Allen-Bradley 1756-OV16E ControlLogix digital output module

Series#: AllenBradley

Product Details

  • Allen-Bradley 1756-OV16E ControlLogix digital output module
  • Device type: ControlLogix digital output module; Outputs: 16 electronically fused outputs, 8 points per group
  • Voltage category / operating range: 12/24 V DC sinking; 10–30 V DC

Specification

Allen-Bradley 1756-OV16E — ControlLogix digital output module.

Technical Specifications

SpecificationDetails
ManufacturerAllen-Bradley
Catalog number1756-OV16E
Device typeControlLogix digital output module
Outputs16 electronically fused outputs, 8 points per group
Voltage category / operating range12/24 V DC sinking; 10–30 V DC

Ordering & Compatibility

Check the exact output voltage, isolation arrangement and terminal block before replacing a module.

Match the complete catalog number, hardware series, installed configuration and required accessories before ordering. Unit condition, package contents, delivery and warranty must be confirmed in the quotation.

1756-OV16E Procurement Questions

How many outputs does the 1756-OV16E provide and how are they grouped?

The module has 16 electronically fused outputs arranged as 8 points/group.

What DC voltage range can the 1756-OV16E outputs operate on?

The voltage category is 12/24V DC sink, and the operating voltage range is 10…30V DC.

What are the maximum current ratings per point and per module?

Current per point, max is 1 A @ 60 °C (140 °F), and current per module, max is 8 A @ 60 °C (140 °F).

What output delay times should I expect when switching?

Off to On delay is 75 µs nom/1 ms max, and On to Off delay is 360 µs nom/1 ms max.

What states can each point take in Fault mode and Program mode?

In both Fault mode and Program mode, each point can be set to Hold last state, On or Off, with Off as the default.

How is the module keyed and fused?

Module keying is electronic and software configurable, and fusing is electronic per group.

Outputs
16 electronically fused (8 points/group)
Pilot duty
1 A (DC-13/SR)
Voltage category
12/24V DC sink
Output delay time — Off to On
75 µs nom/1 ms max
Output delay time — On to Off
360 µs nom/1 ms max
Operating voltage range
10…30V DC
Current draw @ 5.1V
210 mA
Current draw @ 24V
2 mA
Total backplane power
1.12 W
Power dissipation, max
6.72 W @ 60 °C (140 °F)
Thermal dissipation
22.94 BTU/hr
Off-state leakage current per point, max
1 mA per point
On-state voltage drop, max
700 mV DC @ 1 A
Current per point, max
1 A @ 60 °C (140 °F)
Current per module, max
8 A @ 60 °C (140 °F)
Surge current per point
2 A for 10 ms per Point, repeatable every 2 s @ 60 °C (140 °F)
Load current, min
2 mA per point
Scheduled outputs
Synchronization within 16.7 s max, reference to the Coordinated System Time
States in Fault mode per point
Hold last state, On or Off (Off is default)
States in Program mode per point
Hold last state, On or Off (Off is default)
Isolation voltage
250V (continuous), basic insulation type, outputs-to-backplane, and output group-to-group No isolation between individual group outputs
Module keying
Electronic, software configurable
Fusing
Electronically fused per group
RTB keying
User-defined mechanical
Slot width
1
Wire category
1(1)
Enclosure type
None (open-style)
Temperature code
T4

Technical specifications are based on the linked manufacturer references.

Unmatched Customer Service

After Hours Shipping

Real Time Order Tracking

Flexible Delivery Options

Intact Technical Supports

What Does Our Clients Say

Mitsubishi MR-J4

Laura Navas

Great product!

2019/12/01

Keyence sensor

EQDR SALES

Original and fast!

2020/02/22

Need Professional Tech Support or a Quote?

  • Our senior engineers provide 1-on-1 selection & configuration advice
  • 100% genuine products guaranteed with rapid global delivery
UP
WhatsApp