Siemens 6ES5470-8MA12 SIMATIC S5 Analog Output Module

Series#: Siemens

Product Details

  • Siemens 6ES5470-8MA12 SIMATIC S5 Analog Output Module
  • Module type: SIMATIC S5 analog output 470
  • Analog outputs: 2 channels
  • Signal range: ±10 V
  • Listed host systems: S5-90U, S5-95U, S5-100U, ET 100U and ET 200U

Specification

Siemens 6ES5470-8MA12 SIMATIC S5 Analog Output Module.

Technical Specifications

SpecificationDetails
ManufacturerSiemens
Order number6ES5470-8MA12
Module typeSIMATIC S5 analog output 470
Analog outputs2 channels
Signal range±10 V
Listed host systemsS5-90U, S5-95U, S5-100U, ET 100U and ET 200U
IsolationIsolated, per manufacturer model description

6ES5470-8MA12 Procurement Questions

Is this an analog input or an analog output module?

It is an analog output module: the Siemens data sheet designates it as SIMATIC S5, Analog output 470, with 2 outputs +-10V.

Which controllers and I/O units is this module specified for?

The Siemens data sheet states it is isolated for S5-90U/-95U/-100U, ET 100U and ET 200U.

What is the output range and how many outputs does it have?

The manual lists a rated output range of ±10 V and a number of outputs of 2.

Are the outputs isolated from each other?

Yes. The manual states galvanic isolation is provided for the outputs to the grounding point and between outputs.

What supply voltage does the module require?

The manual gives a rated supply voltage L+ (peripheral) of 24 V DC, with a permissible range of 20 to 30 V (ripple included).

Is this order number still a current product?

The Siemens data sheet lists the lifecycle status as ***Spare part***.

Order number (as printed in the manual, space form)
6ES5 470-8MA12
Product designation (Siemens data sheet)
SIMATIC S5, Analog output 470
Compatibility and outputs (Siemens data sheet)
Isolated for S5-90U/-95U/-100U, ET 100U, ET 200U; 2 outputs +-10V
Lifecycle status (Siemens data sheet)
***Spare part***
Output range (rated values)
±10 V
Number of outputs
2
Galvanic isolation
yes (outputs to grounding point and between outputs)
Input resistance
min. 3.3 kΩ
Capacitive load incl. cable capacitance
<100 nF
Connection method
two- or four-wire
Digital representation — resolution
11 bits + sign
Digital representation — units
1024 units = rated value
Measured value representation
two's complement
Conversion time (0 to 100%)
max. 0.15 ms
Permissible overload
25%
Short-circuit protection
yes
Short-circuit current
±30 mA
Permissible voltage difference to ground and between outputs
max. 75 V DC/60 V AC
Basic error limits
±0.3%
Operational error limits (0 to 60 °C)
±0.6%
Length of cable (shielded)
max. 200 m (660 ft.)
Supply voltage L+ (peripheral) — rated value
24 V DC
Supply voltage L+ — permissible range
20 to 30 V (ripple included)
Supply voltage — ripple
3.6 Vpp
Current consumption from +9 V (CPU)
typ. 120 mA
Current consumption from L+
typ. 100 mA
Power loss of the module
typ. 3.1 W
Weight (module weight as printed)
approx. 220 g (10 oz.)

Technical facts follow the exact manufacturer model table or named reference. Conflicting or unestablished numeric claims are withheld. Weight appears only in the specifications table with source basis; no shipping-weight estimate is inferred.

Unmatched Customer Service

After Hours Shipping

Real Time Order Tracking

Flexible Delivery Options

Intact Technical Supports

What Does Our Clients Say