1769-OA8 Procurement Questions
What is the operating voltage range of the 1769-OA8?
The voltage category is 100/240V AC, and the operating voltage range is 85…265V AC at 47…63 Hz.
How are the outputs switched, and what output delay applies?
Output delay, on and off, is 1/2 cycle; triac outputs turn on and off at AC line zero cross.
What current can each point and the whole module carry?
Current per point, max is 0.25 A @ 60 °C and 0.5 A @ 30 °C; current per module, max is 2 A @ 60 °C and 4 A @ 30 °C.
What off-state leakage current should I expect, and how can its effects be limited?
Off-state leakage current, max is 2.0 mA @ 132V AC and 2.5 mA @ 265V AC. To limit the effects of leakage current through solid state outputs, a loading resistor can be connected in parallel with your load; for 120V AC operation use a 15 kΩ, 2W resistor, and for 240V AC operation use a 5 kΩ, 5W resistor.
What surge current can the outputs withstand?
Surge current is 10 A for 25 ms, repeatable every 2 s; connecting surge suppressors across your external load will extend the life of the triac outputs.
Which power supplies are listed for this module, and what is the power supply distance rating?
The listed power supplies are 1769-PA2, 1769-PB2, 1769-PA4, 1769-PB4, and the power supply distance rating is 8 modules.
- Outputs
- 8 (4 points/group)
- Voltage category
- 100/240V AC
- Operating voltage range
- 85…265V AC 47…63 Hz
- Output delay, on
- 1/2 cycle (footnote (1) of Table 52: Triac outputs turn on and off at AC line zero cross.)
- Output delay, off
- 1/2 cycle (footnote (1) of Table 52: Triac outputs turn on and off at AC line zero cross.)
- Current draw @ 5.1V
- 145 mA
- Heat dissipation, max
- 2.12 W
- Off-state leakage current, max
- 2.0 mA @ 132V AC 2.5 mA @ 265V AC (footnote (2) of Table 52: To limit the effects of leakage current through solid state outputs, a loading resistor can be connected in parallel with your load. For 120V AC operation, use a 15 kΩ, 2W resistor. For 240V AC operation use a 5 kΩ, 5W resistor.)
- On-state current, max
- 10 mA
- On-state voltage drop, max
- 1.5V peak @ 2 A
- Current per point, max
- 0.25 A @ 60 °C 0.5 A @ 30 °C
- Current per module, max
- 2 A @ 60 °C 4 A @ 30 °C
- Surge current
- 10 A for 25 ms, repeatable every 2 s (footnote (3) of Table 52: Connecting surge suppressors across your external load will extend the life of the triac outputs.)
- Isolation voltage
- Verified by one of the following dielectric tests: 1836V AC for 1 s or 2596V DC for 1 s, group to group 265V AC working voltage (basic insulation) 150V AC working voltage (IEC Class 2 reinforced insulation)
- Weight, approx (product weight as published)
- 280 g (0.61 lb)
- Dimensions (HxWxD), approx
- 118 x 35 x 87 mm (4.65 x 1.38 x 3.43 in.) Height with mounting tabs 138 mm (5.43 in.)
- Slot width
- 1
- Module location
- DIN rail or panel mount
- Power supply
- 1769-PA2, 1769-PB2, 1769-PA4, 1769-PB4
- Power supply distance rating
- 8 modules
- Terminal screw torque
- 0.68 N·m (6 lb·in)
- Retaining screw torque
- 0.46 N·m (4.1 lb·in)
- Wire size
- (22…14 AWG) solid (22…16 AWG) stranded
- Wire type
- Cu-90 °C (194 °F)
- Replacement terminal block
- 1769-RTBN10 (1 per kit)
- Replacement door label
- 1769-RL1 (2 per kit)
- Replacement door
- 1769-RD (2 per kit)
- Vendor ID code
- 1
- Product type code
- 7
- Product code
- 84
- Enclosure type rating
- None (open style)
Technical specifications are based on the linked manufacturer references.