Allen-Bradley 1756-OG16 ControlLogix digital output module

Series#: AllenBradley

Product Details

  • Allen-Bradley 1756-OG16 ControlLogix digital output module
  • Device type: ControlLogix digital output module; Outputs: 16 outputs, 8 points per group
  • Voltage category / operating range: 5 V DC TTL (Low=True); 4.5–5.5 V DC source

Specification

Allen-Bradley 1756-OG16 — ControlLogix digital output module.

Technical Specifications

SpecificationDetails
ManufacturerAllen-Bradley
Catalog number1756-OG16
Device typeControlLogix digital output module
Outputs16 outputs, 8 points per group
Voltage category / operating range5 V DC TTL (Low=True); 4.5–5.5 V DC source

Ordering & Compatibility

Check the exact output voltage, isolation arrangement and terminal block before replacing a module.

Match the complete catalog number, hardware series, installed configuration and required accessories before ordering. Unit condition, package contents, delivery and warranty must be confirmed in the quotation.

1756-OG16 Procurement Questions

What logic polarity does the 1756-OG16 use?

The module uses a 5V DC TTL voltage category with Low=True.

What supply voltage and ripple does the module require?

The operating voltage range is 4.5…5.5V DC source with 50 mV P-P ripple max.

How much current can each point and the whole module carry?

Load current per point, max is 24 mA, and load current per module, max is 384 mA. Continuous current, max is also 24 mA.

Are the outputs protected against faults?

The module is not protected; a fused IFM is recommended to help protect outputs.

What output states can be configured in Fault and Program modes?

Per point, both Fault mode and Program mode can be set to Hold last state, On or Off, with Off as the default.

What are the output delay times for a resistive load?

Off to On (5V-to-0V DC transition) is 45 µs nom/450 µs max, and On to Off (0V-to-5V DC transition) is 145 µs nom/700 µs max.

Outputs
16 (8 points/group)
Voltage category
5V DC TTL (Low=True)(1)
Operating voltage range
4.5…5.5V DC source, 50 mV P-P ripple max
Output delay time (resistive load) — Off to On (5V-to-0V DC transition)
45 µs nom/450 µs max
Output delay time (resistive load) — On to Off (0V-to-5V DC transition)
145 µs nom/700 µs max
Current draw @ 5.1V
210 mA
Current draw @ 24V
2 mA
Total backplane power
1.12 W
Power dissipation, max
1.5 W @ 60 °C (140 °F)
Thermal dissipation
5.2 BTU/hr @ 60 °C (140 °F)
Off-state leakage current per point, max
0.1 mA per point
On-state voltage drop, max
0.4V DC
Continuous current, max
24 mA
Load current per point, max
24 mA
Load current per module, max
384 mA
Load current
0.15 mA
Scheduled outputs
Synchronization within 16.7 s max, reference to the Coordinated System Time
States in Fault mode per point
Hold last state, On or Off (Off is default)
States in Program mode per point
Hold last state, On or Off (Off is default)
Isolation voltage
250V (continuous), basic insulation type, outputs-to-backplane, and output group-to-group No isolation between individual group outputs
Module keying
Electronic, software configurable
Fusing
Not protected. A fused IFM is recommended to help protect outputs.
RTB keying
User-defined mechanical
Slot width
1
Wire category
2(2)
Enclosure type
None (open-style)
Temperature code
T4

Technical specifications are based on the linked manufacturer references.

Unmatched Customer Service

After Hours Shipping

Real Time Order Tracking

Flexible Delivery Options

Intact Technical Supports

What Does Our Clients Say

Mitsubishi MR-J4

Laura Navas

Great product!

2019/12/01

Keyence sensor

EQDR SALES

Original and fast!

2020/02/22

Need Professional Tech Support or a Quote?

  • Our senior engineers provide 1-on-1 selection & configuration advice
  • 100% genuine products guaranteed with rapid global delivery
UP
WhatsApp