1769-IR6 Procurement Questions
Which RTD sensor types can the 1769-IR6 accept?
The module supports 100, 200, 500, 1000 Ω Platinum 385, 100, 200, 500, 1000 Ω Platinum 3916, 120 Ω Nickel 672, 120 Ω Nickel 618 and 10 Ω Nickel-iron 518 sensors.
What resistance input ranges does the 1769-IR6 cover?
The input range is 0…150 Ω, 0…500 Ω, 0…1000 Ω and 0…3000 Ω.
What accuracy does the 1769-IR6 achieve at 25 °C (77 °F)?
At 25 °C (77 °F), accuracy is ±0.5 °C (0.9 °F) for Pt 385, ±0.4 °C (0.72 °F) for Pt 3916, ±0.3 °C (0.54 °F) for Ni, ±0.3 °C (0.54 °F) for NiFe and ±0.8 °C (1.44 °F) for Cu, plus ±0.15 Ω for the 150 Ω range, ±0.5 Ω for the 500 Ω range, ±1.0 Ω for the 1000 Ω range and ±1.5 Ω for the 3000 Ω range; accuracy is dependent upon the Analog/Digital converter output rate selection, excitation current selection, data format, and input noise.
How does accuracy change over 0…60 °C (32…140 °F)?
Over 0…60 °C (32…140 °F), accuracy is ±0.9 °C (1.62 °F) for Pt 385, ±0.8 °C (1.44 °F) for Pt 3916, ±0.5 °C (0.9 °F) for Ni, ±0.5 °C (0.9 °F) for NiFe and ±1.1 °C (1.98 °F) for Cu, plus ±0.25 Ω for the 150 Ω range, ±0.8 Ω for the 500 Ω range, ±1.5 Ω for the 1000 Ω range and ±2.5 Ω for the 3000 Ω range; accuracy is dependent upon the Analog/Digital converter output rate selection, excitation current selection, data format, and input noise.
What cable and wire sizes are recommended for wiring the 1769-IR6?
Recommended cable is Belden 9501 or equivalent for 2-wire configuration, Belden 9533 or equivalent for 3-wire configuration, and Belden 83503 or equivalent for 4-wire configuration; wire size is 22…14 AWG solid or 22…16 AWG stranded, with Cu-90 °C (194 °F) wire type.
Which power supplies are listed for the 1769-IR6 and what is its power supply distance rating?
The listed power supplies are 1769-PA2, 1769-PB2, 1769-PA4 and 1769-PB4, and the power supply distance rating is 8 modules.
- Inputs
- 6 RTD inputs
- Input range
- 0…150 Ω 0…500 Ω 0…1000: 0…3000 Ω
- Resolution
- Input filter and configuration dependent
- Sensors supported
- 100, 200, 500, 1000 Ω Platinum 385 100, 200, 500, 1000 Ω Platinum 3916 120 Ω Nickel 672 120 Ω Nickel 618 10 Ω Nickel-iron 518
- Current draw @ 5.1V
- 100 mA
- Current draw @ 24V
- 45 mA
- Heat dissipation, max
- 1.5 W
- Converter type
- Sigma Delta
- Common mode voltage range
- ±10V DC max
- Common mode rejection
- 110 dB @ 50 Hz with the 10 or 50 Hz filter selected 110 dB @ 60 Hz with the 10 or 60 Hz filter selected
- Normal mode rejection ratio
- 70 dB @ 50 Hz with the 10 or 50 Hz filter selected 70 dB @ 60 Hz with the 10 or 60 Hz filter selected
- Cable impedance, max
- 25 Ω
- Input impedance
- > 10 MΩ
- Accuracy @ 25 °C (77 °F)
- ±0.5 °C (0.9 °F) for Pt 385; ±0.4 °C (0.72 °F) for Pt 3916 ±0.3 °C (0.54 °F) for Ni ±0.3 °C (0.54 °F) for NiFe ±0.8 °C (1.44 °F) for Cu ±0.15 Ω for 150 Ω range ±0.5 Ω for 500 Ω range ±1.0 Ω for 1000 Ω range ±1.5 Ω for 3000 Ω range (footnote (1) of Table 45: Accuracy is dependent upon the Analog/Digital converter output rate selection, excitation current selection, data format, and input noise.)
