1768-PA3 Procurement Questions
Is the 1768-PA3 a controller or a power supply?
It is a power supply for the 1768 backplane, not a controller. No controller attributes such as user memory, I/O capacity or communication ports apply to this catalog number.
What input voltages does the 1768-PA3 accept?
It is a dual-input supply: 85…265V AC or 108…132V DC, with nominal input voltage 120V/220V AC and input frequency range 47…63 Hz.
What are the output ratings of the 1768-PA3?
Maximum output power is 90 W. The card lists 24V DC to backplane: 3.5 (printed without a current-unit glyph in the source text layer) and 24V DC to user-accessible terminal block: 0.25 A.
How is the 1768-PA3 mounted and what enclosure does it have?
Module location is DIN rail or panel mount, and the enclosure type rating is None (open-style). Mounting screw torque is 1.16 N•m (10 lb•in) using M4 or #8 screws.
What overcurrent protection does the 1768-PA3 require?
Internal overcurrent protection is a non-replaceable fuse soldered in place. Recommended external overcurrent protection is 4…6 A @ 28.5…36.7 A2S, and overcurrent protection is 15 A, user supplied.
What environmental range does the 1768-PA3 support?
Operating temperature is 0 °C< Ta < 60 °C (32 °F< Ta < 140 °F), storage is -40…+85 °C (-40…+185 °F), and relative humidity is 5…95% noncondensing.
- Catalog number
- 1768-PA3
- Input voltage range AC
- 85…265V AC
- Input voltage range DC
- 108…132V DC
- Input voltage nom
- 120V/220V AC
- Input frequency range
- 47…63 Hz
- Input power max
- 120VA/120 W
- Output power max
- 90 W
- Backplane output
- 24V DC to backplane: 3.5
- User terminal output
- 24V DC to user-accessible terminal block: 0.25 A
- Output power min backplane
- 24V DC to backplane: 0.25 A
- Power dissipation
- 30 W
- Inrush current, max (AC low range)
- 50 A @ 85…132V AC
- Inrush current, max (AC high range)
- 80 A @ 195…265V AC
- Isolation voltage input
- 250V, reinforced insulation type, input to system and 24V DC AUX; tested at 4250V DC for 60 s
- Isolation voltage aux
- 150V, basic insulation type, 24V DC AUX to system; tested at 2200V DC for 60 s
- Internal overcurrent protection
- Non-replaceable fuse is soldered in place
- Recommended external overcurrent protection
- 4…6 A @ 28.5…36.7 A2S
- Overcurrent protection max
- 15 A, user supplied
- Weight, approx.
- 0.98 kg (2.15 lb)
- Dimensions, approx.
- 131.25 x 132.75 x 105.50 mm (5.17 x 5.23 x 4.15 in.)
- Module location
- DIN rail or panel mount
- Mounting screw torque
- 1.16 N•m (10 lb•in) - use M4 or #8 screws
- Wire category
- 1 - on power ports
- Wire size input power terminal
- 14 AWG (2.5 mm2) solid or stranded copper wire rated at 75 °C (167 °F) or greater, 1.2 mm (3/64 in.) insulation maximum
- Wire size output power terminal
- 14 AWG (2.5 mm2)…22 AWG (0.25 mm2) solid or stranded copper wire rated at 75 °C (167 °C) or greater, 1.2 mm (3/64 in.) insulation max
- Conductor screw torque
- 0.6 N•m (5 lb•in)
- North American temperature code
- T4
- Ride through interval min
- 25 ms @ 90 W
- Full power hold up interval
- 5 ms @ 90 W
- Extended hold up interval
- 8...12 s @ 1.25 W
- Output 2 voltage (front panel)
- 18...27.60V @ front panel
- Enclosure type rating
- None (open-style)
- Temperature operating
- 0 °C< Ta < 60 °C (32 °F< Ta < 140 °F)
- Temperature storage
- -40…+85 °C (-40…+185 °F)
- Relative humidity
- 5…95% noncondensing
- Vibration
- 5 g at 10…500 Hz
- Shock operating
- 30 g
- Shock nonoperating
- 50 g
- Certification — UL listing
- UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
- Certification — UL hazardous-location listing
- UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.