Allen-Bradley 1756-OC8 ControlLogix digital output module

Series#: AllenBradley

Product Details

  • Allen-Bradley 1756-OC8 ControlLogix digital output module
  • Device type: ControlLogix digital output module; Outputs: 8 outputs, 4 points per group
  • Voltage category / operating range: 48 V DC sourcing; 30–60 V DC

Specification

Allen-Bradley 1756-OC8 — ControlLogix digital output module.

Technical Specifications

SpecificationDetails
ManufacturerAllen-Bradley
Catalog number1756-OC8
Device typeControlLogix digital output module
Outputs8 outputs, 4 points per group
Voltage category / operating range48 V DC sourcing; 30–60 V DC

Ordering & Compatibility

Check the exact output voltage, isolation arrangement and terminal block before replacing a module.

Match the complete catalog number, hardware series, installed configuration and required accessories before ordering. Unit condition, package contents, delivery and warranty must be confirmed in the quotation.

1756-OC8 Procurement Questions

What voltage range can the 1756-OC8 outputs operate on?

The module is a 48V DC source voltage category with an operating voltage range of 30…60V DC.

How much current can each point and the whole module carry?

Current per point is 2 A max and current per module is 8 A max, both at 60 °C (140 °F).

Are the outputs protected against overcurrent?

No. The outputs are not protected, and a fused IFM is recommended to help protect outputs.

What happens to the outputs when the module enters Fault or Program mode?

Per point, states in Fault mode and in Program mode can be Hold last state, On or Off, with Off as the default.

What is the output switching delay?

Output delay time is 1 ms max Off to On and 2 ms max On to Off.

How is isolation specified between outputs and the backplane?

Isolation voltage is 250V (continuous), basic insulation type, outputs-to-backplane and output group-to-group, with no isolation between individual group outputs.

Outputs
8 (4 points/group)
Pilot duty
2A
Voltage category
48V DC source
Operating voltage range
30…60V DC
Output delay time — Off to On
1 ms, max
Output delay time — On to Off
2 ms, max
Current draw @ 5.1V
165 mA
Current draw @ 24V
2 mA
Total backplane power
0.89 W
Power dissipation, max
4.9 W @ 60 °C (140 °F)
Thermal dissipation
16.71 BTU/hr
Off-state leakage current, max
1 mA per point
On-state voltage drop, max
2V DC @ 2 A
Current per point, max
2 A @ 60 °C (140 °F)
Current per module, max
8 A @ 60 °C (140 °F)
Surge current per point
4 A for 10 ms per point, repeatable every 1 s @ 60 °C (140 °F)
Load current, min
2 mA per point
Scheduled outputs
Synchronization within 16.7 s max, reference to the Coordinated System Time
States in Fault mode per point
Hold last state, On or Off (Off is default)
States in Program mode per point
Hold last state, On or Off (Off is default)
Isolation voltage
250V (continuous), basic insulation type, outputs-to-backplane, and output group-to-group No isolation between individual group outputs
Module keying
Electronic, software configurable
Fusing
Not protected. A fused IFM is recommended to help protect outputs
RTB keying
User-defined mechanical
Slot width
1
Wire category
1(1)
Enclosure type
None (open-style)
Temperature code
T4

Technical specifications are based on the linked manufacturer references.

Unmatched Customer Service

After Hours Shipping

Real Time Order Tracking

Flexible Delivery Options

Intact Technical Supports

What Does Our Clients Say

Mitsubishi MR-J4

Laura Navas

Great product!

2019/12/01

Keyence sensor

EQDR SALES

Original and fast!

2020/02/22

Need Professional Tech Support or a Quote?

  • Our senior engineers provide 1-on-1 selection & configuration advice
  • 100% genuine products guaranteed with rapid global delivery
UP
WhatsApp