Allen-Bradley 1756-L72S — GuardLogix primary controller.
| Specification | Details |
|---|---|
| Manufacturer | Allen-Bradley |
| Catalog number | 1756-L72S |
| Role | GuardLogix primary controller |
| Safety partner | 1756-L7SP |
| Safety tasks | 1 |
Do not confuse standard tasks with the single safety task.
Match the complete catalog number, hardware series, installed configuration and required accessories before ordering. Unit condition, package contents, delivery and warranty must be confirmed in the quotation.
The 1756-L72S provides 4 MB of user memory and 2 MB of safety memory.
Digital I/O max is 128,000, analog I/O max is 4000, and total I/O max is 128,000.
The controller is chassis-based and can go in any slot, but the safety partner must be installed in the slot to the immediate right of the primary controller.
Current draw is 5 mA @ 1.2V DC and 800 mA @ 5.1V DC, with power dissipation of 2.5 W and thermal dissipation of 8.5 BTU/hr.
Isolation voltage is 30V (continuous), basic insulation, USB port-to-system, compliant and tested according to IEC/UL 61010-1; the enclosure type rating is None (open-style).
Optional nonvolatile memory storage is 1 GB, and the 1756-SD1 ships with every controller.
Technical specifications are based on the linked manufacturer references.