0: STEP 7 as of version 5.4 + SP4)
Engineering - optional package S7 Distributed Safety (PI A5E01061862-04)
Optional package S7 Distributed Safety as of V5.4 + SP1
Process image I/O, default size - the 1024 Bytes/1024 Bytes value is the CPU 319F-3 PN/DP column (the same quote prints the base CPU 319-3 value 256 Bytes/256 Bytes first; column attribution verified by pdftotext -bbox word geometry) (PI A5E01061862-04)
1024 Bytes/1024 Bytes
Failure probability, F-compatible row (PI A5E01061862-04; column attribution geometry-verified)
Low demand mode less than 1E-04; high demand/continuous mode less than 3E-09 per hour; proof-test interval 10 years (F-compatible row)
Failure probability, CPU 319F-3 PN/DP row (PI A5E01061862-04; column attribution geometry-verified)
Low demand mode less than 2E-04; high demand/continuous mode less than 3E-09 per hour; proof-test interval 20 years (CPU 319F-3 PN/DP row)
RAMtoROM handling of safety-program data blocks (PI A5E01061862-04)
Data blocks of the safety program are not copied from the work memory to the load memory by the RAMtoROM function
F-DB creation/deletion restriction - SFC 22, SFC 23, SFC 82 (PI A5E01061862-04)
F-DBs can neither be created nor deleted (restriction for SFC 22, SFC 23 and SFC 82, stated in the section heading)
Safety protector rack restriction - 6ES7195-7KF00-0XA0 product versions 01 and 02 (PI A5E01061862-04)
Safety protector 6ES7195-7KF00-0XA0, product versions 01 and 02, must not be inserted in the same rack as the F-CPU (restriction does not apply to product version 03 and higher)

Facts follow the cited model table/reference configuration. Firmware, memory areas and interface roles are kept distinct. Product/reference weight appears only in the specifications table. No shipping mass, stock, pricing or ratings inferred.

Unmatched Customer Service

After Hours Shipping

Real Time Order Tracking

Flexible Delivery Options

Intact Technical Supports

What Does Our Clients Say

Mitsubishi MR-J4

Laura Navas

Great product!

2019/12/01

Keyence sensor

EQDR SALES

Original and fast!

2020/02/22

Need Professional Tech Support or a Quote?

  • Our senior engineers provide 1-on-1 selection & configuration advice
  • 100% genuine products guaranteed with rapid global delivery
UP
WhatsApp