1769-IQ6XOW4 Procurement Questions
What input voltage range does the 1769-IQ6XOW4 accept?
The inputs are 24V DC sink/source, with an operating voltage range of 10…30V DC @ 30 °C (86 °F) and 10…26.4V DC @ 60 °C (140 °F).
What are the relay output contact ratings at 240V AC?
At 240V AC the continuous amps per point, max is 2.5 A; make is 7.5 A; break is 0.75 A; voltamperes, make is 1800VA; voltamperes, break is 180VA; NEMA ICS 2-125 is C300.
How are the DC relay contact ratings determined?
For DC voltage applications, the make/break ampere rating for relay contacts can be determined by dividing 28 VA by the applied DC voltage; for example, 28 VA/48V DC = 0.58A. For DC voltage applications less than 48V, the make/break ratings for relay contacts cannot exceed 2A.
Which power supplies are listed for this module?
The listed power supplies are 1769-PA2, 1769-PB2, 1769-PA4, and 1769-PB4.
What wire size and wire type are specified for the terminals?
Wire size is (22…14 AWG) solid and (22…16 AWG) stranded; wire type is Cu-90 °C (194 °F).
What are the on and off input delays?
The input delay, on is 8 ms and the delay, off is 8 ms.
- Current draw @ 5.1V
- 105 mA
- Current draw @ 24V
- 50 mA
- Heat dissipation, max
- 2.75 W
- Off-state voltage, max
- 11V DC
- Isolation voltage
- Verified by one of the following dielectric tests: 1200V AC for 1 s or 1697V DC for 1 s, input group to bus, output group to bus, and input group to output group; 75V DC working voltage (IEC Class 2 reinforced insulation)
- Weight, approx (product weight as published)
- 280 g (0.61 lb)
- Dimensions (HxWxD), approx
- 118 x 35 x 87 mm (4.65 x 1.38 x 3.43 in.) Height with mounting tabs 138 mm (5.43 in.)
- Slot width
- 1
- Module location
- DIN rail or panel mount
- Power supply
- 1769-PA2, 1769-PB2, 1769-PA4, 1769-PB4
- Power supply distance rating
- 8 modules
- Terminal screw torque
- 0.68 N·m (6 lb·in)
- Retaining screw torque
- 0.46 N·m (4.1 lb·in)
- Wire size
- (22…14 AWG) solid (22…16 AWG) stranded
- Wire type
- Cu-90 °C (194 °F)
- IEC input compatibility
- Type 1+
- Replacement terminal block
- 1769-RTBN18 (1 per kit)
- Replacement door label
- 1769-RL1 (2 per kit)
- Replacement door
- 1769-RD (2 per kit)
- Vendor ID code
- 1
- Product type code
- 7
- Product code
- 66
- Enclosure type rating
- None (open-style)
- Inputs
- 6
- Voltage category
- 24V DC sink/source
- Operating voltage range
- 10…30V DC @ 30 °C (86 °F) 10…26.4V DC @ 60 °C (140 °F)
- Delay, on
- 8 ms
- Delay, off
- 8 ms
- Off-state voltage, max
- 5V DC
- Off-state current, max
- 1.5 mA
- On-state voltage, mi
- 10V DC
- On-state current, min
- 2.0 mA
- Inrush current, max
- 250 mA
- Input impedance, nom
- 3 kΩ
- IEC input compatibility
- Type 3
- Outputs
- 4
- Voltage category
- AC/DC normally open relay contacts
- Operating voltage range
- 5…265V AC 5…125V DC
- Delay, on
- 10 ms
- Delay, off
- 10 ms
- Off-state leakage, max
- 0 mA
- On-state current, min
- 10 mA @ 5V DC
- Current per point, max
- 2.5 A
- Current per module, max
- 8A
- Relay contact rating @ 240V AC
- Continuous amps per point, max: 2.5 A; Make: 7.5 A; Break: 0.75 A; Voltamperes, make: 1800VA; Voltamperes, break: 180VA; NEMA ICS 2-125: C300
- Relay contact rating @ 120V AC
- Continuous amps per point, max: 2.5 A; Make: 15 A; Break: 1.5 A; Voltamperes, make: 1800VA; Voltamperes, break: 180VA
- Relay contact rating @ 125V DC
- Continuous amps per point, max: 1.0 A; Break: 0.22 A; Voltamperes, break: 28VA; NEMA ICS 2-125: R150 (footnote (2) of Table 41: For DC voltage applications, the make/break ampere rating for relay contacts can be determined by dividing 28 VA by the applied DC voltage. For example, 28 VA/48V DC = 0.58A. For DC voltage applications less than 48V, the make/break ratings for relay contacts cannot exceed 2A.)
- Relay contact rating @ 24V DC
- Continuous amps per point, max: 2.0 A; Break: 1.2 A; Voltamperes, break: 28VA; NEMA ICS 2-125: — (footnote (2) of Table 41: For DC voltage applications, the make/break ampere rating for relay contacts can be determined by dividing 28 VA by the applied DC voltage. For example, 28 VA/48V DC = 0.58A. For DC voltage applications less than 48V, the make/break ratings for relay contacts cannot exceed 2A.)