Allen-Bradley 1756-OB8 ControlLogix digital output module

Series#: AllenBradley

Product Details

  • Allen-Bradley 1756-OB8 ControlLogix digital output module
  • Device type: ControlLogix digital output module; Outputs: 8 outputs, 4 points per common
  • Voltage category / operating range: 12/24 V DC sourcing; 10–30 V DC; Compatible RTBs: 1756-TBNH or 1756-TBSH (20 positions)

Specification

Allen-Bradley 1756-OB8 — ControlLogix digital output module.

Technical Specifications

SpecificationDetails
ManufacturerAllen-Bradley
Catalog number1756-OB8
Device typeControlLogix digital output module
Outputs8 outputs, 4 points per common
Voltage category / operating range12/24 V DC sourcing; 10–30 V DC
Compatible RTBs1756-TBNH or 1756-TBSH (20 positions)

Ordering & Compatibility

Check the exact output voltage, isolation arrangement and terminal block before replacing a module.

Match the complete catalog number, hardware series, installed configuration and required accessories before ordering. Unit condition, package contents, delivery and warranty must be confirmed in the quotation.

1756-OB8 Procurement Questions

How many outputs does the 1756-OB8 provide and how are they grouped?

The module provides 8 outputs, arranged as 4 points/common.

What operating voltage range does the 1756-OB8 support?

The voltage category is 12/24V DC source, and the operating voltage range is 10…30V DC.

What are the maximum current ratings per point and per module?

Current per point, max is 2 A @ 60 °C (140 °F), and current per module, max is 8 A @ 60 °C (140 °F).

What output delay times should I expect when switching?

Output delay time is 1 ms max Off to On and 2 ms max On to Off.

Are the outputs fused on this module?

The module is not protected; a fused IFM is recommended to help protect outputs.

What states can points take in Fault mode?

States in Fault mode per point can be Hold last state, On or Off, with Off as the default.

Outputs
8 (4 points/common)
Pilot duty
Yes
Voltage category
12/24V DC source
Operating voltage range
10…30V DC
Output delay time — Off to On
1 ms max
Output delay time — On to Off
2 ms max
Current draw @ 5.1V
165 mA
Current draw @ 24V
2 mA
Total backplane power
0.89 W
Power dissipation, max
2.5 W @ 60 °C (140 °F)
Thermal dissipation
8.53 BTU/hr
Off-state leakage current, max
1 mA per point
On-state voltage drop, max
1.2V DC @ 2 A
Current per point, max
2 A @ 60 °C (140 °F)
Current per module, max
8 A @ 60 °C (140 °F)
Surge current per point
4 A for 10 ms each, repeatable every 1 s @ 60 °C (140 °F)
Load current, min
2 mA per point
Scheduled outputs
Synchronization within 16.7 s max, reference to the Coordinated System Time
States in Fault mode per point
Hold last state, On or Off (Off is default)
States in Program mode per point
Hold last state, On or Off (Off is default)
Isolation voltage
250V (continuous), basic insulation type, outputs-to-backplane, and output group-to-group No isolation between individual group outputs
Module keying
Electronic, software configurable
Fusing
Not protected. A fused IFM is recommended to help protect outputs
RTB keying
User-defined mechanical
Slot width
1
Wire category
1(1)
Enclosure type
None (open-style)
Temperature code
T4

Technical specifications are based on the linked manufacturer references.

Unmatched Customer Service

After Hours Shipping

Real Time Order Tracking

Flexible Delivery Options

Intact Technical Supports

What Does Our Clients Say

Mitsubishi MR-J4

Laura Navas

Great product!

2019/12/01

Keyence sensor

EQDR SALES

Original and fast!

2020/02/22

Need Professional Tech Support or a Quote?

  • Our senior engineers provide 1-on-1 selection & configuration advice
  • 100% genuine products guaranteed with rapid global delivery
UP
WhatsApp