Allen-Bradley 1769-OF8C Analog Output Module

Series#: AllenBradley

Product Details

  • Allen-Bradley 1769-OF8C Analog Output Module
  • Outputs: 8 single-ended
  • Signal type: Current

Specification

Allen-Bradley 1769-OF8C — Analog Output Module.

Technical Specifications

SpecificationDetails
ManufacturerAllen-Bradley
Catalog number1769-OF8C
Outputs8 single-ended
Signal typeCurrent
Manufacturer approximate product weight0.281 kg — packaging inclusion not specified
1769-TD006H-EN-P (November 2023), p. 51

Ordering & Compatibility

OF8C has shared analog-common wiring; do not assume individually isolated channels.

Match the complete catalog number, hardware series, installed configuration and required accessories before ordering. Unit condition, package contents, delivery and warranty must be confirmed in the quotation.

1769-OF8C Procurement Questions

What output ranges does the 1769-OF8C support?

The module provides 0…20 mA and 4…20 mA output ranges, with a full scale range of 0…21 mA and 3.2…21 mA. Per the table footnote, the over- or under-range flag comes on when the normal operating range is exceeded, the module continues to convert up to the maximum full scale range, and the flag resets automatically within the normal operating range.

What load can I connect to the current outputs?

Resistive load on current output is 0…500 Ω, which includes wire resistance, and the maximum inductive load on the current outputs is 0.1 mH.

How accurate is the module and how does accuracy change with temperature?

Accuracy is ±0.35% full scale @ 25 °C (77 °F), and per the table footnote this includes offset, gain, nonlinearity, and repeatability error terms. Accuracy drift with temperature is ±0.0058% per °C.

What supply current does the module draw and how much heat does it dissipate?

Current draw is 145 mA @ 5.1V and 140 mA @ 24V, and maximum heat dissipation is 2.69 W.

What isolation does the 1769-OF8C provide?

Isolation voltage is 500V AC or 710V DC for 1 min (qualification test) from output group to bus, with 30V AC/30V DC working voltage (IEC Class 2 reinforced insulation).

What wiring and terminal hardware does the module use?

Wire size is (22…14 AWG) solid and (22…16 AWG) stranded, wire type is Cu-90 °C (194 °F), terminal screw torque is 0.68 N·m (6 lb·in) and retaining screw torque is 0.46 N·m (4.1 lb·in). The replacement terminal block is 1769-RTBN18 (1 per kit).

Outputs
8 single-ended
Output range
0…20 mA 4…20 mA
Full scale range
0…21 mA 3.2…21 mA (footnote (1) of Table 72: The over- or under-range flag will come on when the normal operating range (over/under) is exceeded. The module will continue to convert the analog input up to the maximum full scale range. The flag automatically resets when within the normal operating range.)
Resolution
16 bits (unipolar) 0…20 mA: 15.91 bits, 0.323 PA/bit 4…20 mA: 15.59 bits, 0.323PA/bit
Current draw @ 5.1V
145 mA
Current draw @ 24V
140 mA
Heat dissipation, max
2.69 W
Conversion rate (all channels), max
5 ms (2)
Step response to 63%
< 2.9 ms
Resistive load on current output
0…500 Ω(includes wire resistance)
Inductive load (current outputs), max
0.1 mH
Field calibration
None required
Accuracy
±0.35% full scale @ 25 °C (77 °F) (footnote (3) of Table 72: Includes offset, gain, nonlinearity, and repeatability error terms.)
Accuracy drift with temperature
±0.0058% per °C
Output ripple
±0.05% @ 0…50 kHz (footnote (4) of Table 72: Output ripple is the amount a fixed output varies with time, assuming a constant load and temperature.)
Nonlinearity
±0.05%
Repeatability
±0.05% (footnote (5) of Table 72: Repeatability is the ability of the input module to register the same reading in successive measurements for the same input signal.)
Module error
±0.55%
Offset error
±0.05%
Output impedance
> 1 MΩ
Open and short-circuit protection
Yes
Short-circuit protection, max
21 mA
Output overvoltage protection
Yes
Output response at system powerup and power down
±0.5V DC spike for < 5 ms
Rated working voltage
30V AC/30V DC (footnote (6) of Table 72: Rated working voltage is the maximum continuous voltage that can be applied at the input terminal, including the input signal and the value that floats above ground potential (for example, 10V DC input signal and 20V DC potential above ground).)
Isolation voltage
500V AC or 710V DC for 1 min (qualification test), output group to bus 30V AC/30V DC working voltage (IEC Class 2 reinforced insulation)
Weight, approx (product weight as published)
281 g (0.62 lb)
Dimensions (HxWxD), approx
118 x 35 x 87 mm (4.65 x 1.38 x 3.43 in.) Height with mounting tabs 138 mm (5.43 in.)
Slot width
1
Module location
DIN rail or panel mount
Power supply
1769-PA2, 1769-PB2, 1769-PA4, 1769-PB4 (7)
Optional 24V DC Class 2 power supply voltage range
20.4…26.4V DC
Power supply distance rating
8 modules
Terminal screw torque
0.68 N·m (6 lb·in)
Retaining screw torque
0.46 N·m (4.1 lb·in)
Wire size
(22…14 AWG) solid (22…16 AWG) stranded
Wire type
Cu-90 °C (194 °F)
Replacement terminal block
1769-RTBN18 (1 per kit)
Replacement door label
1769-RL2 (2 per kit)
Replacement door
1769-RD (2 per kit)
Vendor ID code
1
Product type code
10
Product code
40
Input words
11
Output words
9
Configuration words
64
Enclosure type rating
None (open style)

Technical specifications are based on the linked manufacturer references.

Unmatched Customer Service

After Hours Shipping

Real Time Order Tracking

Flexible Delivery Options

Intact Technical Supports

What Does Our Clients Say

Mitsubishi MR-J4

Laura Navas

Great product!

2019/12/01

Keyence sensor

EQDR SALES

Original and fast!

2020/02/22

Need Professional Tech Support or a Quote?

  • Our senior engineers provide 1-on-1 selection & configuration advice
  • 100% genuine products guaranteed with rapid global delivery
UP
WhatsApp