  • Device type: ControlLogix analog voltage/current input module
  • Channels / wiring: 8 single-ended, 4 differential or 2 high-speed differential

Specification

Allen-Bradley 1756-IF8 — ControlLogix analog voltage/current input module.

Technical Specifications

SpecificationDetails
ManufacturerAllen-Bradley
Catalog number1756-IF8
Device typeControlLogix analog voltage/current input module
Channels / wiring8 single-ended, 4 differential or 2 high-speed differential

Ordering & Compatibility

Do not confuse single-ended channel count with differential channel count.

Match the complete catalog number, hardware series, installed configuration and required accessories before ordering. Unit condition, package contents, delivery and warranty must be confirmed in the quotation.

1756-IF8 Procurement Questions

What input configurations does the 1756-IF8 support?

The module provides eight single-ended, four differential, or two high-speed differential inputs.

Which input ranges can I use?

The stated input ranges are ±10V, 0…10V, 0…5V and 0…20 mA.

Does the catalog record pin a specific series, and do backplane current values differ?

The catalog record does not pin a series. Current draw @ 5.1V is carried split: Series A 150 mA and Series B 200 mA; current draw @ 24V is Series A 40 mA and Series B 30 mA.

What isolation is specified between inputs and backplane?

Isolation voltage is carried split by series: Series A 250V (continuous), Reinforced insulation type, Inputs to Backplane; Series B 250V (continuous), Basic insulation type, Inputs to Backplane. In both cases there is no isolation between individual inputs.

What overvoltage protection is specified?

Maximum overvoltage protection is 30V DC for voltage and 8V DC for current.

Which terminal blocks are listed for this module?

The removable terminal block options listed are 1756-TBCH and 1756-TBS6H, with user-defined mechanical RTB keying.

Inputs
Eight single-ended; Four differential; Two high-speed differential
Input range
±10V; 0…10V; 0…5V; 0…20 mA
Resolution
±10.25V: 320 µV/count (15 bits plus sign bipolar); 0…10.25V: 160 µV/count (16 bits); 0…5.125V: 80 µV/count (16 bits); 0…20.5 mA: 0.32 µA/count (16 bits)
Current draw @ 5.1V
Series A: 150 mA;; Series B: 200 mA
Current draw @ 24V
Series A: 40 mA;; Series B: 30 mA
Total backplane power
Series A: 1.73 W;; Series B: 1.74 W
Voltage and current ratings
Series A: Input voltage range: -10…+10V Backplane: 5.1V DC, 150 mA max, 24V DC, 40 mA max Input current range: 4…20mA Limited to 100VA;; Series B: Input voltage range: -10…+10V Backplane: 5.1V DC, 200 mA max, 24V DC, 30 mA max Input current range: 0…20mA Limited to 100VA
Power consumption
Series A: 1.73 W; Series B: 1.74 W
Power dissipation
Series A: Voltage: 1.73 W, Current: 2.56 W; Series B: Voltage: 1.74 W, Current: 2.58 W
Thermal dissipation
Series A: Voltage: 5.89 BTU/hr, Current: 8.74 BTU/hr; Series B: Voltage: 5.94 BTU/hr, Current: 8.79 BTU/hr
Input impedance
Differential voltage: ≥10 MΩ; Current: 249 Ω
Open circuit detection time
Single-ended voltage: even-numbered channels go to positive full-scale reading within 5 s, odd-numbered channels go to negative full-scale reading within 5 s; Single-ended/differential current: negative full-scale reading within 5 s; Differential voltage: positive full-scale reading within 5 s
Overvoltage protection, max
Voltage: 30V DC; Current: 8V DC
Normal mode noise rejection
>80 dB @ 50/60 Hz(1)
Common mode noise rejection
>100 dB @ 50/60 Hz
Calibrated accuracy 25 °C (77 °F)
Voltage: Better than 0.05% of range Current: Better than 0.15% of range
Offset drift
45 µV/°C
Gain drift with temperature
Voltage: 15 ppm/°C; Current: 20 ppm/°C
Module error
Voltage: 0.1% of range; Current: 0.3% of range
Module input scan time, min
8 pt single-ended (floating point): 16…488 ms; 4 pt differential (floating point): 8…244 ms; 2 pt differential (floating point): 5…122 ms
Onboard data alarming
Yes
Scaling to engineering units
Yes
Real-time channel sampling
Yes
Data format
Integer mode (left justified, 2 s complement) IEEE 32-bit floating point
Module conversion method
Sigma-Delta
Isolation voltage
Series A: 250V (continuous), Reinforced insulation type, Inputs to Backplane. No isolation between individual Inputs.;; Series B: 250V (continuous), Basic(2) insulation type, Inputs to Backplane. No isolation between individual Inputs.
Module keying
Electronic, software configurable
RTB keying
User-defined mechanical
Slot width
1
Wire size
1756-TBCH Single wire connection: 0.33…2.1 mm2 (22…14 AWG) solid or stranded shielded copper wire, rated at 105 °C (221 °F) or greater, 1.2 mm (3/ 64 in.) insulation max. Double wire connection: 0.33…1.3 mm2 (22…16 AWG) solid or stranded copper wire, rated at 105 °C (221 °F) or greater, 1.2 mm (3/64 in.) insulation max. 1756-TBS6H Single wire connection: 0.33…2.1 mm2 (22…14 AWG) solid or stranded shielded copper wire, rated at 105 °C (221 °F) or greater, 1.2 mm (3/ 64 in.) insulation max.
Wiring category
2 - on signal ports(3)
Enclosure type
None (open-style)
Temperature code
T4

Technical specifications are based on the linked manufacturer references.

Unmatched Customer Service

After Hours Shipping

Real Time Order Tracking

Flexible Delivery Options

Intact Technical Supports

What Does Our Clients Say

Mitsubishi MR-J4

Laura Navas

Great product!

2019/12/01

Keyence sensor

EQDR SALES

Original and fast!

2020/02/22

Need Professional Tech Support or a Quote?

  • Our senior engineers provide 1-on-1 selection & configuration advice
  • 100% genuine products guaranteed with rapid global delivery
UP
WhatsApp