1756-ON8 Procurement Questions
What is the maximum current per point and per module, and how does temperature affect it?
Current per point, max is 2 A @ 60 °C (140 °F) and 5 A @ 30 °C (86 °F) linear derating. Current per module, max is 5 A @ 30 °C (86 °F) linear derating and 4 A @ 60 °C (140 °F) linear derating.
What commutating voltage limits apply to the 1756-ON8 outputs?
Per footnote (2), the commutating dv/dt of the output voltage (OUTPUT to L2) should not exceed 0.2V/µs for loads under 50 mA; the 4V/µs maximum rating applies to the higher load segment defined in footnote (2) (OUTPUT to L2).
What are the minimum load current and the off-state leakage current?
Load current, min is 10 mA per point, and off-state leakage current, max is 3 mA per point.
What output states can be configured in Fault mode and Program mode?
For each point, both Fault mode and Program mode support Hold last state, On or Off, with Off as the default.
What isolation does the module provide between outputs and the backplane?
Isolation voltage is 250V (continuous), basic insulation type, outputs-to-backplane, and output group-to-group. There is no isolation between individual group outputs.
What wire size and terminal block options are supported?
With the 1756-TBNH, single wire connection accepts 0.33…2.1 mm2 (22…14 AWG) and double wire connection accepts 0.33…1.3 mm2 (22…16 AWG). With the 1756-TBSH, single wire connection accepts 0.33…2.1 mm2 (22…14 AWG).
- Outputs
- 8 (4 points/group)
- Voltage category
- 24V AC 50/60 Hz
- Operating voltage range
- 10…30V AC, current >50 mA, 47…63Hz; 16…30V AC, current <50 mA, 47…63Hz
- Output delay time — Off to On
- 11 ms @ 50 Hz; 9.3 ms @ 60 Hz
- Output delay time — On to Off
- 11 ms @ 50 Hz; 9.3 ms @ 60 Hz
- Voltage and current ratings
- Backplane: 5.1V DC, 200 mA; 24V DC, 2 mA; Output: 10…30V AC, 50/60Hz, 2 A Pilot Duty (DC-13/SQ); MDL: 5A/4A 30°C/60°C
- Current draw @ 5.1V
- 200 mA
- Current draw @ 24V
- 2 mA
- Total backplane power
- 1.07 W
- Power dissipation, max
- 5.1 W @ 60 °C (140 °F)
- Thermal dissipation
- 17.39 BTU/hr
- Off-state leakage current, max
- 3 mA per point
- On-state voltage drop, max
- 1.5V peak @ 2 A; 6V peak @ load current < 50 mA
- Current per point, max
- 2 A @ 60 °C (140 °F) 5 A @ 30 °C (86 °F) linear derating
- Current per module, max
- 5 A @ 30 °C (86 °F) linear derating; 4 A @ 60 °C (140 °F) linear derating
- Surge current per point
- 20 A for 43 ms per point, repeatable every 2 s @ 60 °C (140 °F)
- Load current, min
- 10 mA per point
- Commutating voltage
- 4V/µs for loads > 50 mA; 0.2V/µs for loads < 50 mA(2)
- Scheduled outputs
- Synchronization within 16.7 s max, reference to the Coordinated System Time
- States in Fault mode per point
- Hold last state, On or Off (Off is default)
- States in Program mode per point
- Hold last state, On or Off (Off is default)
- Isolation voltage
- 250V (continuous), basic insulation type, outputs-to-backplane, and output group-to-group No isolation between individual group outputs
- Module keying
- Electronic, software configurable
- Fusing
- Not protected. A fused IFM is recommended to help protect outputs.
- RTB keying
- User-defined mechanical
- Slot width
- 1
- Wire size
- 1756-TBNH Single wire connection: 0.33…2.1 mm2 (22…14 AWG) solid or stranded shielded copper wire rated at 105 °C (221 °F), or greater, 1.2 mm (3/64 in.) insulation max. Double wire connection: 0.33…1.3 mm2 (22…16 AWG) solid or stranded copper wire rated at 105 °C (221 °F), or greater, 1.2 mm (3/64 in.) insulation max. 1756-TBSH Single wire connection: 0.33…2.1 mm2 (22…14 AWG) solid or stranded shielded copper wire rated at 105 °C (221 °F), or greater, 1.2 mm (3/64 in.) insulation max.
- Wire category
- 1 - on signal ports
- Enclosure type
- None (open style)
- Temperature code
- T4