| Specification | Details |
|---|---|
| Manufacturer | Siemens |
| Model / order reference | 6ES5482-7LF21 |
| Read-back inputs | 16; P potential |
| Input use restriction | Only read-back inputs for 24 V safety-related outputs in the other subunit |
| Input isolation grouping | Optocoupler; groups of 8 connected to common M potential |
| Rated input voltage | 24 V DC |
| Permissible input voltage range | 20 to 30 V |
| Number of outputs and switched potential | 16; M potential |
| Rated output current and group-temperature limitation | 0.5 A at signal1; permitted group summed current:100% at 35°C,50% at 55°C |
| Internal current consumption from 5 V | Max. 50 mA |
| Power loss | Typ. 18 W |
| Manufacturer device weight | Approx. 0.7 kg |
They are only read-back inputs for 24 V safety-related outputs in the other subunit.
16 read-back inputs at P potential.
Rated input voltage is 24 V DC; the permissible input voltage range is 20 to 30 V.
Isolation is by optocoupler, with groups of 8 connected to common M potential.
16 outputs at M potential, rated 0.5 A at signal1; permitted group summed current is 100% at 35°C and 50% at 55°C.
Internal current consumption from 5 V is max. 50 mA; power loss is typ. 18 W.