1769-OF4 Procurement Questions
Which output ranges does the 1769-OF4 support?
The module supports ±10V, 0…10V, 0…5V, 1…5V, 0…20 mA and 4…20 mA output ranges.
What happens when the normal operating range is exceeded?
The over- or under-range flag comes on when the normal operating range (over/under) is exceeded; the module continues to convert the analog input up to the maximum full scale range, and the flag automatically resets when within the normal operating range.
What load can the outputs drive?
For current output the resistive load is 0…600 Ω (includes wire resistance); for voltage output it is 1 KΩ or greater. Maximum inductive load is 0.1 mH for current load and 1.0 μF for voltage load.
What is the conversion rate for all channels?
The maximum conversion rate for all channels is 2.5 ms with interrupts not enabled and 3.8 ms with interrupts enabled.
What power supply options and voltage range apply?
Power supplies listed are 1769-PA2, 1769-PB2, 1769-PA4 and 1769-PB4; the optional 24V DC Class 2 power supply voltage range is 20.4…26.4V DC, and if that optional supply is used the 24V DC current draw from the bus is 0 mA.
What wire size and terminal screw torque are specified?
Wire size is (22…14 AWG) solid and (22…16 AWG) stranded, with Cu-90 °C (194 °F) wire type; terminal screw torque is 0.68 N·m (6 lb·in).
- Outputs
- 4 single-ended
- Output range
- ±10V 0…10V 0…5V 1…5V 0…20 mA 4…20 mA
- Full scale range
- ±10.5V -0.5…10.5V -0.5…5.25V 0.5…5.25V 0…21 mA 3.2…21 mA (footnote (1) of Table 66: The over- or under-range flag will come on when the normal operating range (over/under) is exceeded. The module will continue to convert the analog input up to the maximum full scale range. The flag automatically resets when within the normal operating range.)
- Resolution
- 15 bits plus sign unipolar and bipolar
- Current draw @ 5.1V
- 120 mA
- Current draw @ 24V
- 170 mA
- Heat dissipation, max
- 2.86 W
- Conversion rate (all channels), max
- Interrupts not enabled: 2.5 ms Interrupts enabled: 3.8 ms
- Step response to 63%
- 2.9 ms (footnote (2) of Table 66: Step response is the period of time between when the D/A converter was instructed to go from minimum to full range until the device is at 63% of full range.)
- Resistive load
- Current: 0…600 Ω (includes wire resistance) Voltage: 1 K: or greater
- Inductive load, max
- 0.1 mH (current load) 1.0 μF (voltage load)
- Field calibration
- None required
- Accuracy
- 0.5% full scale at 25 °C (77 °F) (footnote (3) of Table 66: Includes offset, gain, drift, nonlinearity, and repeatability error terms.)
- Accuracy drift with temperature
- ±0.0086% of full scale per °C
- Output ripple
- ±0.05% @ 0…50 kHz (footnote (4) of Table 66: Output ripple is the amount a fixed output varies with time, assuming a constant load and temperature.)
- Nonlinearity
- ±0.05% (5)
- Repeatability
- ±0.05%
- Module error
- +/-0.8% of full scale
- Output impedance
- Voltage output: < 1 Ω Current output: > 1 MΩ
- Open and short-circuit protection
- Yes
- Short-circuit protection, max
- 40 mA
- Output overvoltage protection
- Yes
- Output response at system power up and power down
- 2.5…-1.0V DC spike for < 15 ms
- Rated working voltage
- 30V AC/30V DC (footnote (6) of Table 66: Rated working voltage is the maximum continuous voltage that can be applied at the input terminal, including the input signal and the value that floats above ground potential (for example, 10V DC input signal and 20V DC potential above ground).)
- Isolation voltage
- 510V AC or 720V DC for 1 minute (qualification test), output group to bus 30V AC/30V DC working voltage (IEC Class 2 reinforced insulation)
- Weight, approx (product weight as published)
- 280 g (0.61 lb)
- Dimensions (HxWxD), approx
- 118 x 35 x 87 mm (4.65 x 1.38 x 3.43 in.) Height with mounting tabs 138 mm (5.43 in.)
- Slot width
- 1
- Module location
- DIN rail or panel mount
- Power supply
- 1769-PA2, 1769-PB2, 1769-PA4, 1769-PB4
- Optional 24V DC Class 2 power supply voltage range
- 20.4…26.4V DC (footnote (7) of Table 66: If the optional 24V DC Class 2 power supply is used, the 24V DC current draw from the bus is 0 mA.)
- Power supply distance rating
- 8 modules
- Terminal screw torque
- 0.68 N·m (6 lb·in)
- Retaining screw torque
- 0.46 N·m (4.1 lb·in)
- Wire size
- (22…14 AWG) solid (22…16 AWG) stranded
- Wire type
- Cu-90 °C (194 °F)
- Replacement terminal block
- 1769-RTBN18 (1 per kit)
- Replacement door label
- 1769-RL2 (2 per kit)
- Replacement door
- 1769-RD (2 per kit)
- Vendor ID code
- 1
- Product type code
- 10
- Product code
- 48
- Input words
- 5
- Output words
- 5
- Configuration words
- 32
- Enclosure type rating
- None (open style)
Technical specifications are based on the linked manufacturer references.