1769-OA16 Procurement Questions
How many outputs does the 1769-OA16 provide and how are they grouped?
It provides 16 outputs, arranged as 8 points/group.
What AC voltage can the 1769-OA16 outputs switch?
The voltage category is 100/240V AC, and the operating voltage range is 85…265V AC 47…63 Hz.
What is the maximum current per point and per module at different temperatures?
Current per point, max is 0.25 A @ 60 °C and 0.5 A @ 30 °C; current per module, max is 2 A @ 60 °C and 4 A @ 30 °C.
How does the module behave at AC line zero cross, and what are the output delays?
Triac outputs turn on and off at AC line zero cross; output delay on is 1/2 cycle and output delay off is 1/2 cycle.
What off-state leakage current should I expect, and how can its effects be limited?
Off-state leakage current, max is 2.0 mA @ 132V AC and 2.5 mA @ 265V AC. To limit the effects of leakage current through solid state outputs, a loading resistor can be connected in parallel with your load: for 120V AC operation, use a 15 kΩ, 2W resistor; for 240V AC operation use a 5 kΩ, 5W resistor.
What wire size and terminal screw torque apply to the 1769-OA16?
Wire size is (22…14 AWG) solid and (22…16 AWG) stranded, with Cu-90 °C (194 °F) wire type; terminal screw torque is 0.68 N·m (6 lb·in) and retaining screw torque is 0.46 N·m (4.1 lb·in).
- Outputs
- 16 (8 points/group)
- Voltage category
- 100/240V AC
- Operating voltage range
- 85…265V AC 47…63 Hz
- Output delay, on
- 1/2 cycle (footnote (1) of Table 53: Triac outputs turn on and off at AC line zero cross.)
- Output delay, off
- 1/2 cycle (footnote (1) of Table 53: Triac outputs turn on and off at AC line zero cross.)
- Current draw @ 5.1V
- 225 mA
- Heat dissipation, max
- 4.9 W
- Off-state leakage current, max
- 2.0 mA @ 132V AC 2.5 mA @ 265V AC (footnote (2) of Table 53: To limit the effects of leakage current through solid state outputs, a loading resistor can be connected in parallel with your load. For 120V AC operation, use a 15 kΩ, 2W resistor. For 240V AC operation use a 5 kΩ, 5W resistor.)
- On-state current, max
- 10 mA
- On-state voltage drop, max
- 1.5V peak @ 2 A
- Current per point, max
- 0.25 A @ 60 °C 0.5 A @ 30 °C
- Current per module, max
- 2 A @ 60 °C 4 A @ 30 °C
- Surge current
- 5 A for 25 ms, repeatable every 2 s (footnote (3) of Table 53: Connecting surge suppressors across your external load will extend the life of the triac outputs.)
- Isolation voltage
- Verified by one of the following dielectric tests: 1836V AC for 1 s or 2596V DC for 1 s, output point to bus 265V AC working voltage (IEC Class 2 reinforced insulation) Verified by one of the following dielectric tests: 1836V AC for 1 s or 2596V DC for 1 s, output point to bus 265V AC working voltage (basic insulation) 150V AC working voltage (IEC Class 2 reinforced insulation)
- Weight, approx (product weight as published)
- 280 g (0.61 lb)
- Dimensions (HxWxD), approx
- 118 x 35 x 87 mm (4.65 x 1.38 x 3.43 in.) Height with mounting tabs 138 mm (5.43 in.)
- Slot width
- 1
- Module location
- DIN rail or panel mount
- Power supply
- 1769-PA2, 1769-PB2, 1769-PA4, 1769-PB4
- Power supply distance rating
- 8 modules
- Terminal screw torque
- 0.68 N·m (6 lb·in)
- Retaining screw torque
- 0.46 N·m (4.1 lb·in)
- Wire size
- (22…14 AWG) solid (22…16 AWG) stranded
- Wire type
- Cu-90 °C (194 °F)
- Replacement terminal block
- 1769-RTBN18 (1 per kit)
- Replacement door label
- 1769-RL1 (2 per kit)
- Replacement door
- 1769-RD (2 per kit)
- Vendor ID code
- 1
- Product type code
- 7
- Product code
- 93
- Enclosure type rating
- None (open style)
Technical specifications are based on the linked manufacturer references.