- Accuracy @ 0…60 °C (32…140 °F)
- ±0.9 °C (1.62 °F) for Pt 385; ±0.8 °C (1.44 °F) for Pt 3916 ±0.5 °C (0.9 °F) for Ni ±0.5 °C (0.9 °F) for NiFe ±1.1 °C (1.98 °F) for Cu ±0.25 Ω for 150 Ω range ±0.8 Ω for 500 Ωrange ±1.5 Ω for 1000 Ω range ±2.5 Ω for 3000 Ω range (footnote (1) of Table 45: Accuracy is dependent upon the Analog/Digital converter output rate selection, excitation current selection, data format, and input noise.)
- Accuracy drift @ 0…60 °C (32…140 °F)
- ±0.026 °C/°C (0.026 °F/°F) for Pt 385 ±0.023 °C/°C (0.023 °F/°F) for Pt 3916 ±0.012 °C/°C (0.012 °F/°F) for Ni\ ±0.015 °C/°C (0.015 °F/°F) for NiFe ±0.032 °C/°C (0.032 °F/°F) for Cu ±0.007 Ω/°C (±0.013:/°F) for 150 Ω ±0.023 Ω/°C (±0.041:/°F) for 500 Ω ±0.043 Ω/°C (±0.077:/°F) for 1000 Ω ±0.072 Ω/°C (±0.130:/°F) for 3000 Ω (footnote (1) of Table 45: Accuracy is dependent upon the Analog/Digital converter output rate selection, excitation current selection, data format, and input noise.)
- Nonlinearity
- ±0.05%
- Repeatability
- ±0.01 °C (0.018 °F) for Ni and NiFe; ±0.2 °C (0.36 °F) for other RTD inputs ±0.04 Ω for 150 Ω resistances ±0.2 Ω for other resistances (footnote (2) of Table 45: Repeatability is the ability of the input module to register the same reading in successive measurements for the same input signal.)
- Open circuit detection time
- 6 ms…303s (footnote (3) of Table 45: Open-circuit detection time is equal to channel update time.)
- Isolation voltage
- 720V DC for 1 minute, optical and magnetic (qualification), channel to bus 30V AC/30V DC working voltage (IEC Class 2 reinforced insulation)
- Weight, approx (product weight as published)
- 276 g (0.61 lb)
- Dimensions (HxWxD), approx
- 118 x 35 x 87 mm (4.65 x 1.38 x 3.43 in.) Height with mounting tabs 138 mm (5.43 in.)
- Slot width
- 1
- Module location
- DIN rail or panel mount
- Power supply
- 1769-PA2, 1769-PB2, 1769-PA4, 1769-PB4
- Power supply distance rating
- 8 modules
- Terminal screw torque
- 0.68 N·m (6 lb·in)
- Retaining screw torque
- 0.46 N·m (4.1 lb·in)
- Recommended cable
- 2-wire configuration: Belden 9501 or equivalent 3-wire configuration: Belden 9533 or equivalent 4-wire configuration: Belden 83503 or equivalent
- Wire size
- (22…14 AWG) solid (22…16 AWG) stranded
- Wire type
- Cu-90 °C (194 °F)
- IEC input compatibility
- Type 1+
- Replacement terminal block
- 1769-RTBN18 (1 per kit)
- Replacement door label
- 1769-RL2 series B (2 per kit)
- Replacement door
- 1769-RD (2 per kit)
- Vendor ID code
- 1
- Product type code
- 10
- Product code
- 37
- Enclosure type rating
- None (open-style)
- RTD accuracy — Copper 426 10 Ω
- Scaled accuracy max @ 25 °C (77 °F) with calibration: ±0.6 °C (1.08 °F); @ 0…60 °C (32…140 °F) with calibration: ±1.1 °C (1.98 °F); temperature drift max from 25 °C (77 °F) without calibration: ±0.032 °C/°C (0.032 °F/°F)
- RTD accuracy — Nickel 618 120 Ω
