Allen-Bradley 1756-L63 — Controller.

Technical Specifications

SpecificationDetails
ManufacturerAllen-Bradley
Catalog number1756-L63
Controller familyControlLogix 5560
Built-in programming port1 RS-232

Ordering & Compatibility

Distinguish the built-in serial port from optional network modules.

Match the complete catalog number, hardware series, installed configuration and required accessories before ordering. Unit condition, package contents, delivery and warranty must be confirmed in the quotation.

1756-L63 Procurement Questions

How much user memory does the 1756-L63 provide, and how much I/O memory is available?

The 1756-L63 provides 8 MB of user memory and 478 KB of I/O memory.

What task structure does this controller support?

It supports 32 tasks, including a combination of continuous (1), periodic, and event tasks, with 100 programs/task.

What communication ports are built into the controller, and what serial protocols can the serial port use?

The controller has 1 port RS-232 serial. Serial port communication supports DF1 radio modem, DH-485, and Modbus via logic.

Which communication options are listed for this controller?

Listed communication options are EtherNet/IP; ControlNet; DeviceNet; Data Highway Plus; Remote I/O; SERCOS; Third-party process and device networks; ASCII; DF1 full/half-duplex.

What is the maximum number of controller connections supported, and is controller redundancy supported?

Controller connections supported max is 250, and controller redundancy is listed as full support.

What are the current draw and power dissipation figures for this controller?

Current draw is 1200 mA at 5.1V DC and 14 mA at 24V DC; power dissipation is 3.5 W.

Controller tasks
32 tasks, including a combination of continuous (1), periodic, and event tasks; 100 programs/task
Built-in communication ports
1 port RS-232 serial
Communication options
EtherNet/IP; ControlNet; DeviceNet; Data Highway Plus; Remote I/O; SERCOS; Third-party process and device networks; ASCII; DF1 full/half-duplex
Serial port communication
DF1 radio modem; DH-485; Modbus via logic
Controller connections supported max
250
Controller redundancy
Full support
Integrated motion
SERCOS interface; Analog options (encoder input, LDT input, SSI input); Integrated Motion on the EtherNet/IP network
Programming languages
Relay ladder logic; Structured text; Function Block Diagram; Sequential function chart (SFC)
User memory
8 MB
I/O memory
478 KB
Optional nonvolatile memory storage
128 MB (1784-CF128)
Digital I/O max
128,000
Analog I/O max
4000
Total I/O max
128,000
Current draw @ 5.1V DC
1200 mA
Current draw @ 24V DC
14 mA
Power dissipation
3.5 W
Thermal dissipation
11.9 BTU/hr
Isolation voltage
30V (continuous), basic insulation type, RS-232 port to system; Compliant and tested according to IEC/UL 61010-1
Weight, approx (product weight as published)
Series A: 0.32 kg (0.71 lb); Series B: 0.35 kg (0.78 lb)
Slot width
1
Module location
Chassis-based, any slot
Wire category
2 - on RS-232 port
North American temperature code
T4A
IEC temperature code
T4
Enclosure type rating
None (open-style)

Technical specifications are based on the linked manufacturer references.

Unmatched Customer Service

After Hours Shipping

Real Time Order Tracking

Flexible Delivery Options

Intact Technical Supports

What Does Our Clients Say

Mitsubishi MR-J4

Laura Navas

Great product!

2019/12/01

Keyence sensor

EQDR SALES

Original and fast!

2020/02/22

Need Professional Tech Support or a Quote?

  • Our senior engineers provide 1-on-1 selection & configuration advice
  • 100% genuine products guaranteed with rapid global delivery
UP
WhatsApp