Siemens 6ES7138-4CB10-0AB0 ET 200S PM-E Power Module

Series#: Siemens

Product Details

  • Siemens 6ES7138-4CB10-0AB0 ET 200S PM-E Power Module
  • Device role: PM-E power module for ET 200S
  • Diagnostic functions: Blown fuse and missing load voltage
  • Fuse: Internal replaceable 5 × 20 mm fuse, 250 V, 10 A, quick-response
  • Module dimensions (W × H × D): 15 × 81 × 52 mm

Specification

Siemens 6ES7138-4CB10-0AB0 ET 200S PM-E Power Module.

Technical Specifications

SpecificationDetails
ManufacturerSiemens
Order number6ES7138-4CB10-0AB0
Device rolePM-E power module for ET 200S
Diagnostic functionsBlown fuse and missing load voltage
FuseInternal replaceable 5 × 20 mm fuse, 250 V, 10 A, quick-response
Module dimensions (W × H × D)15 × 81 × 52 mm
Manufacturer approximate product weight34 g Siemens reference, PDF page 2. Source weight basis retained; no shipping mass inferred.

6ES7138-4CB10-0AB0 Procurement Questions

What supply voltages does the 6ES7138-4CB10-0AB0 power module support?

The rated load voltage is printed as 24–56.7 VDC and 24–48 VAC/120–230 VAC.

How much current can this power module carry at elevated ambient temperature?

For 24–56.7 VDC the maximum is 10 A up to 30 °C, 9 A up to 40 °C and 7 A up to 60 °C; for 24–48/120/230 VAC it is 8 A up to 30 °C, 7 A up to 40 °C and 5 A up to 60 °C.

How is short-circuit protection implemented on this module?

It uses a replaceable IEC 127-2/1, 250 V, 10 A fast fuse (5 x 20 mm).

Does the module draw current from the backplane bus?

Yes, current consumption from the backplane bus is max. 9.5 mA.

What is the power dissipation of the module?

Power dissipation of the module is max. 5 W.

Product type designation
PM-E 24–48 VDC, 24–230 VAC power module (6ES7138-4CB10-0AB0)
Dimensions
15 x 81 x 52 mm (W x H x D)
Device weight (as printed)
34g
Rated load voltage
24–56.7 VDC; 24–48 VAC/120–230 VAC
Overvoltage protection
Yes
Max. current-carrying capacity
10 A
Current-carrying capacity (derating)
for 24–56.7 VDC: max. 10 A up to 30 °C, max. 9 A up to 40 °C, max. 7 A up to 60 °C; for 24–48/120/230 VAC: max. 8 A up to 30 °C, max. 7 A up to 40 °C, max. 5 A up to 60 °C
Short-circuit protection
Yes, IEC 127-2/1, 250 V, 10 A, fast fuse (5 x 20 mm), replaceable
Insulation tested with
1500 VAC
Current consumption from backplane bus
max. 9.5 mA from the backplane bus
Current consumption from load voltage
max. 9 mA from load voltage L1/L+ (no load)
Power dissipation
max. 5 W
Diagnostic function
Yes

Technical facts follow the exact manufacturer model table or named reference. Conflicting or unestablished numeric claims are withheld. Weight appears only in the specifications table with source basis; no shipping-weight estimate is inferred.

Unmatched Customer Service

After Hours Shipping

Real Time Order Tracking

Flexible Delivery Options

Intact Technical Supports

What Does Our Clients Say

Mitsubishi MR-J4

Laura Navas

Great product!

2019/12/01

Keyence sensor

EQDR SALES

Original and fast!

2020/02/22

Need Professional Tech Support or a Quote?

  • Our senior engineers provide 1-on-1 selection & configuration advice
  • 100% genuine products guaranteed with rapid global delivery
UP
WhatsApp