Allen-Bradley 1756-IA16I ControlLogix digital input module

Series#: AllenBradley

Product Details

  • Allen-Bradley 1756-IA16I ControlLogix digital input module
  • Device type: ControlLogix digital input module; Inputs: 16 individually isolated inputs
  • Voltage category / operating range: 120 V AC category; 79–132 V AC, 47–63 Hz

Specification

Allen-Bradley 1756-IA16I — ControlLogix digital input module.

Technical Specifications

SpecificationDetails
ManufacturerAllen-Bradley
Catalog number1756-IA16I
Device typeControlLogix digital input module
Inputs16 individually isolated inputs
Voltage category / operating range120 V AC category; 79–132 V AC, 47–63 Hz

Ordering & Compatibility

Match the exact voltage category, input wiring and isolation grouping before ordering.

Match the complete catalog number, hardware series, installed configuration and required accessories before ordering. Unit condition, package contents, delivery and warranty must be confirmed in the quotation.

1756-IA16I Procurement Questions

How many inputs does the 1756-IA16I provide, and are they isolated from each other?

The module provides 16 individually isolated inputs.

What AC voltage and frequency range can this module accept?

The voltage category is 120V AC 50/60 Hz, and the operating voltage range is 79…132V AC, 47…63 Hz.

What input delay times apply from screw to backplane?

Off to On: hardware delay 10 ms max plus filter time, with user-selectable filter time of 1 ms or 2 ms. On to Off: hardware delay 8 ms max plus filter time, with user-selectable filter time of 9 ms or 18 ms.

What are the on-state and off-state current limits?

On-state current is 5 mA min @ 79V AC, 47…63 Hz and 15 mA max @ 132V AC, 47…63 Hz; off-state current is 2.5 mA max.

What isolation does the module provide?

Isolation voltage is 125V (continuous), basic insulation type, inputs-to-backplane, and input-to-input.

What backplane current and power does the module require?

Current draw is 125 mA @ 5.1V and 3 mA @ 24V, with total backplane power of 0.71 W.

Inputs
16 individually isolated
Voltage category
120V AC 50/60 Hz
Operating voltage range
79…132V AC, 47…63 Hz
Input voltage, nom
120V AC 50/60 Hz
Input delay time (screw to backplane) — Off to On
Hardware delay: 10 ms max + filter time User-selectable filter time: 1 ms or 2 ms
Input delay time (screw to backplane) — On to Off
Hardware delay: 8 ms max + filter time User-selectable filter time: 9 ms or 18 ms
Current draw @ 5.1V
125 mA
Current draw @ 24V
3 mA
Total backplane power
0.71 W
Power dissipation, max
4.9 W @ 60 °C (140 °F)
Thermal dissipation
16.71 BTU/hr
Off-state voltage, max
20V
Off-state current, max
2.5 mA
On-state current, min
5 mA @ 79V AC, 47…63 Hz
On-state current, max
15 mA @ 132V AC, 47…63 Hz
Inrush current, max
250 mA
Input impedance, max
8.8 kΩ @ 132V AC, 60 Hz
Cyclic update time
200 µs…750 ms
Change of state
Software configurable
Time stamp of inputs
±200 µs
Isolation voltage
125V (continuous), basic insulation type, inputs-to-backplane, and input-to-input
Module keying
Electronic, software configurable
RTB keying
User-defined mechanical
Slot width
1
Wire category
1 - on signal ports
Enclosure type
None (open-style)
North American temperature code
T4A

Technical specifications are based on the linked manufacturer references.

Unmatched Customer Service

After Hours Shipping

Real Time Order Tracking

Flexible Delivery Options

Intact Technical Supports

What Does Our Clients Say

Mitsubishi MR-J4

Laura Navas

Great product!

2019/12/01

Keyence sensor

EQDR SALES

Original and fast!

2020/02/22

Need Professional Tech Support or a Quote?

  • Our senior engineers provide 1-on-1 selection & configuration advice
  • 100% genuine products guaranteed with rapid global delivery
UP
WhatsApp