Allen-Bradley 1756-OW16I ControlLogix digital output module

Series#: AllenBradley

Product Details

  • Allen-Bradley 1756-OW16I ControlLogix digital output module
  • Device type: ControlLogix digital output module; Outputs: 16 normally-open individually isolated relay outputs
  • Voltage category / operating range: 10–240 V AC; 5–125 V DC

Specification

Allen-Bradley 1756-OW16I — ControlLogix digital output module.

Technical Specifications

SpecificationDetails
ManufacturerAllen-Bradley
Catalog number1756-OW16I
Device typeControlLogix digital output module
Outputs16 normally-open individually isolated relay outputs
Voltage category / operating range10–240 V AC; 5–125 V DC

Ordering & Compatibility

Check the exact output voltage, isolation arrangement and terminal block before replacing a module.

Match the complete catalog number, hardware series, installed configuration and required accessories before ordering. Unit condition, package contents, delivery and warranty must be confirmed in the quotation.

1756-OW16I Procurement Questions

What load voltages and currents can the 1756-OW16I outputs switch?

The operating voltage range is 5…125V DC and 10…240V AC. The contact current rating is 1 A @ 5…30V DC; 0.5 A @ 48V DC; 0.22 A @ 125V DC; 1.5 A @ 120V AC 50/60 Hz; 0.75 A @ 240V AC 50/60 Hz.

What is the minimum load current and off-state leakage per point?

Minimum load current is 10 mA per point, and off-state leakage current per point is 1.5 mA per point max.

How fast do the outputs switch, and what is the maximum switching frequency?

Output delay time is 10 ms max Off to On and 10 ms max On to Off. Maximum switching frequency is 1 operation/3 s (0.3 Hz at rated load).

What contact life can be expected?

Expected contact life is 300,000 cycles resistive and 100,000 cycles inductive.

What are the default states in Fault and Program modes?

States in Fault mode per point and States in Program mode per point are each Hold last state, On or Off, with Off as the default.

Are the outputs fused, and which terminal blocks are used for agency-certified systems?

The module is not protected; a fused IFM can be used to help protect outputs. The ControlLogix system has been agency certified using only the ControlLogix RTBs, that is, 1756-TBCH, 1756-TBNH, 1756-TBSH, and 1756-TBS6H.

Outputs
16 N.O. individually isolated
Pilot duty
C300/R150
Operating voltage range
5…125V DC; 10…240V AC
Output delay time — Off to On
10 ms max
Output delay time — On to Off
10 ms max
Current draw @ 5.1V
150 mA
Current draw @ 24V
150 mA
Total backplane power
4.4 W
Power dissipation, max
4.5 W @ 60 °C (140 °F)
Thermal dissipation
15.35 BTU/hr
Off-state leakage current per point, max
1.5 mA per point
Minimum load current
10 mA per point
Initial contact resistance, max
100 mΩ @ 6V 1 A
Switching frequency, max
1 operation/3 s (0.3 Hz at rated load)
Bounce time, mean
1.2 ms
Expected contact life
300,000 cycles resistive; 100,000 cycles inductive
Scheduled outputs
Synchronization within 16.7 s max, reference to the Coordinated System Time
States in Fault mode per point
Hold last state, On or Off (Off is default)
States in Program mode per point
Hold last state, On or Off (Off is default)
Isolation voltage
250V (continuous), basic insulation type, outputs-to-backplane, and output-to-output
Module keying
Electronic, software configurable
Fusing
Not protected. A fused IFM can be used to help protect outputs. See publication 1492-TD008. However, the ControlLogix system has been agency certified using only the ControlLogix RTBs, that is, 1756-TBCH, 1756-TBNH, 1756-TBSH, and 1756-TBS6H. Any application that requires agency certification of the ControlLogix system that uses other wiring termination methods can require application-specific approval by the certifying agency.
RTB keying
User-defined mechanical
Slot width
1
Wire category
1(1)
Enclosure type
None (open-style)
North American temperature code
T4A
Contact current rating
1 A @ 5…30V DC; 0.5 A @ 48V DC; 0.22 A @ 125V DC; 1.5 A @ 120V AC 50/60 Hz; 0.75 A @ 240V AC 50/60 Hz

Technical specifications are based on the linked manufacturer references.

Unmatched Customer Service

After Hours Shipping

Real Time Order Tracking

Flexible Delivery Options

Intact Technical Supports

What Does Our Clients Say

Mitsubishi MR-J4

Laura Navas

Great product!

2019/12/01

Keyence sensor

EQDR SALES

Original and fast!

2020/02/22

Need Professional Tech Support or a Quote?

  • Our senior engineers provide 1-on-1 selection & configuration advice
  • 100% genuine products guaranteed with rapid global delivery
UP
WhatsApp