- Scaled accuracy max @ 25 °C (77 °F) with calibration: ±0.2 °C (±0.36 °F); @ 0…60 °C (32…140 °F) with calibration: ±0.4 °C (±0.72 °F); temperature drift max from 25 °C (77 °F) without calibration: ±0.012 °C/°C (±0.012 °F/°F)
- RTD accuracy — Nickel 672 120 Ω
- Scaled accuracy max @ 25 °C (77 °F) with calibration: ±0.2 °C (±0.36 °F); @ 0…60 °C (32…140 °F) with calibration: ±0.4°C (±0.72°F); temperature drift max from 25 °C (77 °F) without calibration: ±0.012 °C/°C (±0.012 °F/°F)
- RTD accuracy — Nickel-Iron 518 604 Ω
- Scaled accuracy max @ 25 °C (77 °F) with calibration: ±0.3 °C (±0.54 °F); @ 0…60 °C (32…140 °F) with calibration: ±0.5°C (±0.9°F); temperature drift max from 25 °C (77 °F) without calibration: ±0.015 °C/°C (±0.015 °F/°F)
- RTD accuracy — Platinum 385 100 Ω
- Scaled accuracy max @ 25 °C (77 °F) with calibration: ±0.5 °C (±0.9 °F); @ 0…60 °C (32…140 °F) with calibration: ±0.9 °C (±1.62°F); temperature drift max from 25 °C (77 °F) without calibration: ±0.026 °C/°C (±0.026 °F/°F)
- RTD accuracy — Platinum 385 200 Ω
- Scaled accuracy max @ 25 °C (77 °F) with calibration: ±0.5 °C (±0.9 °F); @ 0…60 °C (32…140 °F) with calibration: ±0.9 °C (±1.62°F); temperature drift max from 25 °C (77 °F) without calibration: ±0.026 °C/°C (±0.026 °F/°F)
- RTD accuracy — Platinum 385 500 Ω
- Scaled accuracy max @ 25 °C (77 °F) with calibration: ±0.5 °C (±0.9 °F); @ 0…60 °C (32…140 °F) with calibration: ±0.9 °C (±1.62°F); temperature drift max from 25 °C (77 °F) without calibration: ±0.026 °C/°C (±0.026 °F/°F)
- RTD accuracy — Platinum 385 1000 Ω
- Scaled accuracy max @ 25 °C (77 °F) with calibration: ±0.5 °C (±0.9 °F); @ 0…60 °C (32…140 °F) with calibration: ±0.9 °C (±1.62°F); temperature drift max from 25 °C (77 °F) without calibration: ±0.026 °C/°C (±0.026 °F/°F)
- RTD accuracy — Platinum 3916 100 Ω
- Scaled accuracy max @ 25 °C (77 °F) with calibration: ±0.4 °C (±0.72 °F); @ 0…60 °C (32…140 °F) with calibration: ±0.8 °C (±1.44°F); temperature drift max from 25 °C (77 °F) without calibration: ±0.023 °C/°C (±0.023 °F/°F)
- RTD accuracy — Platinum 3916 200 Ω
- Scaled accuracy max @ 25 °C (77 °F) with calibration: ±0.4 °C (±0.72 °F); @ 0…60 °C (32…140 °F) with calibration: ±0.8 °C (±1.44°F); temperature drift max from 25 °C (77 °F) without calibration: ±0.023 °C/°C (±0.023 °F/°F)
- RTD accuracy — Platinum 3916 500 Ω
- Scaled accuracy max @ 25 °C (77 °F) with calibration: ±0.4 °C (±0.72 °F); @ 0…60 °C (32…140 °F) with calibration: ±0.8 °C (±1.44°F); temperature drift max from 25 °C (77 °F) without calibration: ±0.023 °C/°C (±0.023 °F/°F)
- RTD accuracy — Platinum 3916 1000 Ω
- Scaled accuracy max @ 25 °C (77 °F) with calibration: ±0.4 °C (±0.72 °F); @ 0…60 °C (32…140 °F) with calibration: ±0.8 °C (±1.44°F); temperature drift max from 25 °C (77 °F) without calibration: ±0.023 °C/°C (±0.023 °F/°F)
Technical specifications are based on the linked manufacturer references.
What Does Our Clients Say
Mitsubishi MR-J4
Laura Navas
Great product!
2019/12/01
Keyence sensor
EQDR SALES
Original and fast!
2020/02/22