Allen-Bradley 1756-OX8I ControlLogix digital output module

Series#: AllenBradley

Product Details

  • Allen-Bradley 1756-OX8I ControlLogix digital output module
  • Device type: ControlLogix digital output module; Outputs: 8 isolated N.O./N.C. relay output sets
  • Voltage category / operating range: 10–240 V AC; 5–125 V DC

Specification

Allen-Bradley 1756-OX8I — ControlLogix digital output module.

Technical Specifications

SpecificationDetails
ManufacturerAllen-Bradley
Catalog number1756-OX8I
Device typeControlLogix digital output module
Outputs8 isolated N.O./N.C. relay output sets
Voltage category / operating range10–240 V AC; 5–125 V DC

Ordering & Compatibility

Check the exact output voltage, isolation arrangement and terminal block before replacing a module.

Match the complete catalog number, hardware series, installed configuration and required accessories before ordering. Unit condition, package contents, delivery and warranty must be confirmed in the quotation.

1756-OX8I Procurement Questions

What output configuration does the 1756-OX8I provide?

It provides 8 N.O. and 8 N.C. individually isolated outputs, with two points per group.

What operating voltage range does this module support?

The operating voltage range is 5…125V DC and 10…240V AC.

What contact current ratings apply at the different voltages?

The contact current rating is 1 A @ 5…30V DC; 0.5 A @ 48V DC; 0.22 A @ 125V DC; 1.5 A @ 120V AC 50/60 Hz; 0.75 A @ 240VAC 50/60 Hz.

Are the outputs protected against overcurrent?

No. The outputs are not protected, and a fused IFM is recommended to help protect outputs.

What is the minimum load current per point?

The minimum load current is 10 mA per point.

What states can each point take in Fault mode?

Each point can hold last state, On or Off, with Off as the default.

Outputs
8 N.O. 8 N.C. individually isolated (two points per group)
Pilot duty
C300/R150
Operating voltage range
5…125V DC; 10…240V AC
Contact current rating
1 A @ 5…30V DC; 0.5 A @ 48V DC; 0.22 A @ 125V DC; 1.5 A @ 120V AC 50/60 Hz; 0.75 A @ 240VAC 50/60 Hz
Output delay time — Off to On
13 ms max
Output delay time — On to Off
13 ms max
Current draw @ 5.1V
100 mA
Current draw @ 24V
100 mA
Total backplane power
2.9 W
Power dissipation, max
3.1 W @ 60 °C (140 °F)
Thermal dissipation
10.57 BTU/hr
Off-state leakage current per point, max
0 mA
Minimum load current
10 mA per point
Initial contact resistance, max
100 mΩ @ 6V 1 A
Switching frequency, max
1 operation/3 s (0.3 Hz at rated load)
Bounce time, mean
1.2 ms
Expected contact life
300,000 cycles resistive 100,000 cycles inductive
Scheduled outputs
Synchronization within 16.7 s max, reference to the Coordinated System Time
States in Fault mode per point
Hold last state, On or Off (Off is default)
States in Program mode per point
Hold last state, On or Off (Off is default)
Isolation voltage
250V (continuous), basic insulation type, outputs-to-backplane, and output-to-output
Module keying
Electronic, software configurable
Fusing
Not protected. A fused IFM is recommended to help protect outputs.
RTB keying
User-defined mechanical
Slot width
1
Wire category
1(1)
Enclosure type
None (open-style)
North American temperature code
T4A

Technical specifications are based on the linked manufacturer references.

Unmatched Customer Service

After Hours Shipping

Real Time Order Tracking

Flexible Delivery Options

Intact Technical Supports

What Does Our Clients Say

Mitsubishi MR-J4

Laura Navas

Great product!

2019/12/01

Keyence sensor

EQDR SALES

Original and fast!

2020/02/22

Need Professional Tech Support or a Quote?

  • Our senior engineers provide 1-on-1 selection & configuration advice
  • 100% genuine products guaranteed with rapid global delivery
UP
WhatsApp