Allen-Bradley 1769-L18ER-BB1B Controller

Series#: AllenBradley

Product Details

  • Allen-Bradley 1769-L18ER-BB1B Controller
  • Embedded digital I/O: 16 DC inputs; 16 DC outputs
  • Local expansion: 8 x 1734 POINT I/O modules maximum

Specification

Allen-Bradley 1769-L18ER-BB1B — Controller.

Technical Specifications

SpecificationDetails
ManufacturerAllen-Bradley
Catalog number1769-L18ER-BB1B
Embedded digital I/O16 DC inputs; 16 DC outputs
Local expansion8 x 1734 POINT I/O modules maximum
Manufacturer approximate product weight0.66 kg — packaging inclusion not specified
1769-TD005O-EN-P (November 2023), p. 7

Ordering & Compatibility

Do not select 1769 expansion modules for the local POINT I/O bus.

Match the complete catalog number, hardware series, installed configuration and required accessories before ordering. Unit condition, package contents, delivery and warranty must be confirmed in the quotation.

1769-L18ER-BB1B Procurement Questions

How much user memory does the 1769-L18ER-BB1B provide?

The 1769-L18ER-BB1B provides 512 KB of available user memory.

Which memory card is shipped with the 1769-L18ER-BB1B, and what alternative is listed?

The 1784-SD1 (1 GB) is shipped with the controller; the 1784-SD2 (2 GB) is also listed.

What communication ports does the 1769-L18ER-BB1B have?

It has 2 EtherNet/IP ports and 1 USB port.

How many EtherNet/IP connections and TCP connections does the 1769-L18ER-BB1B support?

It supports 256 EtherNet/IP connections and 120 TCP connections.

How many EtherNet/IP nodes and POINT I/O expansion modules can the 1769-L18ER-BB1B support?

It supports a maximum of 8 EtherNet/IP nodes and has a module expansion capacity of 8 POINT I/O modules.

Does the 1769-L18ER-BB1B support motion axes, and what is its embedded power supply rating?

Axes supported and CIP Drive axes (position loop) supported are both listed as Not Applicable for this model. The embedded power supply is 10…28.8V DC with 24V DC nominal; only Series B power supply modules are isolated, while Series A modules are non-isolated.

Available user memory
512 KB
Memory card
1784-SD1 (1 GB), shipped with controller; 1784-SD2 (2 GB)
Communication ports
2 EtherNet/IP; 1 USB
Embedded I/O
16 sinking 24V DC digital input points; 16 sourcing 24V DC digital output points
EtherNet/IP connections
256 EtherNet/IP; 120 TCP
EtherNet/IP nodes supported, max
8
Axes supported, max
Not Applicable
CIP Drive axes (position loop) supported, max
Not Applicable
Module expansion capacity
8 POINT I/O modules
Battery
None
Embedded power supply
10…28.8V DC; 24V DC nominal; isolation: only Series B power supply modules are isolated; Series A modules are non-isolated (footnote (1), p.12)

Technical specifications are based on the linked manufacturer references.

Unmatched Customer Service

After Hours Shipping

Real Time Order Tracking

Flexible Delivery Options

Intact Technical Supports

What Does Our Clients Say

Mitsubishi MR-J4

Laura Navas

Great product!

2019/12/01

Keyence sensor

EQDR SALES

Original and fast!

2020/02/22

Need Professional Tech Support or a Quote?

  • Our senior engineers provide 1-on-1 selection & configuration advice
  • 100% genuine products guaranteed with rapid global delivery
UP
WhatsApp