1769-HSC Procurement Questions
What encoder inputs does the 1769-HSC provide?
It provides 2 quadrature (ABZ) differential inputs, with an input frequency max of 1 MHz, a minimum pulse width of 250 ns and a minimum phase separation of 131 ns.
What input voltage levels will the module accept?
The input voltage range is 2.6…30V DC; on-state voltage is 2.6V DC min and 30V DC max, while off-state voltage max is 1.0V DC.
How much current do the outputs carry?
On-state output current per point, max is 1 A, 30V DC, 40 °C and 0.5A, 5V DC, 60 °C; per module, max is 4 A,30V DC, 40 °C and 2A, 5V DC, 60 °C.
What is the maximum turn-on time of the outputs?
Turn-on time, max is 400 μs for an output voltage range of 5…7V DC; for output voltages greater than 7V DC, the maximum turn-on time is 200 μs. Turn-off time, max is 200 μs.
What wire and cable does the module call for?
Wire size is 0.32…2.1 mm2 (22…14 AWG) solid copper wire or 0.32…1.3 mm2 (22…16 AWG) stranded copper wire rated at 90 °C (194 °F) insulation max, with wire type Cu-90 °C (194 °F); the recommended cable is individually shielded, twisted-pair cable (or the type recommended by the encoder or sensor manufacturer).
How is the module isolated?
Isolation voltage is 75V (continuous), reinforced insulation type, channel-to-system and channel-to-channel, type tested at 1200V AC for 2 s.
- Bus current draw
- 425 mA, 5V DC 0 mA, 24V DC
- Heat dissipation, max
- 6.21 W, the Watts per point, plus the min Watts, with all points energized
- Isolation voltage
- 75V (continuous), reinforced insulation type, channel-to-system and channel-to-channel Type tested at 1200V AC for 2 s
- Weight, approx (product weight as published)
- 309 g (0.681 lb)
- Dimensions (HxWxD), approx
- 118 x 35 x 87 mm (4.65 x 1.38 x 3.43 in.) Height with mounting tabs 138 mm (5.43 in.)
- Slot width
- 1
- Module location
- DIN rail or panel mount
- Power supply
- 1769-PA2, 1769-PB2, 1769-PA4, 1769-PB4
- Power supply distance rating
- 4 modules
- Terminal screw torque
- 0.68 N·m (6 lb·in)
- Retaining screw torque
- 0.46 N·m (4.1 lb·in)
- Wire size
- 0.32…2.1 mm2 (22…14 AWG) solid copper wire or 0.32…1.3 mm2 (22…16 AWG) stranded copper wire rated at 90 °C (194 °F) insulation max
- Wire type
- Cu-90 °C (194 °F)
- Recommended cable
- Individually shielded, twisted-pair cable (or the type recommended by the encoder or sensor manufacturer)
- Wiring Category
- 2 - on signal ports (footnote (1) of Table 94: Use this Conductor Category information for planning conductor routing. Refer to the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.)
- Vendor ID code
- 1
- Product type code
- 109
- Product code
- 19
- Enclosure type rating
- None (open-style)
- Inputs
- 2 quadrature (ABZ) differential inputs (1)
- Input voltage range
- 2.6…30V DC
- On-state voltage, max
- 30V DC
- On-state voltage, min
- 2.6V DC
- On-state current, min
- 6.8 mA
- Off-state voltage, max
- 1.0V DC
- Off-state current, max
- 1.5 mA
- Off-state leakage current, max
- 1.5 mA
- Input current, max
- 15 mA
- Input current, min
- 6.8 mA
- Input impedance
- 1950:
- Pulse width, min
- 250 ns
- Phase separation, min
- 131 ns
- Input frequency, max
- 1 MHz
- Isolation voltage
- Verified by one of the following dielectric tests: 1200V AC or 1697V DC for 1 s, input to bus and input to input 75V DC working voltage (IEC Class 2 reinforced insulation)
- Outputs
- 16 total, 4 physical and 12 virtual
- Output voltage range
- 5…30V DC
- On-state voltage, max
- User power - 0.1V DC
- On-state output current per point, max
- 1 A, 30V DC, 40 °C 0.5A, 5V DC, 60 °C
- On-state output current per module, max
- 4 A,30V DC, 40 °C 2A, 5V DC, 60 °C
- On-state output current, min
- 1 mA
- On-state voltage drop, max
- 0.5V DC
- Off-state leakage current, max
- 5 μA
- Turn-on time, max
- 400 μs(1) (footnote (1) of Table 96: Maximum turn-on time applies to output voltage range of 5…7V DC. For output voltages greater than 7V DC, the maximum turn-on time is 200 μs.)
- Turn-off time, max
- 200 μs
- Reverse polarity protection
- 30V DC
- Isolation voltage
- Verified by one of the following dielectric tests: 1200V AC or 1697V DC for 1 s, output to bus 75V DC working voltage (IEC Class 2 reinforced insulation)
- Temperature, operating
- 0…60 °C (32…140 °F)
- Temperature, surrounding air, max
- 40 °C (104 °F)
- Temperature, nonoperating
- -40…85 °C (-40…185 °F)
- Relative humidity
- 5…95% noncondensing
- Vibration, operating
- 5 g @ 10…500 Hz, peak-to-peak
- Vibration, relay operation
- 2 g @ 10…500 Hz(1) (footnote (1) of Table 97: This rating applies for your system if a relay module, such as the 1769-OW8, is used.)
- Shock, operating
- 30 g, 11 ms panel mounted; 20 g, 11 ms DIN rail mounted; test standard: IEC 60068-2-27 (Test Ea, Unpackaged Shock)
- Shock, nonoperating
- 40 g, panel mounted; 30 g, DIN rail mounted; test standard: IEC 60068-2-27 (Test Ea, Unpackaged Shock)
- Emissions
- Group 1, Class A
- ESD immunity
- 6 kV contact discharges; 8 kV air discharges; test standard: IEC 61000-4-2
- Radiated RF immunity
- 10V/m with 1 kHz sine-wave 80% AM from; 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM at 900 and 1890 MHz 10V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz; test standard: IEC 61000-4-3
- EFT/B immunity
- ±2 kV at 5 kHz on power ports; ±2 kV at 5 kHz on signal ports; test standard: IEC 61000-4-4
- Surge transient immunity
- ±1 kV line-line (DM) and ±2 kV line-earth (CM); on power ports ±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports ±1 kV line-earth (CM) on shielded ports; test standard: IEC 61000-4-5
- Conducted RF immunity
- 10V rms with 1 kHz sine-wave 80% AM from; 150 kHz…80 MHz; test standard: IEC 61000-4-6
Technical specifications are based on the linked manufacturer references.