Allen-Bradley 1769-OF2 Analog Output Module

Series#: AllenBradley

Product Details

  • Allen-Bradley 1769-OF2 Analog Output Module
  • Outputs: 2 single-ended
  • Signal types: Voltage and current

Specification

Allen-Bradley 1769-OF2 — Analog Output Module.

Technical Specifications

SpecificationDetails
ManufacturerAllen-Bradley
Catalog number1769-OF2
Outputs2 single-ended
Signal typesVoltage and current
Manufacturer approximate product weight0.3 kg — packaging inclusion not specified
1769-TD006H-EN-P (November 2023), p. 47

Ordering & Compatibility

Do not assume channel-to-channel isolation from output-group-to-bus isolation.

Match the complete catalog number, hardware series, installed configuration and required accessories before ordering. Unit condition, package contents, delivery and warranty must be confirmed in the quotation.

1769-OF2 Procurement Questions

What output ranges does the 1769-OF2 support?

The module supports ±10V, 0…10V, 0…5V, 1…5V, 0…20 mA and 4…20 mA output ranges.

What is the maximum resistive load on the current output?

The resistive load on the current output is 0…500 Ω, which includes wire resistance.

What load range applies to the voltage output?

The load range on voltage output is > 1 kΩ @ 10V DC, and the current load on voltage output, max is 10 mA.

How accurate is the 1769-OF2 at 25 °C?

Accuracy is Voltage: ±0.5% full scale @ 25 °C (77 °F) and Current: ±0.35% full scale @ 25 °C (77 °F); this includes offset, gain, nonlinearity, and repeatability error terms.

What isolation does the module provide?

Isolation voltage is 500V AC or 710V DC for 1 min (qualification test), output group to bus, with 30V AC/30V DC working voltage (IEC Class 2 reinforced insulation).

What wire size and terminal screw torque are specified?

Wire size is (22…14 AWG) solid or (22…16 AWG) stranded, and terminal screw torque is 0.68 N·m (6 lb·in).

Outputs
2 single-ended
Output range
±10V 0…10V 0…5V 1…5V 0…20 mA 4…20 mA
Full scale range
±10.5V -0.5…10.5V -0.5…5.25V 0.5…5.25V 0…21 mA 3.2…21 mA (footnote (1) of Table 64: The over- or under-range flag will come on when the normal operating range (over/under) is exceeded. The module will continue to convert the analog input up to the maximum full scale range. The flag automatically resets when within the normal operating range.)
Resolution
14 bits (unipolar) 14 bits plus sign (bipolar) ±10V DC: sign + 14 bits, 0.64 mV 0…10V DC: sign + 13 bits, 0.64 mV 0…5V DC: sign + 14 bits, 0.64 mV 1…5V DC: sign + 14 bits, 1.28 PA 0…20 mA: sign + 13 bits, 0.64 mV 4…20 mA: sign + 14 bits, 1.28PA
Current draw @ 5.1V
120 mA
Current draw @ 24V
120 mA
Converter type
Delta Sigma
Heat dissipation, max
2.63 W
Conversion rate (all channels), max
2.5 ms
Step response to 63%
2.9 ms (footnote (2) of Table 64: Step response is the period of time between when the D/A converter was instructed to go from minimum to full range until the device is at 63% of full range.)
Current load on voltage output, max
10 mA
Resistive load on current output
0…500 Ω(includes wire resistance)
Load range on voltage output
> 1 kΩ @ 10V DC
Inductive load (current outputs), max
0.1 mH
Capacitive load (voltage outputs), max
1 PF
Field calibration
None required
Accuracy
Voltage: ±0.5% full scale @ 25 °C (77 °F) Current: ±0.35% full scale @ 25 ° C (77 °F) (footnote (3) of Table 64: Includes offset, gain, nonlinearity, and repeatability error terms.)
Accuracy drift with temperature
Voltage: ±0.0086% per °C Current: ±0.0058% per °C
Output ripple
±0.05% @ 0…50 kHz (footnote (4) of Table 64: Output ripple is the amount a fixed output varies with time, assuming a constant load and temperature.)
Nonlinearity
±0.05%
Repeatability
±0.05% (footnote (5) of Table 64: Repeatability is the ability of the input module to register the same reading in successive measurements for the same input signal.)
Module error
Voltage: ±0.8% Current: ±0.55%
Offset error
±0.05%
Output impedance
15 Ω
Open and short-circuit protection
Yes
Short-circuit protection, max
21 mA
Output overvoltage protection
Yes
Time to detect open wire condition (current mode)
10 ms, typical 13.5 ms, max
Output response at system powerup and power down
±5V DC spike for < 5 ms
Rated working voltage
30V AC/30V DC (footnote (6) of Table 64: Rated working voltage is the maximum continuous voltage that can be applied at the input terminal, including the input signal and the value that floats above ground potential (for example, 10V DC input signal and 20V DC potential above ground).)
Isolation voltage
500V AC or 710V DC for 1 min (qualification test), output group to bus 30V AC/30V DC working voltage (IEC Class 2 reinforced insulation)
Weight, approx (product weight as published)
300 g (0.65 lb)
Dimensions (HxWxD), approx
118 x 35 x 87 mm (4.65 x 1.38 x 3.43 in.) Height with mounting tabs 138 mm (5.43 in.)
Slot width
1
Module location
DIN rail or panel mount
Power supply
1769-PA2, 1769-PB2, 1769-PA4, 1769-PB4
Optional 24V DC Class 2 power supply voltage range
20.4…26.4V DC (footnote (7) of Table 64: If the optional 24V DC Class 2 power supply is used, the 24V DC current draw from the bus is 0 mA.)
Power supply distance rating
8 modules
Terminal screw torque
0.68 N·m (6 lb·in)
Retaining screw torque
0.46 N·m (4.1 lb·in)
Wire size
(22…14 AWG) solid (22…16 AWG) stranded
Wire type
Cu-90 °C (194 °F)
Replacement terminal block
1769-RTBN18 (1 per kit)
Replacement door label
1769-RL2 (2 per kit)
Replacement door
1769-RD (2 per kit)
Vendor ID code
1
Product type code
10
Product code
32
Enclosure type rating
None (open style)

Technical specifications are based on the linked manufacturer references.

Unmatched Customer Service

After Hours Shipping

Real Time Order Tracking

Flexible Delivery Options

Intact Technical Supports

What Does Our Clients Say

Mitsubishi MR-J4

Laura Navas

Great product!

2019/12/01

Keyence sensor

EQDR SALES

Original and fast!

2020/02/22

Need Professional Tech Support or a Quote?

  • Our senior engineers provide 1-on-1 selection & configuration advice
  • 100% genuine products guaranteed with rapid global delivery
UP
WhatsApp