Allen-Bradley 1756-OB16IS ControlLogix digital output module

Series#: AllenBradley

Product Details

  • Allen-Bradley 1756-OB16IS ControlLogix digital output module
  • Device type: ControlLogix digital output module; Outputs: 16 individually isolated outputs, 8 scheduled
  • Voltage category / operating range: 12/24 V DC sink/source; 10–30 V DC; Output fusing: Not protected; fused IFM can be used

Specification

Allen-Bradley 1756-OB16IS — ControlLogix digital output module.

Technical Specifications

SpecificationDetails
ManufacturerAllen-Bradley
Catalog number1756-OB16IS
Device typeControlLogix digital output module
Outputs16 individually isolated outputs, 8 scheduled
Voltage category / operating range12/24 V DC sink/source; 10–30 V DC
Output fusingNot protected; fused IFM can be used

Ordering & Compatibility

Check the exact output voltage, isolation arrangement and terminal block before replacing a module.

Match the complete catalog number, hardware series, installed configuration and required accessories before ordering. Unit condition, package contents, delivery and warranty must be confirmed in the quotation.

1756-OB16IS Procurement Questions

How many outputs does the 1756-OB16IS provide, and how many are scheduled?

The module has 16 individually isolated outputs, of which 8 are scheduled.

What operating voltage range does the 1756-OB16IS support?

The voltage category is 12/24V DC sink/source, and the operating voltage range is 10…30V DC.

What are the output delay times for this module?

Output delay time is 1 ms max Off to On and 2 ms max On to Off.

What is the maximum current per point and per module?

Current per point, max is 2 A @ 30 °C (86 °F); 1 A @ 60 °C (140 °F) (linear derating). Current per module, max is 4 A @ 60 °C (140 °F) (linear derating); 8 A @ 30 °C (86 °F).

What output states can be configured in Fault mode and Program mode?

Per point, both Fault mode and Program mode can be set to Hold last state, On or Off (Off is default).

Is the module protected against output faults, and which terminal blocks are used for agency-certified systems?

Outputs are not protected; a fused IFM can be used to help protect outputs (see publication 1492-TD008). The ControlLogix system has been agency certified using only the ControlLogix RTBs, that is, 1756-TBCH, 1756-TBNH, 1756-TBSH, and 1756-TBS6H.

Outputs
16 individually isolated, 8 scheduled
Pilot duty
2 A (DC-13SQ)
Voltage category
12/24V DC sink/source
Operating voltage range
10…30V DC
Output delay time — Off to On
1 ms max
Output delay time — On to Off
2 ms max
Current draw @ 5.1V
350 mA
Current draw @ 24V
2.5 mA
Total backplane power
1.8 W
Power dissipation, max
3.6 W @ 60 °C (140 °F)
Thermal dissipation
12.28 BTU/hr
Off-state leakage current per point, max
0.5 mA per point
On-state voltage drop, max
1.2V DC @ 2 A
Current per point, max
2 A @ 30 °C (86 °F); 1 A @ 60 °C (140 °F) (linear derating)
Current per module, max
4 A @ 60 °C (140 °F) (linear derating); 8 A @ 30 °C (86 °F)
Surge current per point
4 A for 10 ms per point, repeatable every 2 s
Load current, min
1 mA per point
Scheduled outputs
Synchronization within 16.7 s max, reference to the Coordinated System Time
States in Fault mode per point
Hold last state, On or Off (Off is default)
States in Program mode per point
Hold last state, On or Off (Off is default)
Isolation voltage
250V (continuous), basic insulation type, outputs-to-backplane, and output-to-output
Module keying
Electronic, software configurable
Fusing
Not protected. A fused IFM can be used to help protect outputs. See publication 1492-TD008. However, the ControlLogix system has been agency certified using only the ControlLogix RTBs, that is, 1756-TBCH, 1756-TBNH, 1756-TBSH, and 1756-TBS6H. Any application that requires agency certification of the ControlLogix system that uses other wiring termination methods can require application-specific approval by the certifying agency.
RTB keying
User-defined mechanical
Slot width
1
Wire category
1(2)
Wire type
Copper
Enclosure type
None (open-style)
Temperature code
T4

Technical specifications are based on the linked manufacturer references.

Unmatched Customer Service

After Hours Shipping

Real Time Order Tracking

Flexible Delivery Options

Intact Technical Supports

What Does Our Clients Say

Mitsubishi MR-J4

Laura Navas

Great product!

2019/12/01

Keyence sensor

EQDR SALES

Original and fast!

2020/02/22

Need Professional Tech Support or a Quote?

  • Our senior engineers provide 1-on-1 selection & configuration advice
  • 100% genuine products guaranteed with rapid global delivery
UP
WhatsApp