1756-OA16 Procurement Questions
What load current range does the 1756-OA16 support per point?
The minimum load current is 10 mA per point, and the maximum current per point is 0.5 A @ 60 °C (140 °F).
What commutating voltage limits apply to the 1756-OA16 outputs?
Per footnote (2), the commutating dv/dt of the output voltage (OUTPUT to L2) should not exceed 0.2V/µs for loads under 50 mA; the 4V/µs maximum rating applies to the higher load segment defined in footnote (2) (OUTPUT to L2).
How are the outputs fused and grouped?
The module has 16 mechanically fused outputs at 8 points per group, with one fuse and indicator per group. Fusing is mechanically fused/group, 3.15 A @ 250V AC slow blow, 1500 A interruption current, Littelfuse p/n H2153.15.
What surge current can a point and a group withstand?
Surge current per point is 5 A for 43 ms per point, repeatable every 2 s @ 60 °C (140 °F); surge current per group is 15 A for 43 ms per group, repeatable every 2 s @ 60 °C (140 °F).
What output states can be configured in Fault and Program modes?
Per point, both Fault mode and Program mode can be set to Hold last state, On or Off, with Off as the default.
Which removable terminal blocks and wire sizes are specified?
The removable terminal block options are 1756-TBNH and 1756-TBSH. For 1756-TBNH, single wire connection is 0.33…2.1 mm2 (22…14 AWG) and double wire connection is 0.33…1.3 mm2 (22…16 AWG); for 1756-TBSH, single wire connection is 0.33…2.1 mm2 (22…14 AWG), all with 1.2 mm (3/64 in.) insulation max.
- Time stamp of diagnostics
- ±1 ms
- Fuse blown
- One fuse and indicator/group
- Outputs
- 16 mechanically fused/group (8 points/group)
- Pilot duty
- 0.5 A
- Voltage category
- 120/240V AC 50/60 Hz
- Operating voltage range
- 74…265V AC, 47…63 Hz
- Output delay time — Off to On
- 11 ms @ 50 Hz; 9.3 ms @ 60 Hz
- Output delay time — On to Off
- 11 ms @ 50 Hz; 9.3 ms @ 60 Hz
- Current draw @ 5.1V
- 400 mA
- Current draw @ 24V
- 2 mA
- Total backplane power
- 2.1 W
- Power dissipation, max
- 6.5 W @ 60 °C (140 °F)
- Thermal dissipation
- 22.17 BTU/hr
- Off-state leakage current, max
- 3 mA per point
- On-state voltage drop, max
- 1.5V @ 0.5 A; 5.7V @ load current < 50 mA
- Current per point, max
- 0.5 A @ 60 °C (140 °F)
- Current per group, max
- 2 A @ 60 °C (140 °F)
- Current per module, max
- 4 A @ 60 °C (140 °F)
- Surge current per point
- 5 A for 43 ms per point, repeatable every 2 s @ 60 °C (140 °F)
- Surge current per group
- 15 A for 43 ms per group, repeatable every 2 s @ 60 °C (140 °F)
- Load current, min
- 10 mA per point
- Commutating voltage
- 4V/µs for loads > 50 mA; 0.2V/µs for loads < 50 mA(2)
- Scheduled outputs
- Synchronization within 16.7 s max, reference to the Coordinated System Time
- States in Fault mode per point
- Hold last state, On or Off (Off is default)
- States in Program mode per point
- Hold last state, On or Off (Off is default)
- Isolation voltage
- 250V (continuous), basic insulation type, outputs to backplane, and group to group
- Inhibit voltage, max
- Zero crossing 60V peak
- Module keying
- Electronic, software configurable
- Fusing
- Mechanically fused/group, 3.15 A @ 250V AC slow blow, 1500 A interruption current, Littelfuse p/n H2153.15
- RTB keying
- User-defined mechanical
- Slot width
- 1
- Wire size
- 1756-TBNH Single wire connection: 0.33…2.1 mm2 (22…14 AWG) solid or stranded shielded copper wire rated at 105 °C (221 °F), or greater, 1.2 mm (3/64 in.) insulation max. Double wire connection: 0.33…1.3 mm2 (22…16 AWG) solid or stranded copper wire rated at 105 °C (221 °F), or greater, 1.2 mm (3/64 in.) insulation max. 1756-TBSH Single wire connection: 0.33…2.1 mm2 (22…14 AWG) solid or stranded shielded copper wire rated at 105 °C (221 °F), or greater, 1.2 mm (3/64 in.) insulation max.
- Wire category
- 1 - on signal ports
- Enclosure type
- None (open style)
- North American temperature code
- T4
Technical specifications are based on the linked manufacturer references.