Allen-Bradley 1756-OG16 — ControlLogix digital output module.
| Specification | Details |
|---|---|
| Manufacturer | Allen-Bradley |
| Catalog number | 1756-OG16 |
| Device type | ControlLogix digital output module |
| Outputs | 16 outputs, 8 points per group |
| Voltage category / operating range | 5 V DC TTL (Low=True); 4.5–5.5 V DC source |
Check the exact output voltage, isolation arrangement and terminal block before replacing a module.
Match the complete catalog number, hardware series, installed configuration and required accessories before ordering. Unit condition, package contents, delivery and warranty must be confirmed in the quotation.
The module uses a 5V DC TTL voltage category with Low=True.
The operating voltage range is 4.5…5.5V DC source with 50 mV P-P ripple max.
Load current per point, max is 24 mA, and load current per module, max is 384 mA. Continuous current, max is also 24 mA.
The module is not protected; a fused IFM is recommended to help protect outputs.
Per point, both Fault mode and Program mode can be set to Hold last state, On or Off, with Off as the default.
Off to On (5V-to-0V DC transition) is 45 µs nom/450 µs max, and On to Off (0V-to-5V DC transition) is 145 µs nom/700 µs max.
Technical specifications are based on the linked manufacturer references.