1769-IF16V Procurement Questions
What input ranges does the 1769-IF16V support?
The module supports input ranges of ±10V, 0…10V, 0…5V and 1…5V across its 16 single-ended inputs.
What happens when the normal operating range is exceeded?
The over- or under-range flag comes on when the normal operating range (over/under) is exceeded; the module continues to convert the analog input up to the maximum full scale range, and the flag automatically resets when within the normal operating range.
How does filter selection affect resolution and response speed?
Resolution depends on filter selection, with maximum resolution achieved with either the 50 or 60 Hz filter selected. Response speed varies by filter: at 16 Hz the step response is 1550 ms, update per input pair 200 ms and update per module 1600 ms; at 50 Hz, 500 ms, 70 ms and 560 ms; at 60 Hz, 420 ms, 60 ms and 480 ms; at 315 Hz, 90 ms, 15 ms and 120 ms; at 1365 Hz, 35 ms, 5 ms and 40 ms.
What are the common mode voltage requirements?
The common mode voltage range is ±10V DC max per channel; for proper operation, both the plus and minus input terminals must be within ±10V DC of analog common.
What overload can the input terminals withstand?
The maximum overload at the input terminals is ±30 mA continuous, ±7.6V DC; damage may occur to the input circuit if this value is exceeded.
Which power supplies are listed for this module and how far can it sit from the supply?
The listed power supplies are 1769-PA2, 1769-PB2, 1769-PA4 and 1769-PB4, and the power supply distance rating is 8 modules.
- Inputs
- 16 single-ended
- Input range
- ±10V 0…10V 0…5V 1…5V
- Full scale range
- ±10.5V -0.5…10.5V -0.5…5.25V 0.5…5.25V (footnote (1) of Table 25: The over- or under-range flag will come on when the normal operating range (over/under) is exceeded. The module will continue to convert the analog input up to the maximum full scale range. The flag automatically resets when within the normal operating range.)
- Current draw @ 5.1V
- 190 mA
- Current draw @ 24V
- 70 mA
- Heat dissipation, max
- 2.4 W
- Converter type
- Sigma Delta
- Resolution
- 16 bits (unipolar) 15 bits plus sign (bipolar) (footnote (2) of Table 25: Resolution is dependent upon your filter selection. The maximum resolution is achieved with either the 50 or 60 Hz filter selected.)
- Rated working voltage
- 30V AC/30V DC (footnote (3) of Table 25: Rated working voltage is the maximum continuous voltage that can be applied at the input terminal, including the input signal and the value that floats above ground potential (for example, 10V DC input signal and 20V DC potential above ground).)
- Common mode voltage range
- ±10V DC max per channel (footnote (4) of Table 25: For proper operation, both the plus and minus input terminals must be within ±10V DC of analog common.)
- Common mode rejection
- > 60 dB @ 50 and 60 Hz with the 16 Hz filter selected
- Input impedance
- > 1MΩ
- Accuracy
- ±0.35% full scale @ 25 °C (77 °F) (footnote (5) of Table 25: Includes offset, gain, nonlinearity, and repeatability error terms.)
- Accuracy drift with temperature
- ±0.03% per °C
- Nonlinearity
- ±0.03%
- Repeatability
- ±0.06% (footnote (6) of Table 25: Repeatability is the ability of the input module to register the same reading in successive measurements for the same input signal.)
- Module error
- 1.0%
- Overload at input terminals, max
- ±30 mA continuous, ±7.6V DC (footnote (7) of Table 25: Damage may occur to the input circuit if this value is exceeded.)
- Isolation voltage
- 500V AC or 710V DC for 1 minute (qualification test), group to bus 30V AC/30V DC working voltage (IEC Class 2 reinforced insulation)
- Weight, approx (product weight as published)
- 281 g (0.62 lb)
- Dimensions (HxWxD), approx
- 118 x 35 x 87 mm (4.65 x 1.38 x 3.43 in.) Height with mounting tabs 138 mm (5.43 in.)
- Slot width
- 1
- Module location
- DIN rail or panel mount
- Power supply
- 1769-PA2, 1769-PB2, 1769-PA4, 1769-PB4
- Power supply distance rating
- 8 modules
- Terminal screw torque
- 0.68 N·m (6 lb·in)
- Retaining screw torque
- 0.46 N·m (4.1 lb·in)
- Wire size
- (22…14 AWG) solid (22…16 AWG) stranded
- Wire type
- Cu-90 °C (194 °F)
- Replacement terminal block
- 1769-RTBN18 (1 per kit)
- Replacement door label
- 1769-RL2 series B (2 per kit)
- Replacement door
- 1769-RD (2 per kit)
- Vendor ID code
- 1
- Product type code
- 10
- Product code
- 46
- Input words
- 22
- Output words
- 2
- Configuration words
- 98
- Enclosure type rating
- None (open-style)
- Response speed @ 16 Hz filter
- Step Response: 1550 ms; Update per Input Pair: 200 ms; Update per Module: 1600 ms
- Response speed @ 50 Hz filter
- Step Response: 500 ms; Update per Input Pair: 70 ms; Update per Module: 560 ms
- Response speed @ 60 Hz filter
- Step Response: 420 ms; Update per Input Pair: 60 ms; Update per Module: 480 ms
- Response speed @ 315 Hz filter
- Step Response: 90 ms; Update per Input Pair: 15 ms; Update per Module: 120 ms
- Response speed @ 1365 Hz filter
- Step Response: 35 ms; Update per Input Pair: 5 ms; Update per Module: 40 ms
Technical specifications are based on the linked manufacturer references.