1756-OB8I Procurement Questions
How many outputs does the 1756-OB8I provide, and are they isolated from each other?
The module has 8 individually isolated outputs.
What operating voltage range does the 1756-OB8I accept?
The voltage category is 12/24V DC source, and the operating voltage range is 10…30V DC.
What are the maximum current ratings per point and per module?
Current per point is 2 A @ 60 °C (140 °F), and current per module is 16 A @ 60 °C (140 °F).
Are the outputs protected against overcurrent?
The outputs are not protected; a fused IFM is recommended to protect outputs.
What output delay times should I expect?
Output delay time is 1 ms max Off to On and 2 ms max On to Off.
What states can each point take in Fault mode and Program mode?
In both Fault mode and Program mode, each point can hold last state, On or Off, with Off as the default.
- Outputs
- 8 individually isolated
- Pilot duty
- 2A
- Voltage category
- 12/24V DC source
- Operating voltage range
- 10…30V DC
- Output delay time — Off to On
- 1 ms max
- Output delay time — On to Off
- 2 ms max
- Current draw @ 5.1V
- 165 mA
- Current draw @ 24V
- 2 mA
- Total backplane power
- 0.89 W
- Power dissipation, max
- 4.6W @ 60 °C (140 °F)
- Thermal dissipation
- 15.70 BTU/hr
- Off-state leakage current, max
- 0.5 mA per point
- On-state voltage drop, max
- 0.5V DC @ 2 A
- Current per point, max
- 2 A @ 60 °C (140 °F)
- Current per module, max
- 16 A @ 60 °C (140 °F)
- Surge current per point
- 4 A for 10 ms each, repeatable every 1 s @ 60 °C (140 °F)
- Load current, min
- 2 mA
- Scheduled outputs
- Synchronization within 16.7 s max, reference to the Coordinated System Time
- States in Fault mode per point
- Hold last state, On or Off (Off is default)
- States in Program mode per point
- Hold last state, On or Off (Off is default)
- Isolation voltage
- 250V (continuous), reinforced insulation type, outputs-to-backplane 250V (continuous), basic insulation type, output-to-output Routine tested @ 1350V AC for 2 s
- Module keying
- Electronic, software configurable
- Fusing
- Not protected. A fused IFM is recommended to protect outputs
- RTB keying
- User-defined mechanical
- Slot width
- 1
- Wire category
- 1(1)
- North American temperature code
- T4A
- Enclosure type
- None (open-style)
Technical specifications are based on the linked manufacturer references.