1756-OA8D Procurement Questions
How are the 1756-OA8D outputs grouped and fused?
The module has 8 diagnostic outputs with electronic fusing, arranged as 4 points per group. Fusing is electronic per point.
What AC supply does the 1756-OA8D operate on?
The voltage category is 120V AC 50/60 Hz, and the operating voltage range is 74…132V AC, 47…63 Hz.
What is the maximum current per point and per module, and how does temperature affect it?
Current per point, max is 1 A @ 30 °C (86 °F) linear derating and 0.5 A @ 60 °C (140 °F) linear derating. Current per module, max is 8 A @ 30 °C (86 °F) linear derating and 4 A @ 60 °C (140 °F) linear derating.
What is the minimum load current the module supports?
Load current, min is 10 mA per point.
What output states can be configured in Fault and Program modes?
States in Fault mode per point and States in Program mode per point are both Hold last state, On or Off (Off is default).
What isolation does the module provide?
Isolation voltage is 125V (continuous), basic insulation type, outputs-to-backplane, and output group-to-group, with no isolation between individual group outputs.
- Outputs
- 8 diagnostic, electronic fusing (4 points/group)
- Voltage category
- 120V AC 50/60 Hz
- Operating voltage range
- 74…132V AC, 47…63 Hz
- Output delay time — Off to On
- 11 ms @ 50 Hz; 9.3 ms @ 60 Hz
- Output delay time — On to Off
- 11 ms @ 50 Hz; 9.3 ms @ 60 Hz
- Current draw @ 5.1V
- 175 mA
- Current draw @ 24V
- 250 mA
- Total backplane power
- 6.89 W
- Power dissipation, max
- 5.3 W @ 60 °C (140 °F)
- Thermal dissipation
- 18.0 BTU/hr
- Off-state leakage current, max
- 3 mA per point
- On-state voltage drop, max
- 2.5V peak @ 0.5 A; 3V peak @ 1 A
- Current per point, max
- 1 A @ 30 °C (86 °F) linear derating; 0.5 A @ 60 °C (140 °F) linear derating
- Current per module, max
- 8 A @ 30 °C (86 °F) linear derating; 4 A @ 60 °C (140 °F) linear derating
- Surge current per point
- 8 A for 43 ms per point, repeatable every 2 s @ 30 °C (86 °F); 5 A for 43 ms per point, repeatable every 1 s @ 60 °C (140 °F)
- Load current, min
- 10 mA per point
- Scheduled outputs
- Synchronization within 16.7 s max, reference to the Coordinated System Time
- States in Fault mode per point
- Hold last state, On or Off (Off is default)
- States in Program mode per point
- Hold last state, On or Off (Off is default)
- Isolation voltage
- 125V (continuous), basic insulation type, outputs-to-backplane, and output group-to-group No isolation between individual group outputs
- Inhibit voltage, max
- Zero crossing 25V peak
- Module keying
- Electronic, software configurable
- Fusing
- Electronically fused per point
- RTB keying
- User-defined mechanical
- Slot width
- 1
- Wire size
- 1756-TBNH Single wire connection: 0.33…2.1 mm2 (22…14 AWG) solid or stranded shielded copper wire rated at 105 °C (221 °F), or greater, 1.2 mm (3/64 in.) insulation max. Double wire connection: 0.33…1.3 mm2 (22…16 AWG) solid or stranded copper wire rated at 105 °C (221 °F), or greater, 1.2 mm (3/64 in.) insulation max. 1756-TBSH Single wire connection: 0.33…2.1 mm2 (22…14 AWG) solid or stranded shielded copper wire rated at 105 °C (221 °F), or greater, 1.2 mm (3/64 in.) insulation max.
- Wire category
- 1 - on signal ports
- Enclosure type
- None (open style)
- North American temperature code
- T4A
Technical specifications are based on the linked manufacturer references.