Allen-Bradley 1756-IB16D ControlLogix digital input module

Series#: AllenBradley

Product Details

  • Allen-Bradley 1756-IB16D ControlLogix digital input module
  • Device type: ControlLogix digital input module; Inputs: 16 diagnostic inputs, 4 points per group
  • Voltage category / operating range: 12/24 V DC sinking; 10–30 V DC

Specification

Allen-Bradley 1756-IB16D — ControlLogix digital input module.

Technical Specifications

SpecificationDetails
ManufacturerAllen-Bradley
Catalog number1756-IB16D
Device typeControlLogix digital input module
Inputs16 diagnostic inputs, 4 points per group
Voltage category / operating range12/24 V DC sinking; 10–30 V DC

Ordering & Compatibility

Match the exact voltage category, input wiring and isolation grouping before ordering.

Match the complete catalog number, hardware series, installed configuration and required accessories before ordering. Unit condition, package contents, delivery and warranty must be confirmed in the quotation.

1756-IB16D Procurement Questions

What input configuration does the 1756-IB16D provide?

The module provides 16 diagnostic inputs, arranged as 4 points/group.

What voltage range can the inputs operate over?

The voltage category is 12/24V DC sink, the operating voltage range is 10…30V DC, and the nominal input voltage is 24V DC.

How is the input filter time configured for Off to On transitions?

Off to On delay is a hardware delay of 340 µs nom/1 ms max plus filter time, with a user-selectable filter time of 0 ms, 1 ms, or 2 ms.

How is the input filter time configured for On to Off transitions?

On to Off delay is a hardware delay of 740 µs nom/4 ms max plus filter time, with a user-selectable filter time of 0 ms, 1 ms, 9 ms, or 18 ms.

What diagnostic capabilities does this module offer?

Open wire diagnostics use an off-state leakage current of 1.2 mA min, the time stamp of diagnostics is ±1 ms, and the time stamp of inputs is ±200 µs.

What isolation does the module provide between inputs and the backplane?

Isolation voltage is 250V (continuous), basic insulation type, inputs-to-backplane, and input group-to-group, with no isolation between individual group inputs.

Open wire
Off-state leakage current 1.2 mA min
Time stamp of diagnostics
±1 ms
Inputs
16 diagnostic (4 points/group)
Voltage category
12/24V DC sink
Operating voltage range
10…30V DC
Input voltage, nom
24V DC
Input delay time (screw to backplane) — Off to On
Hardware delay: 340 µs nom/1 ms max + filter time User-selectable filter time: 0 ms, 1 ms, or 2 ms
Input delay time (screw to backplane) — On to Off
Hardware delay: 740 µs nom/4 ms max + filter time User-selectable filter time: 0 ms, 1 ms, 9 ms, or 18 ms
Current draw @ 5.1V
150 mA
Current draw @ 24V
3 mA
Total backplane power
0.84 W
Power dissipation, max
5.8 W @ 60 °C (140 °F)
Thermal dissipation
19.78 BTU/hr
Off-state voltage, max
5V
Off-state current, max
1.5 mA
On-state current, min
2 mA @ 10V DC
On-state current, max
13 mA @ 30V DC
Inrush current, max
250 mA
Input impedance, max
2.31 kΩ @ 30V DC
Cyclic update time
200 µs…750 ms
Change of state
Software configurable
Time stamp of inputs
±200 µs
Isolation voltage
250V (continuous), basic insulation type, inputs-to-backplane, and input group-to-group No isolation between individual group inputs
Module keying
Electronic, software configurable
RTB keying
User-defined mechanical
Slot width
1
Wire category
1(1)
Enclosure type
None (open-style)
Temperature code
T3
Reverse polarity protection
Yes

Technical specifications are based on the linked manufacturer references.

Unmatched Customer Service

After Hours Shipping

Real Time Order Tracking

Flexible Delivery Options

Intact Technical Supports

What Does Our Clients Say

Mitsubishi MR-J4

Laura Navas

Great product!

2019/12/01

Keyence sensor

EQDR SALES

Original and fast!

2020/02/22

Need Professional Tech Support or a Quote?

  • Our senior engineers provide 1-on-1 selection & configuration advice
  • 100% genuine products guaranteed with rapid global delivery
UP
WhatsApp