Allen-Bradley 1756-IV16 ControlLogix digital input module

Series#: AllenBradley

Product Details

  • Allen-Bradley 1756-IV16 ControlLogix digital input module
  • Device type: ControlLogix digital input module; Inputs: 16 inputs, 8 points per group
  • Voltage category / operating range: 12/24 V DC sourcing; 10–30 V DC

Specification

Allen-Bradley 1756-IV16 — ControlLogix digital input module.

Technical Specifications

SpecificationDetails
ManufacturerAllen-Bradley
Catalog number1756-IV16
Device typeControlLogix digital input module
Inputs16 inputs, 8 points per group
Voltage category / operating range12/24 V DC sourcing; 10–30 V DC

Ordering & Compatibility

Match the exact voltage category, input wiring and isolation grouping before ordering.

Match the complete catalog number, hardware series, installed configuration and required accessories before ordering. Unit condition, package contents, delivery and warranty must be confirmed in the quotation.

1756-IV16 Procurement Questions

How are the 16 inputs grouped on the 1756-IV16?

The module has 16 inputs arranged as 8 points per group.

What input voltage range does the 1756-IV16 accept?

It is a 12/24V DC source module with a 10…30V DC operating voltage range and 24V DC nominal input voltage.

What filter times can be selected for the input delay?

For Off to On, the hardware delay is 280 µs nom/1 ms max plus filter time, with user-selectable filter time of 0 ms, 1 ms, or 2 ms. For On to Off, the hardware delay is 540 µs nom/2 ms max plus filter time, with user-selectable filter time of 0 ms, 1 ms, 2 ms, 9 ms, or 18 ms.

What are the on-state and off-state current limits?

Off-state current is 1.5 mA max, on-state current is 2 mA min at 10V DC and 10 mA max at 30V DC, and inrush current is 250 mA max.

What isolation does the 1756-IV16 provide?

Isolation voltage is 250V (continuous), basic insulation type, inputs-to-backplane and input group-to-group, with no isolation between individual group inputs.

How much backplane current and power does the module draw?

Current draw is 110 mA at 5.1V and 2 mA at 24V, with 0.61 W total backplane power.

Inputs
16 (8 points/group)
Voltage category
12/24V DC source
Operating voltage range
10…30V DC
Input voltage, nom
24V DC
Input delay time (screw to backplane) — Off to On
Hardware delay: 280 µs nom/1 ms max + filter time User-selectable filter time: 0 ms, 1 ms, or 2 ms
Input delay time (screw to backplane) — On to Off
Hardware delay: 540 µs nom/2 ms max + filter time User-selectable filter time: 0 ms, 1 ms, 2 ms, 9 ms, or 18 ms
Current draw @ 5.1V
110 mA
Current draw @ 24V
2 mA
Total backplane power
0.61 W
Power dissipation, max
5.41 W @ 60 °C (140 °F)
Thermal dissipation
18.47 BTU/hr
Off-state voltage, max
5V DC
Off-state current, max
1.5 mA
On-state current, min
2 mA @ 10V DC
On-state current, max
10 mA @ 30V DC
Inrush current, max
250 mA
Input impedance, max
3.2 kΩ @ 30V DC
Cyclic update time
200 µs…750 ms
Change of state
Software configurable
Time stamp of inputs
±200 µs
Isolation voltage
250V (continuous), basic insulation type, inputs-to-backplane, and input group-to-group No isolation between individual group inputs
Module keying
Electronic, software configurable
RTB keying
User-defined mechanical
Slot width
1
Wire category
1(1)
Enclosure type
None (open-style)
Temperature code
T4
Reverse polarity protection
Yes

Technical specifications are based on the linked manufacturer references.

Unmatched Customer Service

After Hours Shipping

Real Time Order Tracking

Flexible Delivery Options

Intact Technical Supports

What Does Our Clients Say

Mitsubishi MR-J4

Laura Navas

Great product!

2019/12/01

Keyence sensor

EQDR SALES

Original and fast!

2020/02/22

Need Professional Tech Support or a Quote?

  • Our senior engineers provide 1-on-1 selection & configuration advice
  • 100% genuine products guaranteed with rapid global delivery
UP
WhatsApp