Allen-Bradley 1756-IF16 ControlLogix analog voltage/current input module

Series#: AllenBradley

Product Details

  • Allen-Bradley 1756-IF16 ControlLogix analog voltage/current input module
  • Device type: ControlLogix analog voltage/current input module; Channels / wiring: 16 single-ended, 8 differential or 4 high-speed differential
  • Channel isolation: No isolation between individual inputs

Specification

Allen-Bradley 1756-IF16 — ControlLogix analog voltage/current input module.

Technical Specifications

SpecificationDetails
ManufacturerAllen-Bradley
Catalog number1756-IF16
Device typeControlLogix analog voltage/current input module
Channels / wiring16 single-ended, 8 differential or 4 high-speed differential
Channel isolationNo isolation between individual inputs

Ordering & Compatibility

Confirm differential versus single-ended capacity and required input isolation.

Match the complete catalog number, hardware series, installed configuration and required accessories before ordering. Unit condition, package contents, delivery and warranty must be confirmed in the quotation.

1756-IF16 Procurement Questions

What input configurations does the 1756-IF16 support?

The module supports 16 single ended, 8 differential or 4 differential (high speed) inputs.

Which input ranges are available on this module?

The stated input range is ±10V; 0…10V; 0…5V; 0…20 mA.

Does the catalog record pin a series for this module, and why do some values appear in two versions?

The catalog record does not pin a series. Several specifications are carried split by series: current draw @ 5.1V is 150 mA for Series A and 200 mA for Series B; current draw @ 24V is 65 mA for Series A and 35 mA for Series B; total backplane power is 2.33 W for Series A and 1.86 W for Series B. The applicable value depends on the series of the module supplied.

What isolation does the module provide between inputs and the backplane?

Series A: 250V (continuous), Reinforced insulation type, Inputs-to-Backplane. Series B: 250V (continuous), Basic insulation type, Inputs-to-Backplane. In both cases there is no isolation between individual inputs.

What are the module input scan times?

16 pt single-ended: 16…488 ms; 8 pt differential: 8…244 ms; 4 pt differential: 5…122 ms.

Which removable terminal blocks are listed, and what wire sizes do they accept?

The listed removable terminal blocks are 1756-TBCH and 1756-TBS6H. For 1756-TBCH, single wire connection accepts 0.33…2.1 mm2 (22…14 AWG) solid or stranded shielded copper wire rated at 105 °C (221 °F) or greater with 1.2 mm (3/64 in.) insulation max, and double wire connection accepts 0.33…1.3 mm2 (22…16 AWG) solid or stranded copper wire rated at 105 °C (221 °F) or greater with 1.2 mm (3/64 in.) insulation max. For 1756-TBS6H, single wire connection accepts 0.33…2.1 mm2 (22…14 AWG) solid or stranded shielded copper wire rated at 105 °C (221 °F) or greater with 1.2 mm (3/64 in.) insulation max.

Inputs
16 single ended, 8 differential or 4 differential (high speed)
Input range
±10V; 0…10V; 0…5V; 0…20 mA
Resolution
320 µV/count (15 bits + sign bipolar) @ ±10.25V; 160 µV/count (16 bits) @ 0…10.25V; 80 µV/count (16 bits) @ 0…5.125V; 0.32 µA/count (16 bits) @ 0…20.5 mA
Current draw @ 5.1V
Series A: 150 mA;; Series B: 200 mA
Current draw @ 24V
Series A: 65 mA;; Series B: 35 mA
Total backplane power
Series A: 2.33 W;; Series B: 1.86 W
Voltage and current ratings
Series A: Input Voltage Range: -10…+10V Backplane: 5.1V DC, 150 mA max 24V DC, 65 mA max Input Current Range: 4…20mA Limited to 100VA;; Series B: Input Voltage Range: -10…+10V Backplane: 5.1V DC, 200 mA max 24V DC, 35 mA max Input Current Range: 0…20mA Limited to 100VA
Power consumption
Series A: 2.33 W; Series B: 1.86 W
Power dissipation
Series A: Voltage: 2.33 W, Current: 4.00 W; Series B: Voltage: 1.86 W, Current: 3.53 W
Thermal dissipation
Series A: Voltage: 7.93 BTU/hr, Current: 13.65 BTU/hr; Series B: Voltage: 6.35 BTU/hr, Current: 12.06 BTU/hr
Input impedance
Differential voltage: ≥10 MΩ; Current: 249 Ω
Open circuit detection time
Single-ended voltage: even-numbered channels go to positive full-scale reading within 5 s, odd-numbered channels go to negative full-scale reading within 5 s; Single-ended/differential current: negative full-scale reading within 5 s; Differential voltage: positive full-scale reading within 5 s
Overvoltage protection, max
Voltage: 30V DC; Current: 8V DC
Normal mode noise rejection
>80 dB @ 50/60 Hz(1)
Common mode noise rejection
>100 dB @ 50/60 Hz
Channel bandwidth
15 Hz (-3 dB)(1)
Calibrated accuracy 25 °C (77 °F)
Voltage: Better than 0.05% of range Current: Better than 0.15% of range
Offset drift
45 µV/°C
Gain drift with temperature
Voltage: 15 ppm/°C; Current: 20 ppm/°C
Module error
Voltage: 0.1% of range; Current: 0.3% of range
Module input scan time, min
16 pt single-ended: 16…488 ms; 8 pt differential: 8…244 ms; 4 pt differential: 5…122 ms
Onboard data alarming
Yes
Scaling to engineering units
Yes
Real-time channel sampling
Yes
Data format
Integer mode (left justified, 2 s complement) IEEE 32-bit floating point
Module conversion method
Sigma-Delta
Isolation voltage
Series A: 250V (continuous), Reinforced insulation type, Inputs-to-Backplane. No isolation between individual Inputs.;; Series B: 250V (continuous), Basic(2) insulation type, Inputs-to- Backplane. No isolation between individual Inputs.
Module keying
Electronic, software configurable
RTB keying
User-defined mechanical
Slot width
1
Wire size
1756-TBCH Single wire connection: 0.33…2.1 mm2 (22…14 AWG) solid or stranded shielded copper wire rated at 105 °C (221 °F), or greater, 1.2 mm (3/ 64 in.) insulation max. Double wire connection: 0.33…1.3 mm2 (22…16 AWG) solid or stranded copper wire rated at 105 °C (221 °F), or greater, 1.2 mm (3/64 in.) insulation max. 1756-TBS6H Single wire connection: 0.33…2.1 mm2 (22…14 AWG) solid or stranded shielded copper wire rated at 105 °C (221 °F), or greater, 1.2 mm (3/ 64 in.) insulation max.
Wire category
2 - on signal ports
Enclosure type
None (open-style)
Temperature code
T4

Technical specifications are based on the linked manufacturer references.

Unmatched Customer Service

After Hours Shipping

Real Time Order Tracking

Flexible Delivery Options

Intact Technical Supports

What Does Our Clients Say

Mitsubishi MR-J4

Laura Navas

Great product!

2019/12/01

Keyence sensor

EQDR SALES

Original and fast!

2020/02/22

Need Professional Tech Support or a Quote?

  • Our senior engineers provide 1-on-1 selection & configuration advice
  • 100% genuine products guaranteed with rapid global delivery
UP
WhatsApp