Allen-Bradley 1756-IA32 ControlLogix digital input module

Series#: AllenBradley

Product Details

  • Allen-Bradley 1756-IA32 ControlLogix digital input module
  • Device type: ControlLogix digital input module; Inputs: 32 inputs, 16 points per group
  • Voltage category / operating range: 120 V AC category; 74–132 V AC, 47–63 Hz

Specification

Allen-Bradley 1756-IA32 — ControlLogix digital input module.

Technical Specifications

SpecificationDetails
ManufacturerAllen-Bradley
Catalog number1756-IA32
Device typeControlLogix digital input module
Inputs32 inputs, 16 points per group
Voltage category / operating range120 V AC category; 74–132 V AC, 47–63 Hz

Ordering & Compatibility

Match the exact voltage category, input wiring and isolation grouping before ordering.

Match the complete catalog number, hardware series, installed configuration and required accessories before ordering. Unit condition, package contents, delivery and warranty must be confirmed in the quotation.

1756-IA32 Procurement Questions

How many inputs does the 1756-IA32 provide, and how are they grouped?

The module provides 32 inputs, arranged as 16 points/group.

What AC voltage range can the 1756-IA32 operate on?

The voltage category is 120V AC 50/60 Hz, and the operating voltage range is 74…132V AC, 47…63 Hz.

What input delay times apply from screw to backplane?

Off to On uses a hardware delay of 1.5 ms nom/10 ms max plus filter time, with user-selectable filter time of 1 ms or 2 ms. On to Off uses a hardware delay of 1 ms nom/8 ms max plus filter time, with user-selectable filter time of 9 ms or 18 ms.

What are the on-state and off-state current limits?

On-state current, min is 5 mA @ 74V AC and on-state current, max is 15 mA @ 132V AC. Off-state current, max is 2.5 mA.

What isolation is provided between inputs and the backplane, and between input groups?

Isolation voltage is 250V (continuous), basic insulation type, inputs-to-backplane, and 125V (continuous), basic insulation type, input group-to-group. There is no isolation between individual group inputs.

What backplane current and power does the module draw?

Current draw is 165 mA @ 5.1V and 2 mA @ 24V, with total backplane power of 0.9 W.

Inputs
32 (16 points/group)
Voltage category
120V AC 50/60 Hz
Operating voltage range
74…132V AC, 47…63 Hz
Input voltage, nom
120V AC 50/60 Hz
Input delay time (screw to backplane) — Off to On
Hardware delay: 1.5 ms nom/10 ms max + filter time User-selectable filter time: 1 ms or 2 ms
Input delay time (screw to backplane) — On to Off
Hardware delay: 1 ms nom/8 ms max + filter time User-selectable filter time: 9 ms or 18 ms
Current draw @ 5.1V
165 mA
Current draw @ 24V
2 mA
Total backplane power
0.9 W
Power dissipation, max
6.1 W @ 60 °C (140 °F)
Thermal dissipation
20.8 BTU/hr
Off-state voltage, max
20V
Off-state current, max
2.5 mA
On-state current, min
5 mA @ 74V AC
On-state current, max
15 mA @ 132V AC
Inrush current, max
390 mA
Input impedance, max
14.0 kΩ @ 132V AC, 60 Hz
Cyclic update time
200 µs…750 ms
Change of stat
Software configurable
Time stamp of inputs
±200 µs
Isolation voltage
250V (continuous), basic insulation type, inputs-to-backplane 125V (continuous), basic insulation type, input group-to-group No isolation between individual group inputs
Module keying
Electronic, software configurable
RTB keying
User-defined mechanical
Slot width
1
Wire category
1 - on signal ports
Enclosure type
None (open-style)
North American temperature code
T4

Technical specifications are based on the linked manufacturer references.

Unmatched Customer Service

After Hours Shipping

Real Time Order Tracking

Flexible Delivery Options

Intact Technical Supports

What Does Our Clients Say