Allen-Bradley 1756-L71 — Controller.
| Specification | Details |
|---|---|
| Manufacturer | Allen-Bradley |
| Catalog number | 1756-L71 |
| Controller family | ControlLogix 5570 |
| Built-in programming port | 1 USB |
Check USB programming access separately from chassis network modules.
Match the complete catalog number, hardware series, installed configuration and required accessories before ordering. Unit condition, package contents, delivery and warranty must be confirmed in the quotation.
The count depends on the software version: 32 programs/tasks prior to RSLogix 5000 programming software, version 15.01.00; 100 programs/task beginning with RSLogix 5000 programming software, version 15.01.00; and 1000 programs/task beginning with Logix Designer application, version 24.00.00. The controller also supports 32 tasks, including a combination of continuous (1), periodic, and event tasks.
No. The built-in port is a 1-port USB (USB 2.0, full speed (12 Mbps)), and the USB port is intended for temporary local programming purposes only and not intended for permanent connection. It must not be used in hazardous locations.
The maximum number of controller connections supported is 500.
Controller redundancy is listed as Full support; this does not mean redundancy operates without its supporting modules and configuration.
Integrated motion options are SERCOS interface, analog options (encoder input, LDT input, SSI input), and Integrated Motion on the EtherNet/IP network. Programming languages are relay ladder logic, structured text, Function Block Diagram, and Sequential function chart (SFC).
Digital I/O max is 128,000, analog I/O max is 4000, and total I/O max is 128,000.
Technical specifications are based on the linked manufacturer references.
What Does Our Clients Say
Mitsubishi MR-J4
Laura Navas
Great product!
2019/12/01