Allen-Bradley 1769-OF4 — Analog Output Module.

Technical Specifications

SpecificationDetails
ManufacturerAllen-Bradley
Catalog number1769-OF4
Outputs4 single-ended
Signal typesVoltage and current
Manufacturer approximate product weight0.28 kg — packaging inclusion not specified
1769-TD006H-EN-P (November 2023), p. 48

Ordering & Compatibility

The OF4 is not the individually isolated OF4CI or OF4VI.

Match the complete catalog number, hardware series, installed configuration and required accessories before ordering. Unit condition, package contents, delivery and warranty must be confirmed in the quotation.

1769-OF4 Procurement Questions

Which output ranges does the 1769-OF4 support?

The module supports ±10V, 0…10V, 0…5V, 1…5V, 0…20 mA and 4…20 mA output ranges.

What happens when the normal operating range is exceeded?

The over- or under-range flag comes on when the normal operating range (over/under) is exceeded; the module continues to convert the analog input up to the maximum full scale range, and the flag automatically resets when within the normal operating range.

What load can the outputs drive?

For current output the resistive load is 0…600 Ω (includes wire resistance); for voltage output it is 1 KΩ or greater. Maximum inductive load is 0.1 mH for current load and 1.0 μF for voltage load.

What is the conversion rate for all channels?

The maximum conversion rate for all channels is 2.5 ms with interrupts not enabled and 3.8 ms with interrupts enabled.

What power supply options and voltage range apply?

Power supplies listed are 1769-PA2, 1769-PB2, 1769-PA4 and 1769-PB4; the optional 24V DC Class 2 power supply voltage range is 20.4…26.4V DC, and if that optional supply is used the 24V DC current draw from the bus is 0 mA.

What wire size and terminal screw torque are specified?

Wire size is (22…14 AWG) solid and (22…16 AWG) stranded, with Cu-90 °C (194 °F) wire type; terminal screw torque is 0.68 N·m (6 lb·in).

Outputs
4 single-ended
Output range
±10V 0…10V 0…5V 1…5V 0…20 mA 4…20 mA
Full scale range
±10.5V -0.5…10.5V -0.5…5.25V 0.5…5.25V 0…21 mA 3.2…21 mA (footnote (1) of Table 66: The over- or under-range flag will come on when the normal operating range (over/under) is exceeded. The module will continue to convert the analog input up to the maximum full scale range. The flag automatically resets when within the normal operating range.)
Resolution
15 bits plus sign unipolar and bipolar
Current draw @ 5.1V
120 mA
Current draw @ 24V
170 mA
Heat dissipation, max
2.86 W
Conversion rate (all channels), max
Interrupts not enabled: 2.5 ms Interrupts enabled: 3.8 ms
Step response to 63%
2.9 ms (footnote (2) of Table 66: Step response is the period of time between when the D/A converter was instructed to go from minimum to full range until the device is at 63% of full range.)
Resistive load
Current: 0…600 Ω (includes wire resistance) Voltage: 1 K: or greater
Inductive load, max
0.1 mH (current load) 1.0 μF (voltage load)
Field calibration
None required
Accuracy
0.5% full scale at 25 °C (77 °F) (footnote (3) of Table 66: Includes offset, gain, drift, nonlinearity, and repeatability error terms.)
Accuracy drift with temperature
±0.0086% of full scale per °C
Output ripple
±0.05% @ 0…50 kHz (footnote (4) of Table 66: Output ripple is the amount a fixed output varies with time, assuming a constant load and temperature.)
Nonlinearity
±0.05% (5)
Repeatability
±0.05%
Module error
+/-0.8% of full scale
Output impedance
Voltage output: < 1 Ω Current output: > 1 MΩ
Open and short-circuit protection
Yes
Short-circuit protection, max
40 mA
Output overvoltage protection
Yes
Output response at system power up and power down
2.5…-1.0V DC spike for < 15 ms
Rated working voltage
30V AC/30V DC (footnote (6) of Table 66: Rated working voltage is the maximum continuous voltage that can be applied at the input terminal, including the input signal and the value that floats above ground potential (for example, 10V DC input signal and 20V DC potential above ground).)
Isolation voltage
510V AC or 720V DC for 1 minute (qualification test), output group to bus 30V AC/30V DC working voltage (IEC Class 2 reinforced insulation)
Weight, approx (product weight as published)
280 g (0.61 lb)
Dimensions (HxWxD), approx
118 x 35 x 87 mm (4.65 x 1.38 x 3.43 in.) Height with mounting tabs 138 mm (5.43 in.)
Slot width
1
Module location
DIN rail or panel mount
Power supply
1769-PA2, 1769-PB2, 1769-PA4, 1769-PB4
Optional 24V DC Class 2 power supply voltage range
20.4…26.4V DC (footnote (7) of Table 66: If the optional 24V DC Class 2 power supply is used, the 24V DC current draw from the bus is 0 mA.)
Power supply distance rating
8 modules
Terminal screw torque
0.68 N·m (6 lb·in)
Retaining screw torque
0.46 N·m (4.1 lb·in)
Wire size
(22…14 AWG) solid (22…16 AWG) stranded
Wire type
Cu-90 °C (194 °F)
Replacement terminal block
1769-RTBN18 (1 per kit)
Replacement door label
1769-RL2 (2 per kit)
Replacement door
1769-RD (2 per kit)
Vendor ID code
1
Product type code
10
Product code
48
Input words
5
Output words
5
Configuration words
32
Enclosure type rating
None (open style)

Technical specifications are based on the linked manufacturer references.

Unmatched Customer Service

After Hours Shipping

Real Time Order Tracking

Flexible Delivery Options

Intact Technical Supports

What Does Our Clients Say

Mitsubishi MR-J4

Laura Navas

Great product!

2019/12/01

Keyence sensor

EQDR SALES

Original and fast!

2020/02/22

Need Professional Tech Support or a Quote?

  • Our senior engineers provide 1-on-1 selection & configuration advice
  • 100% genuine products guaranteed with rapid global delivery
UP
WhatsApp